Power Limit Function

In discharging mode:
Example1:PV<Load, PV+BAT provide power to Load, BAT provides power to the Grid.

Example2:Load<PV<Load+BAT, PV provides power to Load first, PV+BAT will provide power to the Grid.

Example3:PV>Load+BAT, PV provides power to Load and Grid,and the remaining energy will charge BAT.

The function could be realized by:
(1) Make sure Smart Meter connection and communication well.
(2) Turn on export power limit function and set the max output power to grid on App.
Note: Even if output power limit is set to 0W, there might still be a deviation of a max of 100W 
exporting to grid.

Zero Export To Load:

 Hybrid inverter will provide power to the backup load connected. The hybrid 

inverter will also provide power to the home load and sell power to grid by the function of Grid Power 
Limit setting.Smart Meter & CT Connection is not needed.

Zero Export To CT:

 Hybrid inverter will not only provide power to the backup load connected but also 

give power to the home load connected. If PV power and battery power is insufficient, it will take grid 
energy as supplement. In this mode, a Meter&CT is needed. The installation method of the Meter&CT 
please refer to chapter 4.4 Smart Meter & CT Connection. 

Grid Power Limit:

 the maximum power feeds to Grid.

37

38

7. APP Download the app

Method 1: Access https://download.felicitysolar.com using the mobile phone browser and 

download the latest installation package.

Method 2: Scan the following QR code and download the latest installation package.

Please refer the Fsolar End user manual, register the installer and create a plant and owner (skip 

this step if the account has been created). You can obtain the Fsolar End user manual by 

scanning the following QR code.

8. Warning Code

Battery 1 overvoltage alarm

Battery 1 voltage is too high and the battery should 

be discharged.

01

Warning 

Information

Warning 

Code

Warning 

Information

Battery 2 overvoltage alarm

02

Battery 2 voltage is too high and the battery should 

be discharged.

Battery 1 undervoltage alarm

03

Battery 1 voltage is too low, the battery should be 

charged.

Battery 2 undervoltage alarm

04

Battery 2 voltage is too low, the battery should be 

charged.

Under-frequency derating alarm

09

The frequency is too low, the inverter reduce the power.

Over-frequency derating alarm

10

The frequency is too high, the inverter reduce the power.

Load Overload Alarm

12

The load is overloaded, and the load should be reduced.

DC lightning protection alarm

13

If the DC lightning protector is abnormal, check whether 

the lightning protector is abnormal.

AC lightning protection alarm

14

If the AC lightning protector is abnormal, check whether 

the lightning protector is abnormal.

16

The ambient temperature is too high, and the inverter 

reduces the power. 

Ambient overtemperature derating 

alarm

Содержание HY-50K-HT

Страница 1: ...358 010351 00A HY 50K HT...

Страница 2: ...ntact Signal 4 6 DRMS Connection 4 7 Lithium Battery Communication 4 8 Installation of WIFI module 4 9 Wiring System 4 10 Typical application diagram of diesel generatol 5 Display and operation 5 1 Op...

Страница 3: ...lectrical parts even cause an explosion Please strictly follow installation procedure when you want to disconnect AC or DC terminals Please refer to Installation section of this manual for the details...

Страница 4: ...ce Time of use function Smart Load Function Basic System Architecture The following illustration shows basic application of this inverter It also includes following devices to have a complete running...

Страница 5: ...COM connector 1 2 3 4 5 6 No Name Expansion Bolts M5 combination screw M10 Allen wrench M5 Allen wrench Meter CT optional 7 8 Battery connector 3 3 Installation Environment Figure 2 2 3 Paper packages...

Страница 6: ...n the cover of the inverter or replace any part as incomplete inverter may cause electric shock and damage the device during operation Figure 3 3 2 Installation position The installation of inverter s...

Страница 7: ...lation resistance to ground of the PV string must exceed 19 33k in case of any shock hazard 3 PV string could not connect to earth grounding conductor 4 Use the right PV plugs in the accessory box Ste...

Страница 8: ...ommended table of AC circuit breakers INVERTER MODEL AC BREAKER SPECIFIFICATION FLS 50KTH S0 72A 400V 4P The absence of AC breaker on back up side will lead to inverter damage if an electrical short c...

Страница 9: ...fore connecting AC cable 13 14 A B C D Outside diameter Separated wire length Conductor wire length Conductor core section 30 40mm 200 250mm 20 25mm 15 20mm A B C D Connection terminal Screw Cap Cable...

Страница 10: ...e 7 8 Meter 485B Table 4 4 1 RS485 interface 2 Meter 485A 15 16 L3 CT3 CT2 CT1 L2 L1 N PE Grid Red line Black line Black line Black line Red line Red line L3 L2 L1 N PE Grid L3 L2 L1 N PE CT3 CT2 CT1...

Страница 11: ...7 8 DRM1 5 DRM2 6 DRM3 7 DRM4 8 REF COM 17 18...

Страница 12: ...MS Port On IVGM 8 1 8 1 Power Supply Lithium Battery Communication 19 20 DC Breaker AC Breaker AC Breaker GRID PE N L1 L2 L3 L1 L2 L3 N PE N L1 L2 L3 PE CT1 CT2 CT3 Ground AC Breaker AC Breaker 4 9 Wi...

Страница 13: ...C AC Normal Alarm Green led solid light Green led solid light Green led solid light Red led solid light Messages PV Connection normal Grid Connection normal Inverter operating normal Malfunction or wa...

Страница 14: ...nto the power curve page 1 Back up Power 2 Voltage Power for each Phase 3 Daily and total backup consump on 23 24 This is Grid detail page Press the Energy button will enter into the power curve page...

Страница 15: ...ackup load connected The hybrid inverter will neither provide power to the home load nor sell power to grid The built in CT will detect power owing back to the grid and will reduce the power of the in...

Страница 16: ...e the battery until the SOC reaches 40 At the same time if battery SOC is lower than 40 then grid will charge the battery SOC to 40 During 12 00 14 00 if battery SOC is lower than 90 it will use grid...

Страница 17: ...dervoltage protection point and protection time LV5 Level 5 undervoltage protection point and protection time Voltage Unbalance Grid voltage unbalance percentage protection point and protection time H...

Страница 18: ...l response to a new PF 0 9 Inductive reactive power Lock in Pn When the inverter output active power is higher then Lock in Pn rated power it will enter the P PF mode Lock out Pn When the inverter out...

Страница 19: ...ver frequency protection point and protection time HF2 Level 2 over frequency protection point and protection time LF1 Level 1 under frequency protection point and protection time LF2 Level 2 under fr...

Страница 20: ...nergy Distribution Priority Load BAT Grid 6 Work Mode 35 36 ECO mode During Charge Priority time period load is rst supplied with grid power If there is excess solar power after battery charging the e...

Страница 21: ...d 1 Access https download felicitysolar com using the mobile phone browser and download the latest installation package Method 2 Scan the following QR code and download the latest installation package...

Страница 22: ...rcurrent fault 23 Battery 1 is reversed check the battery wiring 24 Battery 1 reverse connection fault Battery 2 reverse connection fault 25 Battery 2 is reversed check the battery wiring Battery 1 SO...

Страница 23: ...Protection PV String Input Reverse Polarity Protection Battery Input Lightning Protection Battery Input Reverse Polarity Protection Insulation Resistor Detection Residual Current Monitoring Unit Outpu...

Отзывы: