F-35-60
October 2018
1
FEATURES
•
Safe start with DETECT-A-FLAME
®
flame sensing
technology
•
Custom pre-purge and inter-purge timings
*
•
Single or three trials for ignition
•
System diagnostic LED
•
Flame current test points
•
Local or remote flame sensing
•
Automatic reset
**
•
Alarm output (normally closed contact)
APPLICATIONS
•
Commercial cooking
•
Gas furnaces
•
Boilers
•
Water heaters
•
Other gas-fired appliances
DESCRIPTION
The 35-60 is a 24 VAC direct spark ignition (DSI) control
designed for use in all types of gas-fired appliances. The control
uses a microprocessor circuit to provide precise, repeatable
timing and operating sequences. On-board diagnostics with LED
output makes troubleshooting easy and ensures safe and
efficient operation.
Export Information (USA)
Jurisdiction: EAR
ECCN: EAR99
Agency Certifications
*
Pre-purge time cannot exceed inter-purge time on CE
Approved models.
**
Automatic reset is not allowed for CE Approved models.
*** EMC emission requirements shall be verified after
incorporation of the burner control system into the end use
appliance.
SPECIFICATIONS
Recognized under the UL component program, UL
372. Software certified to ANSI/UL 1998. UL File
MH8817
Design Certified to ANSI Z21.20,
CAN/CSA C22.2 No. 199-M89
CE Approved to EN 298-2012
Code Compliant to:
AS 4625 - 2008
AS 4622 - 2004
Input Power
Control: 18-30 VAC 50/60Hz
(Class 2 transformer)
Input Current
300 mA @24 VAC with gas valve
relay energized (control only)
Gas Valve
2.0A max @ 24 VAC
Operating Temperature
-40°F to +176°F
(-40°C to +80°C)
Storage Temperature
-40°F to +185°F
(-40°C to +85°C)
Flame Sensitivity
0.7
µ
A minimum
Flame Failure Response
0.8 seconds maximum
Flame Detector Self-check
Rate
Once per second minimum
Gas Types
Natural, LP, or manufactured
Spark Rate:
Remote
Local
50/60 sparks/sec
25/30 sparks/sec
Size (LxWxH)
with enclosure
5.69 x 3.94 x 1.87 inches
(14.45 x 10.01 x 4.75 cm)
Moisture Resistance
Conformal coated to operate non-
condensing to 95% R.H. Module
should not be exposed to water
Ingress Protection
Not rated, protection provided by
appliance in which it is installed
Tries for Ignition
One or three try versions available
Trial for Ignition Periods
4, 7, 10, 15 seconds available
Pre-purge and
Inter-purge Timings
0, 15 or 30 seconds available
SERIES 35-60
24 VAC Microprocessor-Based
Direct Spark Ignition Control
R