FEMA ELECTRÓNICA . Series C . C40-D

19

The ‘

Tools

’ (‘

tooL

’) menu contains multiple configuration options of 

the instrument.

• 

select at the ‘

Option 1

’ (‘

out.1

’) parameter the module type 

installed at the ‘Opt.1’ 

(see section 2) 

slot. Select ‘

relay’

 (‘

rELE

’) 

for the relay output module ‘

A1

’. Select ‘

analog output

 

(‘

420

’) 

for the analog output module ‘

M1

’. Select ‘

Modbus RTU

 

(‘

r.485

’) 

for the Modbus RTU serial output module ‘

S1

’.

Note : the parameter ‘

420

’ gives access to the calibration menu 

for the analog output module. See section 2.2 for more informa-

tion about this menu and the calibration.

• 

the  ‘

Steps

’  (‘

StEP

’)  parameter  allows  to  configure  a  defined 

minimum  step  change  on  the  reading.  Reading    will  change  in 

steps of 1, 2, 5, 10, 20 or 50 counts.

  the  ‘

Average  filter

’  (‘

AVr

’)  function  allows  to  reduce  reading 

oscillations due to noisy signals, by applying a recursive filter on 

the reading values. The strength of the recursive filter is a value 

configurable  between  ‘0’  and  ‘100’.  Value  ‘0’  means  ‘filter  dis

-

abled’. Filter strength increases with the value. Increasing the fil

-

ter strength, increases the response time of the instrument.

• 

the  ‘

Offset  reading

’  (‘

oFFS

’)  parameter  allows  to  configure  a 

fixed number of counts to be subtracted from the reading. Ac

-

cepts values from -500 to 500. This function allows to compen

-

sate  for  the  possible  error  introduced  by  the  resistance  of  the 

signal wires when measuring Pt probes, Ni probes or resistances. 

For more information see section 

1.22

1.29.7 Menu ‘Tools’

Option 1

analog output

relay

disabled

Tools

1.29 Configuration menu (cont.)

Average filter

Steps

Modbus RTU

Offset reading

the parameter ‘420’ gives 

access  to  the  calibration 

menu  for  the  analog  out-

put.  See  section  2.2  for 

more information.

 select parameter ‘

Decimal point 2

’ (‘

dP.2

’) to activate the decimal 

point at position XX.XX

• 

select parameter ‘

Decimal point 3

’ (‘

dP.3

’) to activate the decimal 

point at position X.XXX

Parameters  ‘

Decimal  point  0

’  (‘

dP.0

’)and  similar  ‘

dP.1

’,  ‘

dP.2

’  and

 

dP.3

’ control which decimal point is on. When the external contact 

closes, the decimal point selected lights on and the decimal point 

that was activated before will power off. When the external contact  

opens, the previous decimal point powers on again while removing 

the new decimal point. Display does not show in flash mode when 

decimal point functions are activated.

 select parameter ‘

Second scaling

’ (‘

ScL.2

’) to activate the second 

scaling configured at menu ‘

Tools

’ (‘

TooL

’) \ ‘

Second scaling

’. The 

activation of the ‘

Second scaling

’ function is accepted for all signal 

input ranges based on AC input signals, DC input signals, process 

and resistances. Display does not show in flash mode when second 

scaling function is activated. For more information on the ‘

Second 

scaling’

 seer section 

1.25

0 to 100

Содержание C Series

Страница 1: ...ith 4 digits 9999 1999 Fast access function to alarm setpoints external control to activate predefined functions Eco mode for low consumption selectable dual scaling 5 levels of configurable brightnes...

Страница 2: ...23 Eco mode 13 1 24 External control 13 1 25 Second scaling 13 1 26 To open the instrument 14 1 27 How to operate the menus 15 1 28 Messages and errors 15 1 29 Configuration menu 16 1 29 1 Input signa...

Страница 3: ...terminals 1 and 4 Signals for 5 A current AC and DC must be con nected at terminals 3 and 4 All other signals must be connected between terminals 2 and 4 Terminal 5 is a multifunction terminal config...

Страница 4: ...r process signals 5 Vdc for potentiometers at terminal 5 see sections 1 5 and 1 16 Power supply power U 18 to 265 Vac dc isolation 1500 Veff isolation tested for 60 sec AC frequency 50 60 Hz consumpti...

Страница 5: ...Jumpers S Jumper T AC voltages and currents 600 Vac G I 4 5 200 Vac I 20 Vac A I 2 Vac B I 200 mVac C I 60 mVac E I 5 Aac I 20 mAac D I DC voltages and currents 600 Vdc G 4 5 200 Vdc 20 Vdc A 2 Vdc B...

Страница 6: ...steps listed at section 1 7 Signal connections are indicated at section 1 5 Location for internal jump ers is indicated at section 1 9 Vac ranges Veff Scale by default Scalable Jumper S see section 1...

Страница 7: ...ion 1 7 Signal connections are indicated at section 1 5 Location for internal jump ers is indicated at section 1 9 Vdc ranges Scale by default Scalable Jumper S see section 1 9 Jumper T see section 1...

Страница 8: ...ouple K E 4 5 100 1350 C 148 2462 F 2 tc 4 tc 3 Thermocouple J 100 1200 C 148 2192 F Thermocouple E 100 1000 C 148 1832 F Thermocouple N 100 1300 C 148 2372 F Thermocouple L 100 900 C 148 1652 F Therm...

Страница 9: ...0 see section 1 29 7 This pa rameter is associated to the specific model of probe installed Sensor Jumper S see section 1 9 Jumper T see section 1 9 Range in C in F Total error Connection terminals Cu...

Страница 10: ...n for internal jump ers is indicated at section 1 9 See below connections for NTC probe 1 14 Measuring with NTC probes NTC R25 configurable Jumper S see section 1 9 Jumper T see section 1 9 Range of m...

Страница 11: ...nnection terminals Zin 4 20 mA passive needs Vexc 0 100 0 de 9999 a 1999 D 1 2 0 15 25 mA 2 signal 5 Vexc 4 7Ohm active 4 5 2 mA 4 mA 0 10 Vdc passive needs Vexc A 1 2 0 20 25 Vdc 2 Vdc 4 comm 5 Vexc...

Страница 12: ...n 1 9 for a list of available functions Start up connections and jumpers For instrument start up follow the steps listed at section 1 7 Signal connections are indicated at section 1 5 Location for int...

Страница 13: ...ree potential contact called Exter nal control To configure the second scaling 1 configure the internal jumper T to activate the EK external control function see section 1 9 2 associate the external c...

Страница 14: ...X and then insert clips A B C and D in this order The internal structure of the instrument is shown in the graphic be low Module Opt 2 connects to module Opt 1 Module Opt 1 connects to the display Opt...

Страница 15: ...t validates the num ber displayed Key UP 5 the UP 5 key gives access to the fast access menu Inside the menus it moves vertically through the different menu op tions At menus with numerical value entr...

Страница 16: ...able options Pt100 3 wire Pt100 2 wire Pt500 Pt1000 Ni100 Ni200 and Ni1000 For measures with 2 wires a manual compensation for the wire resistance error is available us ing parameter Offset reading oF...

Страница 17: ...ximum type alarm or minimum type activates when the dis play value is higher or lower than the setpoint value at the Setpoint SEt parameter enter the value for the alarm activation point This paramete...

Страница 18: ...vate a tare to the signal The actual signal will read 0 The calibration is not changed select parameter Decimal point 0 dP 0 to remove the decimal point on display select parameter Decimal point 1 dP...

Страница 19: ...compen sate for the possible error introduced by the resistance of the signal wires when measuring Pt probes Ni probes or resistances For more information see section 1 22 1 29 7 Menu Tools Option 1...

Страница 20: ...Ni1000 PTC and NTC For thermocouple probes resolution is fixed to 1 at the Degrees dEG menu select the temperature values to be read in C degrees Celsius or in F degrees Fahrenheit at the Alpha ALPh...

Страница 21: ...r 485 at Tools out 1 r 485 to have the serial output configuration at this menu entry Configure the address for the instrument parameter Address 1 to 247 Addr the bus speed parameter Speed kbps bAud...

Страница 22: ...c range 2 Vdc range 200 mVdc range 60 mVdc range 5 Adc range 20 mAdc range Process 4 20 mA range 0 10 Vdc range Thermocouples thermocouple K thermocouple J thermocouple E thermocouple N thermocouple L...

Страница 23: ...ss Memory of max Memory of min Setpoint 1 Setpoint 2 Degrees degrees Celsius degrees Fahrenheit Temperature resolution 1 resolution 0 1 resolution Second scaling Decimal point Display Low Display High...

Страница 24: ...elected at Tool Out 1 Analog output Display Low Display High Modbus RTU Address 1 to 247 Speed Kbps Format Password Version Factory reset Minimum Brightness Maximum Standard Alpha Alpha 385 Alpha 390...

Страница 25: ...ent Industrial CISPR 11 Instrument Class A Class B Group 1 For a detailed declaration see document www fema es docs 4152_CE Declaration_C40 D_en pdf Barber del Vall s January 2017 Xavier Junc Product...

Страница 26: ...portional to the reading of the instrument The mA output can be connected to work in active loop the module provides the power of the loop or passive mode the power of the loop is not provided by the...

Страница 27: ...420 see section 1 29 7 to inform the instrument that there is a M1 analog output module installed From this point you will need the calibration sheet provided together with the module M1 This sheet s...

Страница 28: ...the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad 3 1 Option NBT O ring for IP65 front protec...

Страница 29: ...ll mount housing Together with the KIP protector offers a full IP65 protection For Series C of panel meters 4 4 WME wall housing Benchtop housing for Series C and of panel meters Handle with three sel...

Страница 30: ...FEMA ELECTR NICA Series C C40 D 30 Notes...

Страница 31: ...FEMA ELECTR NICA Series C C40 D 31 Notes...

Страница 32: ......

Отзывы: