FEMA ELECTRÓNICA . Series S . S40-P
9
Tools
Key UP
(‘Fast access’)
Memory of
maximum
Memory of
minimum
Setpoint 1
Setpoint 2
‘Tare’ value
‘Measure’
Segment
linearization
Scaling
Activate
Reset
Number
of segments
Value 2 to 20
Input 0
Display 0
Input 1
Display 1
1.10 Configuration menu (cont.)
The ‘
Segment Linearization
’ (‘
S.LIn
’) menu provides up to 20 seg
-
ments to linearize non-linear signals.
• at the ‘
Number of segments
’ (‘
nuM
’)
parameter, select the num
-
ber of segment to use. Value between ‘2’ and ‘20’.
• at the ‘
Scaling
’ (‘
ScAL
’) menu define the input signal values (‘
In-
put
’) and the associated reading (‘
Display
’) for each point. This menu
starts ad point ‘0’ and ends at the number of segments previously
defined.
• the ‘
Activate
’ (‘
Act
’) function activates the segment linearization,
with the values previously configured. If the instrument detects error
in any of the values, it will display an error message with information
of the point where the error is located.
• the ‘
Reset
’ (‘
rSt
’) function resets all previously defined points and
resets the ‘
Number of segments
’ (‘
nuM
’)
parameter to ‘2’ with a
scaling of 0/100
% of the input signal range selected and a reading
of 0 to 100.
1.10.5 Segment linearization
The ‘UP’ (
5
) key at the front of the instrument gives access to a list
of functions configurable by the operator. See section
for an ex
-
planation on how to operate the ‘
fast access
’ menu.
The ‘
Key UP (Fast access)
’ (‘
K.uP
’) menu allows to select which func
-
tions will be accessible through the ‘fast access’ menu. Select ‘
on
’ to
activate each function.
• the ‘
Setpoint
1
’ (‘
ALr1
’) function allows to visualize and modify the
alarm
1 setpoint through the ‘fast access’ menu.
• the ‘
Setpoint
2
’ (‘
ALr2
’) function allows to visualize and modify the
alarm
2 setpoint through the ‘fast access’ menu.
• the ‘
Memory of maximum
’ (‘
MAX
’)
or
‘
Memory of minimum
’
(‘
MIn
’) functions allow to visualize the maximum or minimum read
-
ing value stored in memory. To reset this value, visualize the memory
value at the ‘fast access’ menu with key UP (
5
) and when message
‘
rSt
’ is displayed, press (
<
) to reset.
•the ‘
Tare value
’ (‘
tArE
’)
function allows to visualize the actual value
of the tare. See section
for more information.
• the ‘
Measure
’ (‘
MEAS
’) function allows to visualize the actual sig
-
nal at input terminals, without scaling. Example : with an instrument
with input 4/20
mA, the ‘
measure
’ function will show the direct value
in mA.
1.10.6
Fast access
If only a single function is selected for the ‘fast access’ menu, press
-
ing the the ‘UP’ (
5
) key will shortly display the function name and
then automatically jump to the function value.
1.10.7
Super fast access