background image

SERIES 35-61

24 VAC Microprocessor Based Direct Spark

Ignition Control with Combustion Blower Relay

FEATURES

n

24 VAC Microprocessor Based DSI Control

n

System Diagnostic LED

n

Automatic reset 1 hour after lockou

t

n

Custom prepurge and interpurge timings

n

Flame sense test pins

DESCRIPTION

The Series 35-61 is a 24 VAC Microprocessor Based Direct Spark
Ignition Control designed for use in all types of heating applications. 
The control utilizes a microprocessor to continually and safely 
monitor, analyze and control the proper operation of the gas burner.
Value added  features such as combustion blower control, LED
diagnostics, automatic one hour reset, and flame current test pins
highlight the controls benefits.

®

35.61.02

Input Power

Control: 18-30 VAC 50/60 Hz 
(Class 2 Transformer)
Line: 120/240 VAC
(L1, IND contacts only)

Input Current Drain

300 mA @ 24 VAC, combustion
blower relay and gas valve relay 
energized (control only)

Gas Valve Rating

2.0A @ 24 VAC

Combustion Blower

3.0 FLA @ 120 VAC (6.0 LRA)

Rating

1.5 FLA @ 240 VAC (3.0 LRA)
1/4 H.P. Motor

Operating Temperature

-40ºF to +160ºF
-40ºC to +71ºC

Flame Sensitivity

.7µA minimum

Spark Rate

Line frequency (50/60 sparks/ sec.)

Enclosure

Gray (Noryl N-190) fire
retardent plastic

Moisture Resistance

Conformal coated to operate
to 95% R.H. Care must be
taken to protect module from
direct exposure to water

Tries for Ignition

One or three try versions
available

Trial for Ignition Periods

4.0,7.0,10.0, or 15.0 seconds
available

Prepurge & Interpurge

None, 15, or 30 seconds
depending on model. Without
prepurge there is a 3.5
second delay before the first
try for ignition.

SPECIFICATIONS

APPLICATIONS

n

Gas Furnaces

n

Boilers

n

Water Heaters

n

Other Similar Appliances

Agency Certifications

Software conforms to UL 1998 requirements

Design certified to ANSI Z21.20, CAN/CSA C22.2 
No. 199-M89

35-61, 24 VAC DSI Control with Blower Relay

Page 1

www.fenwalcontrols.com

1-800-FENWAL-1

Содержание 35-61 Series

Страница 1: ...VAC combustion blower relay and gas valve relay energized control only Gas Valve Rating 2 0A 24 VAC Combustion Blower 3 0 FLA 120 VAC 6 0 LRA Rating 1 5 FLA 240 VAC 3 0 LRA 1 4 H P Motor Operating Temperature 40ºF to 160ºF 40ºC to 71ºC Flame Sensitivity 7µA minimum Spark Rate Line frequency 50 60 sparks sec Enclosure Gray Noryl N 190 fire retardent plastic Moisture Resistance Conformal coated to o...

Страница 2: ...valve Multi try models will make two more attempts to relight the burner If the burner does not relight the control will go into lock out as noted above in Failure to Light If flame is re established normal operation resumes Combustion Airflow Problems Lockout Combustion air flow is continually monitored during an ignition sequence by the air flow switch PSW If during the initial call for heat the...

Страница 3: ...me current is the current which passes through the flame from the sensor to ground The minimum flame current necessary to keep the system from lockout is 7 microamps To measure flame current connect ananalog DC microammeter to the FC FC terminals per figure Meter should read 7 uA or higher If the meter reads below 0 on scale meter leads are reversed Disconnect power and reconnect meter leads for p...

Страница 4: ...fenwalcontrols com 1 800 FENWAL 1 Non Standard Configurations 9 Non Standard Configuration A 9 in this location of the part number i e 35 61 5 113 identifies this configuration as a non standard design The part number does not follow the part numbering system The 9XX is a sequential part number assigned by Fenwal Consult factory for operating characteristics of this control 901 FENWAL 400 MAIN STR...

Отзывы: