User’s Manual M40-P
(dhI-dLo) [Counts]
(IhI-ILo) [mA or Vdc] < 5000
Advanced Display (Ad.dI) -
Segments linearization. The
instrument has 10 linearization segments (11 points). Each
linearization points is formed of a signal input value (“InPX”)
and an associated display value (“dISPX”). Enter the values
for each point from the Points menu (“PntS”). It is required
that the input signal values “InPX” must increase for each new
point. When all points are entered, select “Act” value to “On”
in the activation menu. A check is automatically performed
when entering the points and when activating the points. In
case of error verify the data entered on the points. Leave
the menu pressing “LE” button. Reset option “rESt” deletes
all existing points.
Password (Pass) -
Select a number to act as password. This
password will be requested when entering the Configuration
Menu. To deactivate the password select “Off”.
Factory Settings (Fact) -
Factory default configuration. Se
-
lect “yES” to activate the factory default configuration.
Version (Ver) -
Firmware version installed.
Light (Ligh) -
Brightness. Select between 5 predefined levels
of brightness.
Tools Menu
When the instrument detects that the displayed value does
not correspond to the expected value, the display will flash
and alternate with a message.
“
h.udr
” Hardware underrange. The instrument is reading
the lowest possible signal, and can not follow lower signals.
“
h.oVr
” Hardware overrange. The instrument is reading the
highest possible signal and can not follow higher signals.
“
d.udr
” Display underrange. The instrument is displaying
the minimum value (-9999) and can not display below.
“
d.oVr
” Display overrange. The instrument is displaying the
maximum value (9999) and can not display above.
“
hoLd
” The instrument is showing the value present when
the hold function was activated. Hold function is active.
“
Min
”
The instrument displays the minimum displayed
value in memory. The minimum visualization is active.
“
MAX
” The instrument displays the maximum displayed
value in memory. The maximum visualization is active.
“
P.hLd
” The instrument displays the peak value. Function
Peak&Hold is active.
Err.0
Values introduced on the “ScAL” menu are not valid.
Default values are activated. The slope defined by the two
points is almost vertical (higher than 5000):
Err.1
Password incorrect.
Err.2
The instrument has detected an installed option but
was unable to communicate.
Err.3
Related to the edition of a linearization point. Re-
turns to the point for further edition. The value of “InPX” of
the edited point is lower than “InPX” of the previous point.
Err.4
Related to the activation (“Act”) of the lineariza-
tion segments (“Ad.dI”). Activation is not allowed. The value
“InPX” of one of the points is higher than “InPX” of the next
point.
Err.5
Related to the activation (“Act”) of the linearization
segments (“Ad.dI”). Activation is not allowed. The slope de-
fined by one of the segments is almost vertical.
Messages and errors
Configuration (Conf) -
Informs the configured input signal
range (4/20mA, 0/10Vdc, ...), and the values for input low
“ILo”, display low “dLo”, input high “IhI” and display high “dhI”.
Maximum (MAX) -
Value of the maximum display.
Minimum (MIn) -
Value of the minimum display
AlarmX (ALX) -
Configuration of alarm X. The sequence of
information shows if the alarm is being managed (“On/Off”),
Information Menu
Menu options OPT1, OPT2 and OPT3 give access to the
configuration menus of the installed options. The menu de
-
pends on the installed option. If there is no option installed
the instrument shows “nonE”.
Options Menu
Peak & Hold (P.hLd)
- Peak & Hold function detects sharp
drops in the displayed value, and holds the display if a display
drop is detected. To disable the hold function for a moment,
press any of the front buttons or wait for a predefined time :
Time 0
hold disabled (Off)
Time 1 a 3999
seconds, before disabling the hold
Time 4000
infinite hold
The counting of seconds is started each time there is an in-
crease in the display value. Alarms will follow the input signal
while hold is active.
the alarm type (“Max/Min”), the setpoint, the hysteresis value,
the activation delay and the value of setpoint2 (“Off” or the
setpoint2 value).
OptionX (OptX) -
Type of module installed. If there is no
module shows “nonE”.
Measure (MEAS)-
Multimeter function. Shows the value of
the input signal without scaling. This is the real value the
instrument is receiving on terminals, in Vdc or mA.
Slope condition for Err.0 and Err5
Datasheet