12.- JUMPER'S CONFIGURATION
12.1.- STANDARD CONFIGURATION
The factory set-up jumper's configuration, it is shown below unless customer had specified another
configuration.
SENSOR SELECTION . . . . . . . . . . . . Type NPN.
SIGNAL LEVEL . . . . . . . . . . . . . . . . . . Type "A" (page 7).
FREQUENCY RANGE . . . . . . . . . . . . 100 Hz.
DECIMAL POINT . . . . . . . . . . . . . . . . None.
SCALE FACTOR . . . . . . . . . . . . . . . . . "1".
12.2.- PROCEDURE FOR CHANGE THE CONFIGURATION
If the sensor type is modified or the characteristics of the installation are changed then it is necessary to
modify the initial jumpers configuration. Please follow the configuration procedure shown below.
1.- Power off the instrument.
2.- Remove the rear cover taking off all the screws (page. 6) to obtain the access to the control circuit.
(page 7).
3.- Remove all jumpers installed on S1 and S2 selectors. (Page 7).
4.- Configurate the sensor type for Channel 1 using the jumpers on S1 selector (See table 3 page 7).
5.- Configurate the sensor type for Channel 2 using the jumpers on S1 selector (See table 3 page 7).
6.- Select the frequency range using the jumpers J and K on S2 Selector (see table 2 page 7).
7.- Select the signal input level using the jumpers H and G on S2 Selector (see table 1 page 7).
8.- Install the rear cover on its place and power up the instrument.
NOTE : It is advisable to write all modifications made on page 14 of this manual (paragraph 15,
OPERATOR's NOTES).