background image

F-35-71

March 2020

1

FEATURES

Safe start with DETECT-A-FLAME

®

 flame sensing 

technology

Custom pre-purge and inter-purge timings

Inducer blower control and airflow switch monitoring

Single or three trials for ignition

System diagnostic LED

Flame current test points

Local or remote flame sensing

Automatic reset

Alarm output (normally closed contact)

Open board, potted or enclosure

Polarity insensitive input power

APPLICATIONS

Commercial cooking

Agriculture

Infrared burners

Construction heaters

Other gas-fired appliances

DESCRIPTION

The 35-71 is a 120 VAC direct spark ignition (DSI) control 
designed for use in all types of gas-fired appliances. The control 
uses a microprocessor circuit to provide precise, repeatable 
timing and operating sequences. On-board diagnostics with LED 
output makes troubleshooting easy and ensures safe and 
efficient operation.

Export Information (USA)

Jurisdiction: EAR
ECCN: EAR99

Agency Certifications

SPECIFICATIONS

Recognized under the UL component program, UL 
372. Software certified to ANSI/UL 1998. UL File 
MH8817

Design Certified to ANSI Z21.20,
CAN/CSA C22.2 No. 199-M89

Input Power

102 to 138 VAC, 50/60 Hz

Input Current

350 mA @120 VAC with gas valve relay 
energized (control only)

Gas Valve

1.5A max @ 120 VAC

Inducer Blower

3.0 FLA @ 120 VAC

Operating Temperature

-40°F to +160°F
(-40°C to +71°C)

Storage Temperature

-40°F to +185°F
(-40°C to +85°C)

Flame Sensitivity

1.0 µA minimum

Flame Failure Response

0.8 seconds maximum

Flame Detector Self-check Rate Once per second minimum
Gas Types

Natural, LP, or manufactured

Spark Rate:

Remote
Local

50/60 sparks/sec
25/30 sparks/sec

Size (LxWxH)
with enclosure

5.11 x 3.55 x 2.00 inches
(12.98 x 9.02 x 5.08 cm)

Moisture Resistance

Conformal coated to operate non-con-
densing to 95% R.H. Module should not 
be exposed to water

Ingress Protection

Not rated, protection provided by 
appliance in which it is installed

Tries for Ignition

One or three try versions available

Trial for Ignition Periods

4, 7, 10, 15 seconds available

Pre-purge and Inter-purge 
Timings

0, 5, 15 or 30 seconds available

Post-purge Time

0, 30 or 60 seconds available

SERIES 35-71

120 VAC Microprocessor-Based Direct Spark

Ignition Control with Inducer Blower Relay

R

Содержание 35-71 Series

Страница 1: ...Software certified to ANSI UL 1998 UL File MH8817 Design Certified to ANSI Z21 20 CAN CSA C22 2 No 199 M89 Input Power 102 to 138 VAC 50 60 Hz Input Current 350 mA 120 VAC with gas valve relay energized control only Gas Valve 1 5A max 120 VAC Inducer Blower 3 0 FLA 120 VAC Operating Temperature 40 F to 160 F 40 C to 71 C Storage Temperature 40 F to 185 F 40 C to 85 C Flame Sensitivity 1 0 µA minim...

Страница 2: ...gin after an inter purge delay Multi try models perform two additional attempts to light the burner If the burner relights normal operation resumes If the burner does not relight the control will enter lockout and the inducer blower will turn off following the optional post purge period FLAME FAILURE RECYCLE MODE With the Recycle After Loss of Flame option upon loss of flame the gas valve is de en...

Страница 3: ...f shock hazard potential Wiring and initial operation must be performed by a qualified service technician WARNING Operation outside specifications could result in failure of the Fenwal Controls product and other equipment with potential for injury to people and property Terminal Designations Terminal Description Multi Pin Connector P N TE 1 644615 1 Quick Connect inch NC Alarm 11 1 4 V1 Valve Powe...

Страница 4: ...ocated where they are not exposed during normal operation Flame Current Measurement Flame current is the current that passes through the flame from sensor to ground To measure flame current connect a True RMS or analog DC micro ammeter to the FC and FC terminals Readings should be 1 0 µA DC or higher If the meter reads negative or below 0 on scale meter leads are reversed Re connect leads with pro...

Страница 5: ...Effective March 2020 F 35 71 5 DIMENSIONS Figure 4 Enclosure Figure 5 Potted Figure 6 Integral Standoff Note All dimensions are in inches ...

Страница 6: ...3 try remote sense 7 3 try local sense 8 3 try remote sense Configuration and Wiring options 2 Potted 3 Enclosure 4 Integral Standoffs 5 Enclosure 6 Integral Standoffs 7 Potted 8 Aftermarket Kit 9 Special Configuration An 8 or 9 in this location i e 35 71 5 901 113 indicates a special configuration 9XX is a sequentially assigned part number and does not follow the standard part numbering configura...

Отзывы: