FEMA ELECTRÓNICA . Series K . K40-232

19

1.28 Configuration menu (cont.)

Tools

On power-up

Delay

Seconds

Alarm 1

Alarm 2

Alarm 3

Key UP

 

(‘fast access’)

Memory of  

maximum

Memory of 

minimum

Setpoint 1

Setpoint 2

Setpoint 3

Bus activity

Setpoint on bus

Address

The ‘UP’ (

5

) key at the front of the instrument gives access to a list 

of functions configurable by the operator. See section 

1.27

 for an ex

-

planation on how to operate the ‘

fast access

’ menu.

The ‘

Key UP (Fast access)

’ (‘

K.uP

’) menu allows to select which func

-

tions will be accessible through the ‘fast access’ menu. Select ‘

on

’ to 

activate each function.

• the ‘

Bus activity

’ (‘

buS.A

’) helps to visualize activity in the commu

-

nications bus 

(see section 1.26)

.

• the ‘

Memory of maximum

’  (‘

MAX

’)

 

or

 

Memory of minimum

’ 

(‘

MIn

’) functions allow to visualize the maximum or minimum read

-

ing value stored in memory. To reset this value, visualize the memory 

value at the ‘fast access’ menu with key UP (

5

) and when message 

rSt

’ is displayed, press (

<

) to reset.

• the ‘

Setpoint

1

’ (‘

ALr1

’) function allows to visualize and modify the 

alarm

1  setpoint  through  the  ‘fast  access’  menu.  Available  only  in 

‘Process slave’ mode.

• the ‘

Setpoint

2

’ (‘

ALr2

’) function allows to visualize and modify the 

alarm

2  setpoint  through  the  ‘fast  access’  menu.  Available  only  in 

‘Process slave’ mode.

• the ‘

Setpoint

3

’ (‘

ALr3

’) function allows to visualize and modify the 

alarm

3  setpoint  through  the  ‘fast  access’  menu.  Available  only  in 

‘Process slave’ mode.

• the ‘

Address

’ (‘

Addr

’)

 

function allows to visualize the address of 

the instrument.

1.28.6 

Fast access

The ‘

On Power Up

’ (‘

on.Pu

’) menu configures functions to apply at 

start-up. It applies only to instrument restart after power loss. It does 

not apply to instrument restart due to change in configuration 

(see 

section 1.8)

.

• parameter ‘

Delay

’ (‘

dLAy

’) assigns a waiting time in seconds to be 

applied at start-up. During this waiting time, the display shows all 

decimal points flashing 

(see section 1.8)

 and no action is performed. 

Delay value between 0 and 200 seconds.

• parameters ‘

Alarm 1

’ (‘

ALr1

’)

Alarm 2

’ (‘

ALr2

’)

 

and ‘

Alarm 3

’ (‘

ALr3

’)

 

define the alarm status at instrument start-up 

(see section 1.8)

.

1.28.7 Super fast access

If only a single function is selected for the ‘fast access’ menu, press

-

ing the the ‘UP’ (

5

) key will shortly display the function name and 

then automatically jump to the function value.

1.28.8 

Menu ‘On Power Up’

Available only in ‘Process slave’ mode. Alarm configuration in ‘Pro

-

cess  slave’  mode  is  done  through  the  front  keypad.  Enable  the 

Setpoint on bus

’ (‘

StP.b

’) function to ‘on’ to enable alarm setpoint 

registers  accessible  from  the  communications  bus.  By  default  this 

function is ‘oFF’.
Nota : value written in the ‘alarm’  register updates the alarm set

-

point. But manual modification of alarm setpoint does not update 

the ‘alarm’ register.

1.28.9 Menu ‘Setpoint on bus’

Содержание K Series

Страница 1: ...tandard 96 x 48 mm size 1 8 DIN Fast access to bus ativity alarm setpoints and memory of max and min On power up function configurable read ing brightness password Universal AC and DC power Up to 3 op...

Страница 2: ...mode 3 1 3 Full slave mode 3 1 4 Text mode 3 1 5 Typical application 3 1 6 Front view 4 1 7 Power connections 4 1 8 Start up sequence 4 1 9 Rear view 4 1 10 Signal connections 4 1 11 Technical specif...

Страница 3: ...Analog output value is associated to the display value Display Alarms Analog outputs RS 232 ASCII K40 232 display in Process slave mode In Text mode the instrument receives a set of ASCII characters...

Страница 4: ...ted below at start up af ter a power loss 1 alarm status according to configuration see section 1 28 8 2 start up delay according to configuration see section 1 28 8 3 all registers initialized to val...

Страница 5: ...puts serial communi cations see section 2 Mechanical mounting panel connections plug in screw terminal housing material ABS polycarbonate V0 weight 150 grams front size 96 x 48 mm 1 8 DIN panel cut ou...

Страница 6: ...r For a list of error codes see section 1 22 Frame read RD Identifier 36 Frame to request the data value of a register The register number is indicated in the REG byte sec tion Header Frame answer ANS...

Страница 7: ...e TO Destination address 1 byte 4 0 Master 1 a 31 Slave 128 broadcast 32 v REG Register number 1 byte 5 see sections 1 16 1 17 and 1 18 32 real_value RSV Reserved 1 byte 6 0 32 LONG Length of Data sec...

Страница 8: ...he Slave with address 28 The Header Data Trail STX ID RSV FROM TO REG RSV LONG D0 D1 D2 D3 D4 D5 CRC ETX 2 35 32 32 60 32 32 38 43 54 53 46 52 51 58 3 Start WRA 0 28 0 6 65 43 CRC Stop 1 15 2 Frame ER...

Страница 9: ...frame ANS that contains the value requested 65 43 For compatibility reasons de instrument will always answer with a 6 digit value filling with left zeros the additional positions Header Data Trail STX...

Страница 10: ...when they are dis abled will return error 8 Read only register to save into the E2PROM the values written through the bus into these registers values will be maintained incase of pow er loss enable p...

Страница 11: ...r an instrument configured in Text mode register 0 contains the value to show on display It is an alpha numerical value The register can contain up to 71 characters acceptable characters are indicated...

Страница 12: ...5 53 on off on 6 54 on on off 7 55 on on on Table 6 Register Alarm Status 1 21 Representable characters Representable characters are indicated in the following table In numerical modes Full slave and...

Страница 13: ...ed to a read only register 9 Frame error The frame ID is not known 10 First char error When writing on numerical registers first character must be a number or polarity or In case of other characters t...

Страница 14: ...e applied in the order in dicated below Section DATA can not be empty of characters It generates an error 6 Empty Data First character must be or a number from 0 to 9 It generates error 10 First char...

Страница 15: ...system reset when validat ing the changes Front key pad description Key SQ press the SQ key for 1 second to access the con figuration menu Inside the menu the SQ key functions as a ENTER key It selec...

Страница 16: ...ation or deactivation depends on the display value and the local alarm configuration Full slave mode F SLV instrument receives a numerical value through the communications bus to represent on display...

Страница 17: ...case of watchdog er ror select Flash FLSh to activate the display flash select Dashes dASh to activate dashes on display select Watchdog error Err W to activate message Err W on display select do not...

Страница 18: ...activation point This parameter is eligible for configuration through the Fast access menu see section 1 28 6 configure the hysteresis value at Hysteresis hySt The hyster esis applies to the deactiva...

Страница 19: ...ALr3 function allows to visualize and modify the alarm 3 setpoint through the fast access menu Available only in Process slave mode the Address Addr function allows to visualize the address of the ins...

Страница 20: ...ation for the instrument see section 1 29 1 28 13 Factory reset 1 28 14 Firmware version 1 28 15 Brightness The LE 3 key at the front of the instrument can be configured to activate several functions...

Страница 21: ...slave mode default configuration Alarms 1 2 and 3 Active disabled oFF Type maximum Setpoint 1000 Hysteresis 0 counts Activation delay 0 0 seconds Deactivation delay 0 0 seconds Setpoint 2 off Inverte...

Страница 22: ...stop 8 bits odd parity 1 stop 8 bits no parity 2 stop Alarm 1 Remote Watchdog Alarms in full slave mode Alarm 2 Alarm 3 Remote Watchdog Remote Watchdog Configuration 1 to 247 Local address Watchdog W...

Страница 23: ...inimum Setpoint 1 Setpoint 2 Setpoint 3 Bus activity Setpoint on bus Key LE Alarmunlock No function Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configuration menu for the mo...

Страница 24: ...qualified personnel only To open the housing use a flat screwdriver to free the fixation clips if possible in the following order D C B and A Remove the front cover Let the inside of the instrument sl...

Страница 25: ...s and regulations Manufacturer FEMA ELECTR NICA S A Altimira 14 Pol Ind Santiga E08210 Barber del Vall s BARCELONA SPAIN www fema es info fema es Products K40 232 The manufacturer declares that the in...

Страница 26: ...ntinuous Isolation 3500 Veff Type of terminal plug in screw terminal pitch 5 08 mm Slots allowed Opt 1 Opt 2 Opt 3 Terminal A Common Terminal B NO Normally open Terminal C NC Normally closed Power Opt...

Страница 27: ...special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_ma...

Страница 28: ...Opt 2 Opt 1 Opt 3 B A G B A G Signal B A G Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_man...

Страница 29: ...programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrument front keypad through menu entries Opt 1 Opt 2 or Opt 3 depending on the posit...

Страница 30: ...without front key pad To configure the instrument remove the meter from the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrumen...

Страница 31: ...older 4 1 THM benchtop housing Adapter96 x 96 mmfor96 x 48 mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel m...

Страница 32: ......

Отзывы: