SERIES 35-61 X X X - X X X

Trial for Ignition Time (TFI)

1= 4 Seconds
3= 7 Seconds
5= 10 Seconds
7= 15 Seconds

Inter-PurgeTime

0= NONE (SINGLE TRY MODELS ONLY)
1= 15 Seconds
2= 30 Seconds

Pre-Purge Time

0= NONE
1= 15 Seconds
2= 30 Seconds

Number of Ignition Tries and 

Methods of Flame Sensing

0= Single Try - Local Sense
1= Single Try - Remote Sense
5= Three Tries - Local Sense
6= Three Tries  - Remote Sense

Inducer Control

0= No Post-Purge (w/input only)
1= No Post-Purge
2= 30 Second Post-Purge
3= 60 Second Post-Purge

Product Designation

5= Standard
8= Aftermartet Kit (may consist of control,

high voltage ignition wire,electrode and harness)

9= *Non-Standard Configuration

Special Options

n

No Cover

n

No Diagnostics

n

Recycle after Loss of Flame

DIMENSIONS

CONTROL CONFIGURATION

Description

Page 4

35-61, 24 VAC DSI Control with Blower Relay

www.fenwalcontrols.com 1-800-FENWAL-1

*Non-Standard Configurations  

9 = Non Standard Configuration 

A 9 in this location of the part number 
(i.e. 35-61 5           -113) identifies this 
configuration as a non-standard design.  
The part number does not follow the part  
numbering system.  The 9XX is a sequential
part number assigned by Fenwal.  Consult 
factory for operating characteristics of this 
control.

901

FENWAL
400 MAIN STREET, ASHLAND, MA 01721
TEL: (508) 881-2000 FAX: (508) 881-6729
www.fenwalcontrols.com

© 2003 Fenwal     Printed in 

U.S.A.    TAG

These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications subject to change without notice.
Should further information be desired or should particular problems arise which are not covered
sufficiently for the purchaser’s purposes, the matter should be referred to KIDDE-FENWAL,
Inc., Ashland, Massachusetts.

P/N 35.61.02

6/20/03

®

Содержание 35-61 Series

Страница 1: ...VAC combustion blower relay and gas valve relay energized control only Gas Valve Rating 2 0A 24 VAC Combustion Blower 3 0 FLA 120 VAC 6 0 LRA Rating 1 5 FLA 240 VAC 3 0 LRA 1 4 H P Motor Operating Temperature 40ºF to 160ºF 40ºC to 71ºC Flame Sensitivity 7µA minimum Spark Rate Line frequency 50 60 sparks sec Enclosure Gray Noryl N 190 fire retardent plastic Moisture Resistance Conformal coated to o...

Страница 2: ...valve Multi try models will make two more attempts to relight the burner If the burner does not relight the control will go into lock out as noted above in Failure to Light If flame is re established normal operation resumes Combustion Airflow Problems Lockout Combustion air flow is continually monitored during an ignition sequence by the air flow switch PSW If during the initial call for heat the...

Страница 3: ...me current is the current which passes through the flame from the sensor to ground The minimum flame current necessary to keep the system from lockout is 7 microamps To measure flame current connect ananalog DC microammeter to the FC FC terminals per figure Meter should read 7 uA or higher If the meter reads below 0 on scale meter leads are reversed Disconnect power and reconnect meter leads for p...

Страница 4: ...fenwalcontrols com 1 800 FENWAL 1 Non Standard Configurations 9 Non Standard Configuration A 9 in this location of the part number i e 35 61 5 113 identifies this configuration as a non standard design The part number does not follow the part numbering system The 9XX is a sequential part number assigned by Fenwal Consult factory for operating characteristics of this control 901 FENWAL 400 MAIN STR...

Отзывы: