background image

FEMA ELECTRÓNICA . Series S . S40-P

10

On power-up

Delay

Tare

Seconds

Tools

1.10 Configuration menu (cont.)

The ‘

On Power Up

’ (‘

on.Pu

’) menu configures functions to apply at 

start-up. It applies only to instrument restart after power loss. It does 

not apply to instrument restart due to change in configuration.

• parameter ‘

Delay

’ (‘

dLAy

’) assigns a waiting time in seconds. The 

instrument waits the configured time before starting normal func

-

tion. During this waiting time, the display shows all decimal points 

on in flash mode, all alarms are in ‘oFF’ state, there is no signal acqui

-

sition and there is no communications or control being performed. 

After  the  configured  time  is  over,  the  instrument  starts  in  normal 

function. Delay value between 0 and 200 seconds.

Application - the start-up process for an automation system implies 

that different parts of the system (engines, actuators, controllers, ...) 

have different start-up times. The ‘Delay’ function gives time to the 

instrument to wait until the slowest part of the system is fully func-

tional before executing actions on the system (signal reading, relay 

activation, ...)

• the ‘

Tare

’ (‘

tArE

’) functions allow to activate an automatic tare of 

the reading each time the instrument is restarted. See section 

1.10.9 

for more information on the ‘tare’ function.

1.10.8 Menu ‘On Power Up’

The ‘

Tare function

’ (‘

tArE

’) menu allows to operate the instrument 

for load-cell and weight applications. The tare function assigns the 

actual input signal value to a reading of ‘0’ Kilos, by adding an inter

-

nal offset. It does not modify the scaling parameters of the instru

-

ment.

The ‘Tare’ function can be applied pressing button ‘LE’ (

3

) at the 

front keypad 

(see section 1.10.10)

The offset value is eligible for visu

-

alization through the ‘

Fast access

’ menu 

(see section 1.10.6).

To work with load-cell applications it is important to first adjust the 

scaling of the instrument to the load-cell used.

Application - A load cell with 2 mV/V parameter, powered at 10 Vdc, 

with nominal weight of 500 Kilos, together with a signal converter 

that provides 4/20 mA signals for a 0/20 mV signal from the load-cell. 

The scaling to configure at the meter is 4/20 mA = 0/500.0 Kilos. Once 

the meter is scaled, the tare function can be used to ‘tare’ the reading 

to 0 Kilos.

• at the ‘

Reset

’ (‘

rSt

’) menu select ‘

yES

’ to reset the tare offset value 

in memory.

1.10.9 Menu ‘Tare function’

Tare function

Reset

Key LE

Tare

Alarm unlock

No function

1.10.10 

Menu ‘Key LE’

The ‘LE’ (

3

) key at the front of the instrument can be configured to 

activate several functions. Only one function can be assigned to the 

‘LE’ (

3

) key

• the ‘

No function

’ (‘

nonE

’)

 

value assigns no function.

• the ‘

Tare

’ (‘

Tare

’) value assigns a tare function 

(see section 1.10.9).

• the ‘

Alarm unlock

’ (‘

A.Lck

’)

 

value assigns the manual unlock of the 

alarms function, for instruments with the ‘

Locked alarms

’ (‘

A.Lck

’) 

function activated 

(see section 1.10.3)

Содержание S40-P

Страница 1: ...linearization fast access to alarm setpoints tare function on power up function measure function configurable reading brightness Universal AC and DC power Up to 2 optional modules for output and contr...

Страница 2: ...hold for test break applications see section 1 10 4 Multiple display filters memory for maximum and minimum reading password protection 5 brightness levels 1 1 How to order Index 1 Panel meter S40 P...

Страница 3: ...connections Button UP Logo Alarms Units Button SQ Button LE Configuration menu see section 1 10 Fast access see section 1 10 6 1 6 Mechanical dimensions mm Signal see section 1 5 Jumpers see section...

Страница 4: ...Ranges Accuracy Zin Max signal overload Offset drift span drift includes offset drift 4 20 mA 0 05 FS 11 Ohm 100 mA permanent 10 ppm C 25 ppm C 0 10 Vdc 0 05 FS 932 KOhm 100 Vdc permanent 10 ppm C 25...

Страница 5: ...Key LE 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the chang...

Страница 6: ...ed on the field providing a fast and easy way to compensate offset signals To operate the Field correction F cor function for the offset cor rection generate the minimum input signal and access the Fi...

Страница 7: ...e alarm relays due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set po...

Страница 8: ...ory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see...

Страница 9: ...at the front of the instrument gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP...

Страница 10: ...rE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does not...

Страница 11: ...menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this function it is possible to ada...

Страница 12: ...on 1 10 for a description of each menu entry Scaling Input low Display low Input high Display high Alarm 1 Setpoint Hysteresis Setpoint 2 Active Alarm type Activation delay Deactivation delay Left zer...

Страница 13: ...ng Activate Reset Number of segments Value 2 to 20 Input 0 Display 0 Input 1 Display 1 On power up Delay Tare Seconds Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configurati...

Страница 14: ...el only You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock the lower clips marked with B...

Страница 15: ...ay 0 seconds Tare off Key LE no function Excitation voltage 20 Vdc Password off Brightness 3 clean by using a humid rag and do NOT use abrasive products such as alcohols solvents etc General recommend...

Страница 16: ...t 1 Power Signal A B C A B C The R1 module provides 1 relay output to to install at digital panel meters from Series S up to a maximum of 2 relays in a single meter Note for more than 2 relays per ins...

Страница 17: ...ayed installation as it does not require soldering or special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more inform...

Страница 18: ...uration Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manual_i pdf Protocol Modbus RTU Functi...

Страница 19: ...up to 31 modules Frames codified in represent able ASCII characters codes 32 to 255 directly visible using hyper terminal or similar programs Access to display values alarm status memory of maximum a...

Страница 20: ......

Отзывы: