25

This instrument has been designed and verified conforming to the 61010-1 

CE Security Regulation, for industrial applications.
Installation  of  this  instrument  must  be  performed  by  qualified  personnel 

only. This manual contains the appropriate information for the installation. 

Using the instrument in ways not specified by the manufacturer may lead to 

a reduction of the specified protection level. Disconnect the instrument from 

power before starting any maintenance and / or installation action.
The instrument does not have a general switch and will start operation as 

soon as power is connected. The instrument does not have protection fuse, 

the fuse must be added during installation.
The instrument is designed to be panel mounted. An appropriate ventilation 

of the instrument must be assured. Do not expose the instrument to excess 

of humidity. Maintain clean by using a humid rag and do NOT use abrasive 

products such as alcohols, solvents, etc.
General recommendations for electrical installations apply, and for proper 

functionality  we  recommend  :  if  possible,  install  the  instrument  far  from 

electrical noise or magnetic field generators such as power relays, electrical 

motors, speed variators, ... If possible, do not install along the same conduits 

power cables (power, motor controllers, electrovalves, ...) together with sig

-

nal and/or control cables.
Before  proceeding  to  the  power  connection,  verify  that  the  voltage  level 

available matches the power levels indicated in the label on the instrument.
In case of fire, disconnect the instrument from the power line, fire alarm 

according to local rules, disconnect the air conditioning, attack fire with car

-

bonic snow, never with water.

1.33 

Precautions on installation

Risk of electrical shock. Instrument terminals can be connected 

to dangerous voltage.

Instrument protected with double isolation. No earth connection 

required.

Instrument conforms to CE rules and regulations. 

Manufacturer  FEMA ELECTRÓNICA, S.A. 

 

Altimira 14 - Pol. Ind. Santiga

 

 

E08210 - Barberà del Vallès 

 

 

BARCELONA  - SPAIN

 

 

www.fema.es - [email protected]

Products  

K40-232

The manufacturer declares that the instruments indicated comply with the 

directives and rules indicated below.
Electromagnetic compatibility directive 2014/30/EU

 

Low voltage directive 2014/35/EU

 

Directive ROHS 2011/65/EU

Security rules EN-61010-1

Instrument  

Fixed

 

 

Permanently connected 

Pollution degree 1 and 2 (without condensation) 

 

Isolation  

Double

Electromagnetic compatibility rules EN-61326-1

EM environment

 Industrial

Immunity levels

EN-61000-4-2  By contact ±4 KV 

Criteria B

 

 

By air ±8 KV 

Criteria B

EN-61000-4-3    

Criteria A

EN-61000-4-4   On AC power lines : ±2 KV 

Criteria B

 

 

On DC power lines : ±2 KV 

Criteria B

 

 

On signal lines : ±1 KV 

Criteria B

EN-61000-4-5  Between AC power lines ±1 KV 

Criteria B

 

 

Between AC power lines and earth ±2 KV 

Criteria B

 

 

Between DC power lines ±1 KV 

Criteria B

 

 

Between DC power lines and earth ±2 KV 

Criteria B

 

 

Between signal lines and earth ±1 KV 

Criteria B 

EN-61000-4-6   

Criteria A

EN-61000-4-8  30 A/m at 50/60 Hz 

Criteria A

EN-61000-4-11  0 % 1 cycle 

Criteria A

 

 

40 % 10 cycles 

Criteria A

 

 

70 % 25 cycles 

Criteria B

 

 

0 % 250 cycles 

Criteria B

Emission levels

CISPR 11  

Instrument Class A, Group 1  

Criteria A

Barberà del Vallès May  2017

 

Xavier Juncà - Product Manager

1.35 

CE declaration of conformity

1.34 Warranty

This instrument is warranted against all manufacturing defects for a 

period of 24 MONTHS from the shipment date. This warranty does 

not apply in case of misuse, accident or manipulation by non-autho

-

rized personnel. In case of malfunction get in contact with your local 

provider to arrange for repair. Within the warranty period and after 

examination by the manufacturer, the unit will be repaired or substi

-

tuted when found to be defective. The scope of this warranty is lim

-

ited to the repair cost of the instrument, not being the manufacturer 

eligible for responsibility on additional damages or costs.

According  to  directive  2012/19/EU,  electronic  equip

-

ment must be recicled in a selective and controlled way 

at the end of its useful life.

Содержание K Series

Страница 1: ...tandard 96 x 48 mm size 1 8 DIN Fast access to bus ativity alarm setpoints and memory of max and min On power up function configurable read ing brightness password Universal AC and DC power Up to 3 op...

Страница 2: ...mode 3 1 3 Full slave mode 3 1 4 Text mode 3 1 5 Typical application 3 1 6 Front view 4 1 7 Power connections 4 1 8 Start up sequence 4 1 9 Rear view 4 1 10 Signal connections 4 1 11 Technical specif...

Страница 3: ...Analog output value is associated to the display value Display Alarms Analog outputs RS 232 ASCII K40 232 display in Process slave mode In Text mode the instrument receives a set of ASCII characters...

Страница 4: ...ted below at start up af ter a power loss 1 alarm status according to configuration see section 1 28 8 2 start up delay according to configuration see section 1 28 8 3 all registers initialized to val...

Страница 5: ...puts serial communi cations see section 2 Mechanical mounting panel connections plug in screw terminal housing material ABS polycarbonate V0 weight 150 grams front size 96 x 48 mm 1 8 DIN panel cut ou...

Страница 6: ...r For a list of error codes see section 1 22 Frame read RD Identifier 36 Frame to request the data value of a register The register number is indicated in the REG byte sec tion Header Frame answer ANS...

Страница 7: ...e TO Destination address 1 byte 4 0 Master 1 a 31 Slave 128 broadcast 32 v REG Register number 1 byte 5 see sections 1 16 1 17 and 1 18 32 real_value RSV Reserved 1 byte 6 0 32 LONG Length of Data sec...

Страница 8: ...he Slave with address 28 The Header Data Trail STX ID RSV FROM TO REG RSV LONG D0 D1 D2 D3 D4 D5 CRC ETX 2 35 32 32 60 32 32 38 43 54 53 46 52 51 58 3 Start WRA 0 28 0 6 65 43 CRC Stop 1 15 2 Frame ER...

Страница 9: ...frame ANS that contains the value requested 65 43 For compatibility reasons de instrument will always answer with a 6 digit value filling with left zeros the additional positions Header Data Trail STX...

Страница 10: ...when they are dis abled will return error 8 Read only register to save into the E2PROM the values written through the bus into these registers values will be maintained incase of pow er loss enable p...

Страница 11: ...r an instrument configured in Text mode register 0 contains the value to show on display It is an alpha numerical value The register can contain up to 71 characters acceptable characters are indicated...

Страница 12: ...5 53 on off on 6 54 on on off 7 55 on on on Table 6 Register Alarm Status 1 21 Representable characters Representable characters are indicated in the following table In numerical modes Full slave and...

Страница 13: ...ed to a read only register 9 Frame error The frame ID is not known 10 First char error When writing on numerical registers first character must be a number or polarity or In case of other characters t...

Страница 14: ...e applied in the order in dicated below Section DATA can not be empty of characters It generates an error 6 Empty Data First character must be or a number from 0 to 9 It generates error 10 First char...

Страница 15: ...system reset when validat ing the changes Front key pad description Key SQ press the SQ key for 1 second to access the con figuration menu Inside the menu the SQ key functions as a ENTER key It selec...

Страница 16: ...ation or deactivation depends on the display value and the local alarm configuration Full slave mode F SLV instrument receives a numerical value through the communications bus to represent on display...

Страница 17: ...case of watchdog er ror select Flash FLSh to activate the display flash select Dashes dASh to activate dashes on display select Watchdog error Err W to activate message Err W on display select do not...

Страница 18: ...activation point This parameter is eligible for configuration through the Fast access menu see section 1 28 6 configure the hysteresis value at Hysteresis hySt The hyster esis applies to the deactiva...

Страница 19: ...ALr3 function allows to visualize and modify the alarm 3 setpoint through the fast access menu Available only in Process slave mode the Address Addr function allows to visualize the address of the ins...

Страница 20: ...ation for the instrument see section 1 29 1 28 13 Factory reset 1 28 14 Firmware version 1 28 15 Brightness The LE 3 key at the front of the instrument can be configured to activate several functions...

Страница 21: ...slave mode default configuration Alarms 1 2 and 3 Active disabled oFF Type maximum Setpoint 1000 Hysteresis 0 counts Activation delay 0 0 seconds Deactivation delay 0 0 seconds Setpoint 2 off Inverte...

Страница 22: ...stop 8 bits odd parity 1 stop 8 bits no parity 2 stop Alarm 1 Remote Watchdog Alarms in full slave mode Alarm 2 Alarm 3 Remote Watchdog Remote Watchdog Configuration 1 to 247 Local address Watchdog W...

Страница 23: ...inimum Setpoint 1 Setpoint 2 Setpoint 3 Bus activity Setpoint on bus Key LE Alarmunlock No function Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configuration menu for the mo...

Страница 24: ...qualified personnel only To open the housing use a flat screwdriver to free the fixation clips if possible in the following order D C B and A Remove the front cover Let the inside of the instrument sl...

Страница 25: ...s and regulations Manufacturer FEMA ELECTR NICA S A Altimira 14 Pol Ind Santiga E08210 Barber del Vall s BARCELONA SPAIN www fema es info fema es Products K40 232 The manufacturer declares that the in...

Страница 26: ...ntinuous Isolation 3500 Veff Type of terminal plug in screw terminal pitch 5 08 mm Slots allowed Opt 1 Opt 2 Opt 3 Terminal A Common Terminal B NO Normally open Terminal C NC Normally closed Power Opt...

Страница 27: ...special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_ma...

Страница 28: ...Opt 2 Opt 1 Opt 3 B A G B A G Signal B A G Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_man...

Страница 29: ...programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrument front keypad through menu entries Opt 1 Opt 2 or Opt 3 depending on the posit...

Страница 30: ...without front key pad To configure the instrument remove the meter from the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrumen...

Страница 31: ...older 4 1 THM benchtop housing Adapter96 x 96 mmfor96 x 48 mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel m...

Страница 32: ......

Отзывы: