background image

Effective: March 2020

4

F-35-71

TROUBLESHOOTING

Note:

During a fault condition, the LED will flash on for 
1/4 second and off for 1/4 second as needed to 
indicate the fault code. The code will repeat every 
3 seconds. Removing power from the control will 
clear the fault code.

Internal Control Failure

If the control detects a software or hardware error, all outputs 
are turned off and the LED displays a Steady On condition. If this 
condition persists after an attempt to restart, then the control 
must be replaced.

Flame Fault

If a flame is sensed during a pre-purge or inter-purge, before the 
gas valve opens, a flame fault is declared and the inducer blower 
remains energized. If the flame signal later disappears, then the 
fault will be cleared and the control will start a normal ignition 
sequence.

Proper Electrode Location

Proper location of electrode assembly is important for optimum 
system performance. The electrode assembly should be located 
so that the tips are inside the flame envelope and about 1/2-inch 
(1.2 cm) above the base of the flame as shown:

Notes:

Ceramic insulators must not be in or close to the flame.

Electrode assemblies must not be adjusted or 
disassembled. Electrodes are NOT field adjustable.

Electrodes should have a gap spacing of 0.125± 0.031 
in (3.12± 0.81 mm), unless otherwise specified by the 
appliance manufacturer. If spacing is not correct, the 
assembly must be replaced.

Exceeding temperature limits can cause nuisance 
lockouts and premature electrode failure.

Electrodes must be located where they are not exposed 
during normal operation.

Flame Current Measurement

Flame current is the current that passes through the flame from    
sensor to ground. To measure flame current, connect a True 
RMS or analog DC micro-ammeter to the FC+ and FC- terminals. 
Readings should be 1.0 µA DC or higher. If the meter reads 
negative or below "0" on scale, meter leads are reversed. Re-
connect leads with proper polarity.

Alternately, a Digital Voltmeter may be used to measure DC 
voltage between FC+ and FC- terminals. Each micro-amp of 
flame current produces 1.0 VDC. For example, 2.6 VDC equates 
to 2.6 µA.

A good burner ground that matches the control ground is critical 
for reliable flame sensing.

Troubleshooting Guide

Symptom

Recommended Actions

1. Control does not start

A. Miswired
B. No 120VAC at L1
C. Fuse or circuit breaker fault
D. Faulty control, check LED 

for fault codes

2. Thermostat on - no spark

A. Miswired
B. Faulty thermostat, no 

voltage at terminal L1

C. Faulty control, check LED 

for fault codes

3. Blower on - no TFI after 
purge delay

A. Miswired
B. Flame fault
C. Airflow fault (check voltage 
at PSW)
D. Faulty control (check 
voltage between L1 and IND)

4. Valve on - no spark during 
TFI

A. Shorted electrode - 

establish 1/8-inch gap

B. Check high voltage cable
C. Miswired

5. Spark on - valve off

A. Valve coil open
B. Valve wire disconnected
C. Faulty control, check 

voltage at gas valve 
terminal V1

6. Flame okay during TFI - no 

flame sense after TFI

A. Check electrode position
B. Check high voltage wire
C. Poor ground at burner
D. Poor flame, check flame 

current

Fault Conditions

LED Indication

Fault Mode

Steady On

Internal Control Failure

1 Flash

Airflow Fault

2 Flashes

Flame without call for heat

3 Flashes

Ignition Lockout

Содержание 35-71 Series

Страница 1: ...Software certified to ANSI UL 1998 UL File MH8817 Design Certified to ANSI Z21 20 CAN CSA C22 2 No 199 M89 Input Power 102 to 138 VAC 50 60 Hz Input Current 350 mA 120 VAC with gas valve relay energized control only Gas Valve 1 5A max 120 VAC Inducer Blower 3 0 FLA 120 VAC Operating Temperature 40 F to 160 F 40 C to 71 C Storage Temperature 40 F to 185 F 40 C to 85 C Flame Sensitivity 1 0 µA minim...

Страница 2: ...gin after an inter purge delay Multi try models perform two additional attempts to light the burner If the burner relights normal operation resumes If the burner does not relight the control will enter lockout and the inducer blower will turn off following the optional post purge period FLAME FAILURE RECYCLE MODE With the Recycle After Loss of Flame option upon loss of flame the gas valve is de en...

Страница 3: ...f shock hazard potential Wiring and initial operation must be performed by a qualified service technician WARNING Operation outside specifications could result in failure of the Fenwal Controls product and other equipment with potential for injury to people and property Terminal Designations Terminal Description Multi Pin Connector P N TE 1 644615 1 Quick Connect inch NC Alarm 11 1 4 V1 Valve Powe...

Страница 4: ...ocated where they are not exposed during normal operation Flame Current Measurement Flame current is the current that passes through the flame from sensor to ground To measure flame current connect a True RMS or analog DC micro ammeter to the FC and FC terminals Readings should be 1 0 µA DC or higher If the meter reads negative or below 0 on scale meter leads are reversed Re connect leads with pro...

Страница 5: ...Effective March 2020 F 35 71 5 DIMENSIONS Figure 4 Enclosure Figure 5 Potted Figure 6 Integral Standoff Note All dimensions are in inches ...

Страница 6: ...3 try remote sense 7 3 try local sense 8 3 try remote sense Configuration and Wiring options 2 Potted 3 Enclosure 4 Integral Standoffs 5 Enclosure 6 Integral Standoffs 7 Potted 8 Aftermarket Kit 9 Special Configuration An 8 or 9 in this location i e 35 71 5 901 113 indicates a special configuration 9XX is a sequentially assigned part number and does not follow the standard part numbering configura...

Отзывы: