Fema C Series Скачать руководство пользователя страница 25

FEMA ELECTRÓNICA . Series C . C40-D

25

1.31 Precautions on installation

1.32 Factory configuration

This instrument is warranted against all manufacturing defects for a period 

of 24 months, as requested by the European legislation. This warranty does 

not apply in case of misuse or accident, and the scope of the warranty is lim

-

ited to repair of the instrument, not being  the manufacturer responsible for 

additional damages or additional costs. Within the warranty period and after 

examination by the manufacturer, the unit will be repaired or substituted 

when found to be defective.
Extended  warranty  available  at  www.fema.es / docs / 4153_Warranty1_

en.pdf

1.33 Warranty

Range 

600 Vac

Scaling and decimal point 

0/600 Vac = 0/600

Alarms 1

   Type 

alarm as maximum

   Setpoint 

1000

   Hysteresis 

0 counts

Alarm 2

   Type 

alarm as maximum

   Setpoint 

1000

   Hysteresis 

0 counts

External control 

off

Fast access 

all off

Tools

   Option.1 

off

 (retains last configuration value)

   Step 

1

   Average 

0

   Offset reading 

0

   Second scaling 

0/600

   ‘Eco’ mode 

off

   Temperature resolution 

   Degrees 

ºC

   Alpha 

385

   cJc 

on

   AC deadband 

20

   Brightness 

3

   Password 

off

Option 1 configuration

   Option analog output 

0/100.0=4/20 mA

   Option serial Modbus RTU  9600 bps, address 1, format 8n1

Jumpers ‘S’ 

selected for 600 Vac

Jumper ‘T’ 

selected for ‘EK’ external control function

1.34 CE declaration of conformity

Manufacturer  FEMA ELECTRÓNICA, S.A.

 

 

Altimira 14 - Pol. Ind. Santiga

 

 

E08210 - Barberà del Vallès 

 

 

BARCELONA - SPAIN

 

 

www.fema.es - [email protected]

Products  

C40-D

The manufacturer declares that the instruments indicated comply with the 

directives and rules indicated below.
Electromagnetic compatibility directive 2014/30/EU

 

Low voltage directive 2014/35/EU

 

ROHS directive 2011/65/EU

 

WEEE directive 2012/19/EU

Security rules EN-61010-1

Instrument  

Fixed, Permanently connected

 

Pollution degree 1 and 2 (without condensation) 

 

Isolation  

Double

 

Category 

CAT-III up to 300V

 

 

CAT-II up to 600V (only with ‘Pollution degree 1’)

Electromagnetic compatibility rules EN-61326-1

EM environment  Industrial
CISPR 11  

Instrument Class A & Class B Group 1

For a detailed declaration see document www.fema.es / docs / 4152_CE-

Declaration_C40-D_en.pdf

Barberà del Vallès, January 2017

 

Xavier Juncà - Product Manager

According  to  directive  2012/19/EU,  electronic  equip-

ment  must  be  recycled  in  a  selective  and  controlled 

way at the end of its useful life.

This instrument has been designed and verified conforming to the 61010-1 CE Security 

Regulation, for industrial applications. Installation of this instrument must be performed 

by qualified personnel only. This manual contains the appropriate information for the in

-

stallation. Using the instrument in ways not specified by the manufacturer may lead to a 

reduction of the specified protection level. Disconnect the instrument from power before 

starting any maintenance and / or installation action.

The instrument does not have a general switch and will start operation as soon as power is 

connected. The instrument does not have protection fuse, the fuse must be added during 

installation.

The instrument is designed to be panel mounted. An appropriate ventilation of the in

-

strument must be assured. Do not expose the instrument to excess of humidity. Maintain 

clean by using a humid rag and do NOT use abrasive products such as alcohols, solvents, 

etc. General recommendations for electrical installations apply, and for proper functional

-

ity we recommend : if possible, install the instrument far from electrical noise or magnetic 

field generators such as power relays, electrical motors, speed variators, ... If possible, do 

not install along the same conduits power cables (power, motor controllers, electrovalves, 

...) together with signal and/or control cables. Before proceeding to the power connection, 

verify that the voltage level available matches the power levels indicated in the label on 

the instrument. In case of fire, disconnect the instrument from the power line, fire alarm 

according to local rules, disconnect the air conditioning, attack fire with carbonic snow, 

never with water.

Risk of electrical shock. Instrument terminals can be connected 

to dangerous voltage.

Instrument protected with double isolation. No earth connection 

required.

Instrument conforms to CE rules and regulations. 

Содержание C Series

Страница 1: ...ith 4 digits 9999 1999 Fast access function to alarm setpoints external control to activate predefined functions Eco mode for low consumption selectable dual scaling 5 levels of configurable brightnes...

Страница 2: ...23 Eco mode 13 1 24 External control 13 1 25 Second scaling 13 1 26 To open the instrument 14 1 27 How to operate the menus 15 1 28 Messages and errors 15 1 29 Configuration menu 16 1 29 1 Input signa...

Страница 3: ...terminals 1 and 4 Signals for 5 A current AC and DC must be con nected at terminals 3 and 4 All other signals must be connected between terminals 2 and 4 Terminal 5 is a multifunction terminal config...

Страница 4: ...r process signals 5 Vdc for potentiometers at terminal 5 see sections 1 5 and 1 16 Power supply power U 18 to 265 Vac dc isolation 1500 Veff isolation tested for 60 sec AC frequency 50 60 Hz consumpti...

Страница 5: ...Jumpers S Jumper T AC voltages and currents 600 Vac G I 4 5 200 Vac I 20 Vac A I 2 Vac B I 200 mVac C I 60 mVac E I 5 Aac I 20 mAac D I DC voltages and currents 600 Vdc G 4 5 200 Vdc 20 Vdc A 2 Vdc B...

Страница 6: ...steps listed at section 1 7 Signal connections are indicated at section 1 5 Location for internal jump ers is indicated at section 1 9 Vac ranges Veff Scale by default Scalable Jumper S see section 1...

Страница 7: ...ion 1 7 Signal connections are indicated at section 1 5 Location for internal jump ers is indicated at section 1 9 Vdc ranges Scale by default Scalable Jumper S see section 1 9 Jumper T see section 1...

Страница 8: ...ouple K E 4 5 100 1350 C 148 2462 F 2 tc 4 tc 3 Thermocouple J 100 1200 C 148 2192 F Thermocouple E 100 1000 C 148 1832 F Thermocouple N 100 1300 C 148 2372 F Thermocouple L 100 900 C 148 1652 F Therm...

Страница 9: ...0 see section 1 29 7 This pa rameter is associated to the specific model of probe installed Sensor Jumper S see section 1 9 Jumper T see section 1 9 Range in C in F Total error Connection terminals Cu...

Страница 10: ...n for internal jump ers is indicated at section 1 9 See below connections for NTC probe 1 14 Measuring with NTC probes NTC R25 configurable Jumper S see section 1 9 Jumper T see section 1 9 Range of m...

Страница 11: ...nnection terminals Zin 4 20 mA passive needs Vexc 0 100 0 de 9999 a 1999 D 1 2 0 15 25 mA 2 signal 5 Vexc 4 7Ohm active 4 5 2 mA 4 mA 0 10 Vdc passive needs Vexc A 1 2 0 20 25 Vdc 2 Vdc 4 comm 5 Vexc...

Страница 12: ...n 1 9 for a list of available functions Start up connections and jumpers For instrument start up follow the steps listed at section 1 7 Signal connections are indicated at section 1 5 Location for int...

Страница 13: ...ree potential contact called Exter nal control To configure the second scaling 1 configure the internal jumper T to activate the EK external control function see section 1 9 2 associate the external c...

Страница 14: ...X and then insert clips A B C and D in this order The internal structure of the instrument is shown in the graphic be low Module Opt 2 connects to module Opt 1 Module Opt 1 connects to the display Opt...

Страница 15: ...t validates the num ber displayed Key UP 5 the UP 5 key gives access to the fast access menu Inside the menus it moves vertically through the different menu op tions At menus with numerical value entr...

Страница 16: ...able options Pt100 3 wire Pt100 2 wire Pt500 Pt1000 Ni100 Ni200 and Ni1000 For measures with 2 wires a manual compensation for the wire resistance error is available us ing parameter Offset reading oF...

Страница 17: ...ximum type alarm or minimum type activates when the dis play value is higher or lower than the setpoint value at the Setpoint SEt parameter enter the value for the alarm activation point This paramete...

Страница 18: ...vate a tare to the signal The actual signal will read 0 The calibration is not changed select parameter Decimal point 0 dP 0 to remove the decimal point on display select parameter Decimal point 1 dP...

Страница 19: ...compen sate for the possible error introduced by the resistance of the signal wires when measuring Pt probes Ni probes or resistances For more information see section 1 22 1 29 7 Menu Tools Option 1...

Страница 20: ...Ni1000 PTC and NTC For thermocouple probes resolution is fixed to 1 at the Degrees dEG menu select the temperature values to be read in C degrees Celsius or in F degrees Fahrenheit at the Alpha ALPh...

Страница 21: ...r 485 at Tools out 1 r 485 to have the serial output configuration at this menu entry Configure the address for the instrument parameter Address 1 to 247 Addr the bus speed parameter Speed kbps bAud...

Страница 22: ...c range 2 Vdc range 200 mVdc range 60 mVdc range 5 Adc range 20 mAdc range Process 4 20 mA range 0 10 Vdc range Thermocouples thermocouple K thermocouple J thermocouple E thermocouple N thermocouple L...

Страница 23: ...ss Memory of max Memory of min Setpoint 1 Setpoint 2 Degrees degrees Celsius degrees Fahrenheit Temperature resolution 1 resolution 0 1 resolution Second scaling Decimal point Display Low Display High...

Страница 24: ...elected at Tool Out 1 Analog output Display Low Display High Modbus RTU Address 1 to 247 Speed Kbps Format Password Version Factory reset Minimum Brightness Maximum Standard Alpha Alpha 385 Alpha 390...

Страница 25: ...ent Industrial CISPR 11 Instrument Class A Class B Group 1 For a detailed declaration see document www fema es docs 4152_CE Declaration_C40 D_en pdf Barber del Vall s January 2017 Xavier Junc Product...

Страница 26: ...portional to the reading of the instrument The mA output can be connected to work in active loop the module provides the power of the loop or passive mode the power of the loop is not provided by the...

Страница 27: ...420 see section 1 29 7 to inform the instrument that there is a M1 analog output module installed From this point you will need the calibration sheet provided together with the module M1 This sheet s...

Страница 28: ...the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad 3 1 Option NBT O ring for IP65 front protec...

Страница 29: ...ll mount housing Together with the KIP protector offers a full IP65 protection For Series C of panel meters 4 4 WME wall housing Benchtop housing for Series C and of panel meters Handle with three sel...

Страница 30: ...FEMA ELECTR NICA Series C C40 D 30 Notes...

Страница 31: ...FEMA ELECTR NICA Series C C40 D 31 Notes...

Страница 32: ......

Отзывы: