User’s Manual S40-T

FEMA ELECTRÓNICA - Page 4

Type

Range ºC

Max. error 

at 25ºC*

Range ºF

Offset drift

Span drift*

*includes offset drift

Pt100/RTD

 

800

 

/

 

-200

 

ºC

<0.2ºC

 

1562

 

/

 

-328

 

ºF

0.05º/ºC

0.10º/ºC

Thermocouple J

 

1200

 

/

 

-200

 

ºC

<2ºC

 

2192

 

/

 

-328

 

ºF

0.05º/ºC

0.20º/ºC

Thermocouple K

 

1372

 

/

 

-200

 

ºC

<2ºC

 

2372

 

/

 

-328

 

ºF

0.05º/ºC

0.20º/ºC

Thermocouple T

 

400

 

/

 

-200

 

ºC

<2ºC

 

752

 

/

 

-328

 

ºF

0.02º/ºC

0.02º/ºC

Thermocouple E

 

1000

 

/

 

-200

 

ºC

<2ºC

 

1832

 

/

 

-328

 

ºF

0.05º/ºC

0.20º/ºC

Thermocouple S

 

1768

 

/

    

-50

 

ºC

<4ºC

 

2282

 

/

    

-58

 

ºF

0.20º/ºC

0.20º/ºC

Thermocouple R

 

1600

 

/

    

-50

 

ºC

<4ºC

 

2912

 

/

    

-58

 

ºF

0.20º/ºC

0.20º/ºC

Thermocouple N

 

1300

 

/

 

-200

 

ºC

<2ºC

 

2372

 

/

 

-328

 

ºF

0.05º/ºC

0.20º/ºC

Thermocouple C

 

2320

 

/

       

0

 

ºC

<2ºC

 

4192

 

/

    

 32

 

ºF

0.02º/ºC

0.02º/ºC

Thermocouple L

 

900

 

/

 

-200

 

ºC

<2ºC

 

1652

 

/

 

-328

 

ºF

0.05º/ºC

0.20º/ºC

Thermocouple X

 

4000

 

/

 

-200

 

ºC

<2ºC

 

7232

 

/

 

-328

 

ºF

0.02º/ºC

0.02º/ºC

Table 3 - Thermocouple and PT100/RTD specifications

Technical Data

Digits

 4

Type 

7 segments, red

Height 

14 mm

Display maximum 

9999

Display minimum 

-1999

Decimal point 

selectable 8.8.8.8.

Overrange  

9999 flashing

Underrange 

-1999 flashing

Signals

 accepted 

Pt100/RTD and Thermocouples

Temperature scale 

ITS90

Display units 

ºC or ºF, selectable

Thermocouple

 data 

Thermocouples accepted J, K, T, E, S, R, N, C, L, X

(Thermocouple X is a linear 10uV/ºC signal)

Resolution 1º

Ranges 

see table 3

Max. error at 25ºC 

see table 3

Offset drift  

see table 3

Span drift* 

see table 3

*Note - span drift includes also the offset drift

CJC 

automatic (“On”/“Off” selectable)

CJC accuracy 

<1.0ºC

CJC thermal drift 

<0.04º/ºC

On sensor break 

“to_high” or “to_low”, selectable

Acquisitions 

3 acquisitions / second

Pt100/RTD

 data 

Sensors accepted 

2 or 3 wire, selectable

Resolution 

1º or 0.1º, selectable

Ranges 

 see table 3

Alpha 

Alpha385 or Alpha390, selectable

Max. error at 25ºC 

see table 3

Offset drift 

see table 3

Span drift * 

see table 3

*Note - span drift includes also the offset drift

Cable compensation 

up to 14 Ohm

Compensation accuracy  <0.02ºC / Ohm

Acquisitions 

4 acquisitions / second

Power

 

Power “H” 

85 to 265 Vac/dc

Power “L” 

11 to 60 Vdc and 24/48Vac

Consumption <4W

Isolation 

3500Veff for power “H”

 

2000Veff for power “L”

 

all levels tested for 60 seconds

Configuration

 

3 frontal push buttons

Functions available

Steps  

yes, configurable

Memory of maximum 

yes

Memory of minimum 

yes

Password 

yes, configurable

Double setpoints 

yes

Brightness control 

yes, 5 levels

Options

 

maximum 2

Mechanical

Mounting panel

Connections 

plug-in screw terminals

Weight 

<150 grams

Housing materials  

ABS, polycarbonate, vergaflex

Front size 

72x36mm

Panel cut-out 

69x32.5mm

Deep from panel 

98mm (including terminal)

Protection

  

IP54 standard

 

IP65 optional (Front sealed. Open-

ing the front breaks the seal)

Temperature

 Operation  0 to 50ºC

Temperature Storage 

–20 to +70ºC

Warm-up  

15 minutes

Technical Data (cont.)

Содержание S40-T

Страница 1: ...th internal CJC selectable enabled or disabled Selectable behavior in case of sensor break to_high or to_low Reduced housing 72x36mm DIN standard Display in 4 digits and negative sign Maximum and mini...

Страница 2: ...on the specified protection level Disconnect the instrument from power before starting any maintenance and or installation action Risk of electrical shock Instrument terminals can be connected to dan...

Страница 3: ...he power line a protection fuse acting as disconnection element easily accessible to the operator and identified as a protection device Power H fuse 250mA time lag Power L fuse 400mA time lag 6 7 8 9...

Страница 4: ...able 3 Offset drift see table 3 Span drift see table 3 Note span drift includes also the offset drift CJC automatic On Off selectable CJC accuracy 1 0 C CJC thermal drift 0 04 C On sensor break to_hig...

Страница 5: ...nu or leaves the Informa tion Menu Operating the Information Menu 36 8 32 5 Mechanical Dimensions mm 72 18 80 69 Panel cut out Configuration Conf Information on the configured input sensor and the deg...

Страница 6: ...the menu Allows selec tion of the current option displayed During a value selection menu for example a setpoint value validates the value on display Button UP Moves vertically on the menu Displays the...

Страница 7: ...tion See menu for Alarm1 See menu for Alarm1 See menu for Alarm1 Alarm1 Setpoint Hysteresis Delay Active On Inactive Off Max Maximum Min Minimum Alarm management Alarm as max Alarm as min Counts Secon...

Страница 8: ...fected on the same way as the setpoint with hysteresis and delays Display Menu Functions on this menu allow for configuration of the visu alization Steps StEP Display changes on predefined steps Value...

Страница 9: ...message h udr Hardware underrange The thermocouple signal is lower than minimum readable signal 30mV h oVr Hardware overrange The thermocouple signal is higher than maximum readable signal 80mV d udr...

Страница 10: ...ber 2011 Daniel Junc Quality Manager All instruments are warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse acc...

Страница 11: ...User s Manual S40 T FEMA ELECTR NICA Page 11 T H I S P A G E B L A N K...

Страница 12: ...ucts ELECTRONIC INSTRUMENTATION FOR INDUSTRY www fema es FEMA ELECTR NICA S A Altimira 14 Pol Ind Santiga E08210 Barber del Vall s BARCELONA SPAIN Tel 34 93 729 6004 www fema es Fax 34 93 729 6003 inf...

Отзывы: