Fema Electronica K Series Скачать руководство пользователя страница 14

FEMA ELECTRÓNICA . Series K . K40-232

14

The ‘watchdog’ function activates an error state in case of loss of 

communication with the ‘master’. To configure the ‘watchdog’ indi

-

cate the maximum time accepted to wait between two frames re

-

ceived. If this time exceeds, the ‘watchdog error’ activates. Receiving 

a correct frame resets the ‘watchdog’ timer.
Frames that can reset the ‘watchdog’ timer are those addressed to 

the ‘slave’ instrument. These frames must conform to the indicated 

ASCII protocol and have a correct CRC.
If the function or register or coil indicated in the frame is not correct, 

the ‘slave’ instrument will still reset the ‘watchdog’ timer. It will also 

reply with the corresponding error message.

The  internal  alarms  of  the  instrument  can  be  associated  to  the 

‘watchdog’.  In  case  of  ‘watchdog’  activation,  the  associated  alarm 

will also activate.
Display can also be configured to show an error message in case of 

‘watchdog’ error. It can be configured for flashing, dash (‘------’) or to 

show message ‘Err.W’.
See sections 

1.28.4 

and 

1.28.5 

for information on alarm configura

-

tion and section 

1.28.3

 for information on ‘watchdog’ configuration.

‘Bus activity’ function is a detector of electrical activity on the bus. 

The function is to help when connecting the instrument to the bus 

for the first time. It provides information on wether there is electrical 

activity on the bus or not.
The ‘Bus activity’ function is visible in the form of a counter increas

-

ing its value on the display. It indicates that the UART is detecting 

information bytes on the bus. This detection means that there are 

data on the bus, and that it conforms to the configured speed and 

data format.

‘Bus activity’ function is accessible at key UP (

5

), when enabled as 

indicated in section 

1.28.6.

1.23 

Numerical registers : restrictions

Registers which must contain a numerical value, are controlled to as

-

sure that the value received from the frame is a true numerical value. 

If controls are successful, the value is saved into the register. Other

-

wise, an error is generated. Registers which must contain numerical 

values are the following :

• ‘Display’ register
• ‘Setpoint 1’, ‘Setpoint 2’ and ‘Setpoint 3’ registers

When writing data into these registers, the instrument converts the 

ASCII characters received on the ‘DATA’ section of the frame, to a 

numerical value. The following controls are applied, in the order in

-

dicated below :

• Section ‘DATA’ can not be empty of characters. It generates an 

error 6 ‘Empty Data’.
• First character must be ‘+’, ‘-’, ‘.’, ‘,’ or a number from ‘0’ to ‘9’. It 

generates error 10 ‘First char error’.
•  Section  ‘DATA’  must  contain  maximum  one  decimal  point.  It 

generates error 11 ‘Format error’.
• Section ‘DATA’ can contain only characters from ‘0’ to ‘9’ or dec

-

imal point (‘,’ o ‘.’). First character has already been controled and 

is not controlled again. If other character is found, it generates 

error 11 ‘Format error’. 
• If section ‘DATA’ does not contain decimal point, its maximum 

length is 7 characters. If section ‘DATA’ contains decimal point, its 

maximum length is 8 characters. Larger data generates error 12 

‘Out of range’.
• Conversion from ASCII characters to a number. Decimal point is 

separated from the number, which is treated as an integer.
  Examples : possible conversions are as follows:
 

‘1234’ is read on display as 1234

 

‘-1234’ is read on display as -1234

 

‘-12.34’ is read on display as -12.34

 

‘+.995’ is read on display as 0.995

 

‘+0.995’ is read on display as 0.995

 

‘0.995’ is read on display as 0.995

 

‘.995’ is read on display as 0.995

 

‘+0027’ is read on display as 27

 

‘+27’ is read on display as 27

 

‘27’ is read on display as 27

• The numerical integer is sent to display. If the number is higher 

than the maximum number that can be represented by the dis

-

play, it generates an error 12 ‘Out of range’. 

  Example : ‘-67.89’ is not representable on display, because 

minimum  display  is  -1999.  Instrument  will  generate  an 

‘Out  of  range’  error.  ‘Display’  register  is  not  updated.  It 

generates an answer frame 12 ‘Out of range’ if the writing 

was requested with a ‘WRA’ frame.

Note : character ‘.’ and ‘,’ are equivalent and both are associated 

to the decimal point.

1.24 Addresses and ‘broadcast’ 

Addresses available to assign to the intruments are from 1 to 31. Ad

-

dress 128 is a ‘broadcast’ address.
Instruments  will  accept  and  process  frames  when  destination  ad

-

dress of the frame matches its own address.

All frames addressed to destination address 128 will be accepted by 

all instruments, independent of its own address. Instruments will not 

generate answer frames when destination address is 128.

• a ‘ping’ (‘

PING

’) frame to destination address 128 will not gen

-

erate answer

• a ‘write with aknowldgement’ (‘

WRA

’) frame to destination ad

-

dress 128 will not generate answer

• a ‘read’ (‘

READ

’) frame to destination address 128 will not gen

-

erate answer

• a frame to destination address 128 which contains an error (a 

CRC error for example) will not generate answer

1.25 

‘Watchdog’ function

1.26 

‘Bus activity’ function

Содержание K Series

Страница 1: ...tandard 96 x 48 mm size 1 8 DIN Fast access to bus ativity alarm setpoints and memory of max and min On power up function configurable read ing brightness password Universal AC and DC power Up to 3 op...

Страница 2: ...mode 3 1 3 Full slave mode 3 1 4 Text mode 3 1 5 Typical application 3 1 6 Front view 4 1 7 Power connections 4 1 8 Start up sequence 4 1 9 Rear view 4 1 10 Signal connections 4 1 11 Technical specif...

Страница 3: ...Analog output value is associated to the display value Display Alarms Analog outputs RS 232 ASCII K40 232 display in Process slave mode In Text mode the instrument receives a set of ASCII characters...

Страница 4: ...ted below at start up af ter a power loss 1 alarm status according to configuration see section 1 28 8 2 start up delay according to configuration see section 1 28 8 3 all registers initialized to val...

Страница 5: ...puts serial communi cations see section 2 Mechanical mounting panel connections plug in screw terminal housing material ABS polycarbonate V0 weight 150 grams front size 96 x 48 mm 1 8 DIN panel cut ou...

Страница 6: ...r For a list of error codes see section 1 22 Frame read RD Identifier 36 Frame to request the data value of a register The register number is indicated in the REG byte sec tion Header Frame answer ANS...

Страница 7: ...e TO Destination address 1 byte 4 0 Master 1 a 31 Slave 128 broadcast 32 v REG Register number 1 byte 5 see sections 1 16 1 17 and 1 18 32 real_value RSV Reserved 1 byte 6 0 32 LONG Length of Data sec...

Страница 8: ...he Slave with address 28 The Header Data Trail STX ID RSV FROM TO REG RSV LONG D0 D1 D2 D3 D4 D5 CRC ETX 2 35 32 32 60 32 32 38 43 54 53 46 52 51 58 3 Start WRA 0 28 0 6 65 43 CRC Stop 1 15 2 Frame ER...

Страница 9: ...frame ANS that contains the value requested 65 43 For compatibility reasons de instrument will always answer with a 6 digit value filling with left zeros the additional positions Header Data Trail STX...

Страница 10: ...when they are dis abled will return error 8 Read only register to save into the E2PROM the values written through the bus into these registers values will be maintained incase of pow er loss enable p...

Страница 11: ...r an instrument configured in Text mode register 0 contains the value to show on display It is an alpha numerical value The register can contain up to 71 characters acceptable characters are indicated...

Страница 12: ...5 53 on off on 6 54 on on off 7 55 on on on Table 6 Register Alarm Status 1 21 Representable characters Representable characters are indicated in the following table In numerical modes Full slave and...

Страница 13: ...ed to a read only register 9 Frame error The frame ID is not known 10 First char error When writing on numerical registers first character must be a number or polarity or In case of other characters t...

Страница 14: ...e applied in the order in dicated below Section DATA can not be empty of characters It generates an error 6 Empty Data First character must be or a number from 0 to 9 It generates error 10 First char...

Страница 15: ...system reset when validat ing the changes Front key pad description Key SQ press the SQ key for 1 second to access the con figuration menu Inside the menu the SQ key functions as a ENTER key It selec...

Страница 16: ...ation or deactivation depends on the display value and the local alarm configuration Full slave mode F SLV instrument receives a numerical value through the communications bus to represent on display...

Страница 17: ...case of watchdog er ror select Flash FLSh to activate the display flash select Dashes dASh to activate dashes on display select Watchdog error Err W to activate message Err W on display select do not...

Страница 18: ...activation point This parameter is eligible for configuration through the Fast access menu see section 1 28 6 configure the hysteresis value at Hysteresis hySt The hyster esis applies to the deactiva...

Страница 19: ...ALr3 function allows to visualize and modify the alarm 3 setpoint through the fast access menu Available only in Process slave mode the Address Addr function allows to visualize the address of the ins...

Страница 20: ...ation for the instrument see section 1 29 1 28 13 Factory reset 1 28 14 Firmware version 1 28 15 Brightness The LE 3 key at the front of the instrument can be configured to activate several functions...

Страница 21: ...slave mode default configuration Alarms 1 2 and 3 Active disabled oFF Type maximum Setpoint 1000 Hysteresis 0 counts Activation delay 0 0 seconds Deactivation delay 0 0 seconds Setpoint 2 off Inverte...

Страница 22: ...stop 8 bits odd parity 1 stop 8 bits no parity 2 stop Alarm 1 Remote Watchdog Alarms in full slave mode Alarm 2 Alarm 3 Remote Watchdog Remote Watchdog Configuration 1 to 247 Local address Watchdog W...

Страница 23: ...inimum Setpoint 1 Setpoint 2 Setpoint 3 Bus activity Setpoint on bus Key LE Alarmunlock No function Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configuration menu for the mo...

Страница 24: ...qualified personnel only To open the housing use a flat screwdriver to free the fixation clips if possible in the following order D C B and A Remove the front cover Let the inside of the instrument sl...

Страница 25: ...s and regulations Manufacturer FEMA ELECTR NICA S A Altimira 14 Pol Ind Santiga E08210 Barber del Vall s BARCELONA SPAIN www fema es info fema es Products K40 232 The manufacturer declares that the in...

Страница 26: ...ntinuous Isolation 3500 Veff Type of terminal plug in screw terminal pitch 5 08 mm Slots allowed Opt 1 Opt 2 Opt 3 Terminal A Common Terminal B NO Normally open Terminal C NC Normally closed Power Opt...

Страница 27: ...special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_ma...

Страница 28: ...Opt 2 Opt 1 Opt 3 B A G B A G Signal B A G Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_man...

Страница 29: ...programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrument front keypad through menu entries Opt 1 Opt 2 or Opt 3 depending on the posit...

Страница 30: ...without front key pad To configure the instrument remove the meter from the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrumen...

Страница 31: ...older 4 1 THM benchtop housing Adapter96 x 96 mmfor96 x 48 mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel m...

Страница 32: ......

Отзывы: