1.On the AC side, the individual breaker should be connected between inverter and Grid but
before loads.See Figure 4.3-2.
Figure 4.3-2 Ac breaker connection
·
Make sure the inverter is totally isolated from any DC or AC power before
connecting AC cable.
13
14
A
B
C
D
Outside diameter
Separated wire length
Conductor wire length
Conductor core section
30-40mm
200-250mm
20-25mm
15-20mm
A
B
C
D
Connection terminal
Screw Cap
Cable
Peel off the skin of the AC cable and thread the AC cable through the Screw Cap.
See Figure 4.3-4.
Thread the AC cable through the Screw Cap and connect to the inside of the inverter.
Then tighten the Screw Cap. See Figure 4.3-6.