background image

Fenwal Controls 
400 Main Street 
Ashland, MA  01721 
Tel. (508) 881-2000  

© 

Kidde-Fenwal Inc.   06-237657-001 

 Rev A

C

 

EU DECLARATION OF CONFORMITY 

We 

Company Name: 

 

Kidde-Fenwal Inc. 

Postal Address: 

400 Main Street 

City and Post Code:  

Ashland, MA 01721 

Tel:   

508-881-2000 

Declare that the DoC is issued under sole responsibility and belongs to the following product: 

Apparatus Model(s) 

Series 35-40, 35-53, 35-60, 35-61, 35-63, 35-608, 35-65, 35-66, 35-9X 

Type: 

Fitting 

Batch Number  

Date code and Revision Level Assigned per production lot, (YYWW RR) 

Object of the Declaration: 

Series 35-40, 12/24Vdc Direct Spark Automatic Gas Ignition Controllers 
Series 35-53, 12Vdc Direct Spark Automatic Gas Ignition Controllers 
Series 35-60, 35-61, 35-63, 35-608 24Vac Direct Spark Automatic Gas Ignition 
Series 35-65 & 35-66 24Vac Hot Surface Automatic Gas Ignition Controllers 
Series 35-9X Platform Ignition Module

SERIES 35-40 

SERIES 35-53 

SERIES 35-60/61/63/608 

SERIES 35-65/66 

SERIES 35-9X 

The object of the declaration described above is in conformity within the relevant union 
harmonization legislation: 

Gas Appliance Regulation

(

EU) 2016/426 

Low Voltage Directive: 

2014/35/EC 

EMC Directive:

2014/30/EC

Rohs 

2011/65/EU

The following harmonized standards and technical specifications have been applied: 

EN298:2012:    

Automatic Burner Control systems for Burners and appliances burning gaseous or liquid fuels. 

EN13611:2007_A2:2011: 

Safety and control devices for Gas Burners and Gas burning appliances – General Requirements. 

Name of Notified Body & Number: 

BSI Group, 0086, EU Type Examination Certification 

Notified Body Certificate No.: 

Series 35-40:   

CE682407 

Series 35-53   

CE682404 

Series 35-60/61/63/608 

CE682405 

Series 35-65/66 

CE682406 

Series 35-9x   

CE

690652

 

Surveillance Audit Notified Body: 

BSI Group 

For copies of the Installation Instructions and the EU DoC, got to 

www.fenwalcontrols.com

, - Document Library - Data sheets. 

Paul Finn 

Kidde-Fenwal, Inc. Ashland, MA USA 

01

 

Oct

 2018 

Paul Finn, Certification Engineer 

Place of Issue:  

Date of Issue 

Name 

Содержание 35-60 Series

Страница 1: ...PECIFICATIONS Recognized under the UL component program UL 372 Software certified to ANSI UL 1998 UL File MH8817 Design Certified to ANSI Z21 20 CAN CSA C22 2 No 199 M89 CE Approved to EN 298 2012 Code Compliant to AS 4625 2008 AS 4622 2004 Input Power Control 18 30 VAC 50 60Hz Class 2 transformer Input Current 300 mA 24 VAC with gas valve relay energized control only Gas Valve 2 0A max 24 VAC Ope...

Страница 2: ...n trials before de energizing the gas valve and entering lockout The LED will indicate the fault code for ignition lockout FLAME FAILURE RE IGNITION MODE If the established flame signal is lost while the burner is operating the control will respond within 0 8 seconds by immediately energizing the H V spark for the TFI period in an attempt to relight the flame If the burner does not light within th...

Страница 3: ... Factory for longer lengths CAUTION All wiring must be performed in accordance with both local and national electrical codes CAUTION Label all wires prior to disconnection when servicing controls Wiring errors may cause improper and dangerous operation A functional checkout of a replacement control should always be performed WARNING This product uses voltages of shock hazard potential Wiring and i...

Страница 4: ...urrent Measurement Flame current is the current that passes through the flame from sensor to ground To measure flame current connect a True RMS or analog DC micro ammeter to the FC and FC terminals Readings should be 1 0 µA DC or higher If the meter reads negative or below 0 on scale meter leads are reversed Re connect leads with proper polarity Alternately a Digital Voltmeter may be used to measu...

Страница 5: ... 04 26 42 1 04 26 42 4 00 101 60 4 00 101 60 5 38 136 53 5 38 136 53 1 04 26 37 1 04 26 37 2 25 57 09 2 25 57 09 1 FS NC GND V2 TH PWR V1 1 FS NC GND V2 TH PWR V1 190 005 190 005 4 82 13 4 82 13 DIA 2 HOLES DIA 2 HOLES 25 6 35 25 6 35 2 53 64 21 2 53 64 21 1 79 45 44 1 79 45 44 1 27 32 10 1 27 32 10 1 NC GND V2 TH PWR V1 Remote Flame Sense 6 Pin Local Flame Sense 5 Pin Note All dimensions are in i...

Страница 6: ...s Tries for Ignition and Methods for Flame Sense 0 Single Try Local Sense 1 Single Try Remote Sense 5 Three Tries Local Sense 6 Three Tries Remote Sense Enclosure 0 Noryl Gray Enclosure 1 Integral Standoffs 2 HHVT w Enclosure 3 HHVT No Enclosure Product Designation 2 Standard CE Approved Model 3 Special CE Approved Model 5 Standard 6 Edge Connector 8 Aftermarket Kit 9 Special Configuration On CE A...

Страница 7: ...3 SERIES 35 60 61 63 608 SERIES 35 65 66 SERIES 35 9X The object of the declaration described above is in conformity within the relevant union harmonization legislation Gas Appliance Regulation EU 2016 426 Low Voltage Directive 2014 35 EC EMC Directive 2014 30 EC Rohs 2011 65 EU The following harmonized standards and technical specifications have been applied EN298 2012 Automatic Burner Control sy...

Отзывы: