User’s Manual M40-P

(dhI-dLo)  [Counts]

(IhI-ILo)   [mA or Vdc] < 5000

Advanced Display (Ad.dI) -

 Segments linearization. The 

instrument has 10 linearization segments (11 points). Each 

linearization points is formed of a signal input value (“InPX”) 

and an associated display value (“dISPX”). Enter the values 

for each point from the Points menu (“PntS”). It is required 

that the input signal values “InPX” must increase for each new 

point. When all points are entered, select “Act” value to “On” 

in the activation menu. A check is automatically performed 

when entering the points and when activating the points. In 

case of error verify the data entered on the points. Leave 

the menu pressing “LE” button. Reset option “rESt” deletes 

all existing points.

Password (Pass) - 

Select a number to act as password. This 

password will be requested when entering the Configuration 

Menu. To deactivate the password select “Off”.

Factory Settings (Fact) - 

Factory default configuration. Se

-

lect “yES” to activate the factory default configuration.

Version (Ver) - 

Firmware version installed.

Light (Ligh) - 

Brightness. Select between 5 predefined levels 

of brightness.

Tools Menu

When the instrument detects that the displayed value does 

not correspond to the expected value, the display will flash 

and alternate with a message.

h.udr

”  Hardware underrange. The instrument is reading 

the lowest possible signal, and can not follow lower signals.

h.oVr

”  Hardware overrange. The instrument is reading the 

highest possible signal and can not follow higher signals.

d.udr

”  Display underrange. The instrument is displaying 

the minimum value (-9999) and can not display below.

d.oVr

”  Display overrange. The instrument is displaying the 

maximum value (9999) and can not display above.

hoLd

”  The instrument is showing the value present when 

the hold function was activated. Hold function is active.

Min

” 

The instrument displays the minimum displayed 

value in memory. The minimum visualization is active.

MAX

”  The instrument displays the maximum displayed 

value in memory. The maximum visualization is active.

P.hLd

”  The instrument displays the peak value. Function 

Peak&Hold is active.

Err.0 

Values introduced on the “ScAL” menu are not valid. 

Default values are activated. The slope defined by the two 

points is almost vertical (higher than 5000):

Err.1 

Password incorrect.

Err.2 

The instrument has detected an installed option but 

was unable to communicate.

Err.3 

Related to the edition of a linearization point. Re-

turns to the point for further edition. The value of “InPX” of 

the edited point is lower than “InPX” of the previous point. 

Err.4 

Related to the activation (“Act”) of the lineariza-

tion segments (“Ad.dI”). Activation is not allowed. The value 

“InPX” of one of the points is higher than “InPX” of the next 

point.

Err.5 

Related to the activation (“Act”) of the linearization 

segments (“Ad.dI”). Activation is not allowed. The slope de-

fined by one of the segments is almost vertical.

Messages and errors

Configuration (Conf) -

 Informs the configured input signal 

range (4/20mA, 0/10Vdc, ...), and the values for input low 

“ILo”, display low “dLo”, input high “IhI” and display high “dhI”.

Maximum (MAX) - 

Value of the maximum display.

Minimum (MIn) - 

Value of the minimum display

AlarmX (ALX) - 

Configuration of  alarm X. The sequence of 

information shows if the alarm is being managed (“On/Off”), 

Information Menu 

Menu options OPT1, OPT2 and OPT3 give access to the 

configuration menus of the installed options. The menu de

-

pends on the installed option. If there is no option installed 

the instrument shows “nonE”.

Options Menu

Peak & Hold (P.hLd) 

- Peak & Hold function detects sharp 

drops in the displayed value, and holds the display if a display 

drop is detected. To disable the hold function for a moment, 

press any of the front buttons or wait for a predefined time :

   Time 0 

 

hold disabled (Off)

   Time  1 a 3999    

seconds, before disabling the hold

   Time 4000 

 

infinite hold

The counting of seconds is started each time there is an in-

crease in the display value. Alarms will follow the input signal 

while hold is active.

the alarm type (“Max/Min”), the setpoint, the hysteresis value, 

the activation delay and the value of setpoint2 (“Off” or the 

setpoint2 value).

OptionX (OptX) - 

Type of module installed. If there is no 

module shows “nonE”.

Measure (MEAS)- 

Multimeter function. Shows the value of 

the input signal without scaling. This is the real value the 

instrument is receiving on terminals, in Vdc or mA.

Slope condition for Err.0 and Err5

Datasheet

Sales:

 

+44 (0) 1273 570 220   

Website:

 www.amplicon.com   

Email:

 [email protected]

       IT and Instrumentation for industry

 Amplicon.com

Содержание M40 Series

Страница 1: ...ers Segment linearization maximum and minimum display memory scalable reading filters steps signal autocorrection measure function peak hold alarms with double setpoints 5 levels of brightness Univers...

Страница 2: ...n ways not specified by the manufacturer may lead to a reduction on the specified protection level Disconnect the instrument from power before starting any maintenance and or installation action Risk...

Страница 3: ...e power line a protection fuse acting as disconnection element easily accessible to the operator and identified as a protection device Power H fuse 250mA time lag Power L fuse 400mA time lag Signal Cu...

Страница 4: ...ns and rear jumper for signal selec tion in Vdc or mA Functions available Segment linearization 10 segments Fixed digits yes configurable Filter on display yes recursive configurable Steps yes configu...

Страница 5: ...llows to select each digit for modification with the UP button Reset Leaving the Configuration Menu forces a restart of the instrument even in case of no changes in configuration Configuration See men...

Страница 6: ...rm as maximum Alarm as minimum Counts Seconds Second setpoint Auto correction Auto High Auto Low Alarms Signal Low Display Low Signal High Display High Steps Counts for step Average Display Fixed Digi...

Страница 7: ...ault brightness Range and scaling 4 20mA 0 1000 Decimal point without decimal point Alarms 1 2 3 and 4 Active Off not managed Type maximum Setpoint 1000 Hysteresis 0 counts Delay 0 0 seconds Setpoint2...

Страница 8: ...Left Zero LZEr Value On Off Select On to visualize zeros to the left Add Right Zero rZEr Add a zero to the right Value On Off Select On to light a fifth digit on the display placed to the right LSD p...

Страница 9: ...alues are activated The slope defined by the two points is almost vertical higher than 5000 Err 1 Password incorrect Err 2 The instrument has detected an installed option but was unable to communicate...

Страница 10: ...f misuse accident or manipulation by non authorized personnel In case of mal function get in contact with your local provider to arrange for repair Within the warranty period and after examination by...

Отзывы: