Control Display 

The control display is located in the unit base. It is programmed to display the current set point 
associated with the control sensor located inside the air duct at the top of the case. 

Minimum Run Timer Feature 

The unit controller is programmed to have the condensing unit run a minimum of 5 minutes, 
regardless of the control temp being satisfied. If the temperature control reaches the cut out 
set point before 5 minutes, the minimum run time setting in the control will keep the unit in a 
run cycle mode until the timer reaches 5 minutes. The refrigeration cycle will be off until the 
temperature control cut in temperature is reached. 
 
This timer typically comes into effect in low ambient conditions where the unit may cycle too 
frequently to maintain proper product temperature. 

Maximum Run Timer Feature 

The unit controller is programmed to have the condensing unit run a maximum of 60 minutes.  
If the unit has not reached cut out temperature setting in 60 minutes, the unit goes into on off 
cycle. This typically comes into effect in high ambient temperature and relative humidity 
conditions. 
 

 

REFRIGERATION OPERATION 

 

Self-Contained Models   

 

 

Refrigeration R404A Charge Prior To 01/01/2020 

See Refrigeration 

And Electrical Data 

Pages 

 

Refrigeration R449a Charge After 01/01/2020 

See Refrigeration 

And Electrical Data 

Pages

 

The self-contained models are shipped from the factory with a completely operational 404A 
refrigeration system and require no modifications or adjustments upon installation. Case must 
be installed as per the installation section of this manual to provide proper condensing air 
cooling. 

 

 Self-Contained Refrigeration Operation 

The unit temperature is controlled by the Electronic control outlined in the control section of 
this manual. 
Note: The condenser fan is factory wired to run continuously.  

 

Dual Pressure Control 

(Self-Contained Models Only)

 

 

The  dual  pressure  control  is  used  as  a  safety  device  and  is  factory  set.  The  pressure 
control  works  on  a  differential.  The  low-pressure  side  is  a  safety  to  protect  the 
compressor in the case of refrigerant loss. The high-pressure side is a safety to protect 
from system failure causing too high of system pressure. 

 

The high side of the pressure control is factory set to 400psi and is not adjustable. 

 

Low  side  setting  for  the  R404a  cases  are  set  at  40psi  differential  for  the  cutout  and 
60psi for the cut-in. 

 

Refrigerated Self-Serve Merchandiser (High Profile) 

 

 

 

 

 

Page 13 

Содержание NSSL378

Страница 1: ...78 NSSL578 NSSL678 Non Refrigerated INSTALLATION OPERATION INSTRUCTIONS KEEP THIS MANUAL FOR FUTURE REFERENCE Engineering and technical data are subject to change without notice FEDERAL INDUSTRIES 215...

Страница 2: ...UNDING INSTRUCTIONS 6 Electrical Supply Wiring 6 Grounding Requirements 6 Optional permanent connection 6 OPERATING INSTRUCTIONS 7 Initial Start Up 7 Light Switch Lights 7 LED Light Replacement 7 Digi...

Страница 3: ...21 Special Service Situations 22 SALE DISPOSAL 22 Owner Responsibility 22 REFRIGERATION ELECTRICAL DATA 23 RSSL378 23 RSSL478 24 24A RSSL578 25 25A RSSL678 26 26A NSSL378 NSSL478 NSSL578 NSSL678 27 R...

Страница 4: ...rical work DANGER Improper or faulty hookup of electrical components in the case can result in severe injury or death All electrical wiring hookups must be done in accordance with all applicable local...

Страница 5: ...evere injury or death can occur if you ignore the message CAUTION Minor injury or damage to your case can occur if you ignore the message NOTICE This is important installation operation or service inf...

Страница 6: ...open doors or main door entrances Avoid locations where there is excessive air movement or air disturbances and avoid high humidity locations such as near cases with water misting or fogging devices T...

Страница 7: ...along the top of the display pan Shim under the case frame as needed to level the case It is recommended that the leveled case be sealed to the floor with an NSF Listed Sealant Condensate Evaporator N...

Страница 8: ...al shelf lights are furnished make certain that the shelf light cords are completely inserted into the sockets in the back panel and end of led lights or lights will not work The power supply used on...

Страница 9: ...each display case is required to prevent other appliances on the same circuit from overloading the circuit and causing malfunction The electrical service must be grounded upon installation See the ele...

Страница 10: ...h Led Light Replacement The light is attached to the shelf with plastic spring clips To remove a light un plug cord from end of bulb and pull down When replacing lights use direct equivalents to the o...

Страница 11: ...r approx three seconds The display will read On while the button is depressed When the control powers on the display will read the current set point a number 1 thru 9 The compressor run indicator will...

Страница 12: ...e and temperature as outlined in the Defrost Cycle section Pg Error Bookmark not defined of ELECTRONIC CONTROL PARAMETERS AND EXPLANATION OF OPERATION While it is uncommon that the automatic defrost c...

Страница 13: ...e You may mute the alarm by pressing and releasing the wrench button The red ringing bell and all error codes will still be displayed When the fault is remedied the control will return to normal opera...

Страница 14: ...proper operation on the unit Do not move or relocate this sensor The coil sensor is strapped to the evaporator coil and is labeled DEFROST This sensor location is critical for proper operation of the...

Страница 15: ...ade by downloading a new set of parameters using a program chip supplied by Federal Industries TAB PARAMETER DESCRIPTION RSSM3078 CONFIGURATION Controller Operation Temperature Units Degrees Fahrenhei...

Страница 16: ...ION OPERATION Self Contained Models Refrigeration R404A Charge Prior To 01 01 2020 See Refrigeration And Electrical Data Pages Refrigeration R449a Charge After 01 01 2020 See Refrigeration And Electri...

Страница 17: ...Note Check your State and Local regulations for approved refrigerants for your install location Federal Industries is not liable for any alternate refrigerants used The control is located on the base...

Страница 18: ...and should not exceed 100 feet 2 Refrigeration parts between condensing unit and case are typically supplied by installing contractor 3 Route properly sized and designed refrigeration lines from the...

Страница 19: ...month to insure proper refrigeration performance and to prevent compressor failure In some environments it may be necessary to clean more frequently Failure to clean condenser coil will void condense...

Страница 20: ...lights and power switches and remove all products from case Allow sufficient time for the unit to reach room temperature before proceeding with cleaning NOTICE Remove all products from the case befor...

Страница 21: ...y Clean all shelves and shelf brackets and dry with soft dry towel 3 Lift the display decks up and out of evaporator tub 4 Clean the display deck s using warm soapy water and a brush Rinse thoroughly...

Страница 22: ...before repositioning the shelf brackets The shelves can be installed horizontally or slanted at a 10 downward angle To change the shelf slant first remove the shelf from the shelf support Lift the she...

Страница 23: ...the Tech Support Warranty Option Email Service federalind com For Warranty Compressors please contact the Parts Department Phone 800 356 4206 and choose the Warranty Parts Option Email Parts Federalin...

Страница 24: ...ormance Make sure that warm product is not being installed inside the case All product must be pre chilled prior to loading for proper case performance Check temperature pressure control for proper se...

Страница 25: ...the case Any case malfunction or housekeeping problem that creates a slip fall hazard around or under a case should be corrected immediately SALE DISPOSAL Owner Responsibility If you sell or give awa...

Страница 26: ...REFRIGERATION Self Contained Models Refrigeration R449a Charge Self Contained After 01 01 2020 3 Pounds Refrigeration R404A Charge Self Contained Before 01 01 2020 3 Pounds The self contained models...

Страница 27: ...Fuse Size and Minimum Circuit Ampacity REFRIGERATION Self Contained Models Refrigeration R449a Charge Self Contained 4 Pounds The self contained models are shipped from the factory with a completely...

Страница 28: ...e case for Maximum Fuse Size and Minimum Circuit Ampacity REFRIGERATION Self Contained Models Refrigeration R404A Charge Self Contained 4 Pounds The self contained models are shipped from the factory...

Страница 29: ...m Fuse Size and Minimum Circuit Ampacity REFRIGERATION Self Contained Models Refrigeration R449a Charge Self Contained 4 Pounds The self contained models are shipped from the factory with a completely...

Страница 30: ...ty REFRIGERATION Self Contained Models Refrigeration R404A Charge Self Contained 4 Pounds The self contained models are shipped from the factory with a completely operational R404A refrigeration syste...

Страница 31: ...ize and Minimum Circuit Ampacity REFRIGERATION Self Contained Models Refrigeration R449a Charge Self Contained 4 25 Pounds The self contained models are shipped from the factory with a completely oper...

Страница 32: ...GERATION Self Contained Models Refrigeration R404A Charge Self Contained 4 25 Pounds The self contained models are shipped from the factory with a completely operational R404A refrigeration system and...

Страница 33: ...quency 60 Hertz 60 Hertz Phase 1 Phase 1 Phase Number of Wires 2 ground 2 ground AMPS VOLTS AMPS VOLTS Lights 0 7 120 0 3 208 240 Includes Optional Shelf Lights Refer to the rating plate data attached...

Страница 34: ...871 25C35 Power Supply Led 24V 39 20986 39 20986 39 20986 Light Switch On Off 41 11066 41 11066 41 11066 Heater Wire Assembly 43 14892 43 14892 43 19467 Condensate Pan SA5406 1 SA5406 1 SA5406 2 Conde...

Страница 35: ...066 41 11066 Heater Wire Assembly 43 14892 43 14892 43 19467 Condensate Pan SA5406 1 SA5406 1 SA5406 2 Condensate Pump 47 15686 47 15686 47 15687 Cord Plug RSSL378 43 30818 43 19090 Cord Plug NSSL378...

Страница 36: ...2 20871 38C35 Power Supply Led 24V 39 20986 39 20986 39 20986 Light Switch On Off 41 11066 41 11066 41 11066 Heater Wire Assembly 43 15926 43 15926 Condensate Pan SA5406 2 Condensate Pump 47 15687 47...

Страница 37: ...86 Light Switch On Off 41 11066 41 11066 41 11066 Heater Wire Assembly 43 14891 43 14891 43 15926 Condensate Pan SA5406 1 SA5406 1 SA5406 2 Condensate Pump 47 15686 47 15686 47 15687 Cord Plug RSSL478...

Страница 38: ...d 24V 39 20986 39 20986 39 20986 Light Switch On Off 41 11066 41 11066 41 11066 Heater Wire Assembly 43 20356 43 18043 Condensate Pan SA5406 2 SA5406 12 Condensate Pump 47 15687 47 15686 Cord Plug RSS...

Страница 39: ...Off 41 11066 41 11066 Heater Wire Assembly 43 20356 43 18043 Condensate Pan SA5406 2 SA5406 12 Condensate Pump 47 15687 47 15686 Cord Plug RSSL578 43 19090 Cord Plug NSSL578 43 11302 Miscellaneous Com...

Страница 40: ...35 42 20871 25C35 Power Supply Led 24V 39 20986 39 20986 39 20986 Light Switch On Off 41 11066 41 11066 41 11066 Heater Wire Assembly 43 19113 43 19113 Condensate Pan SA5406 2 SA5406 2 Condensate Pan...

Страница 41: ...Off 41 11066 41 11066 Heater Wire Assembly 43 19113 43 14893 Condensate Pan SA5406 2 SA5406 12 Condensate Pan 1800W OPTIONAL SA5406 3 SA5406 13 Condensate Pump 47 15687 47 15686 Cord Plug RSSL678 43 1...

Страница 42: ...INCHES DISPLAY DECK TOTAL SQUARE INCHES RSSL378 RSSL478 RSSL578 468 0 418 0 2290 0 622 0 555 0 3043 0 3865 0 705 0 790 0 2 2 11 5 2 7 3 6 4 6 2 9 15 2 3 7 19 4 NOTE CUBIC FEET IS MEASURED WITH 2 CLEAR...

Страница 43: ...ES NOT CYCLE WITH COMPRESSOR R G BLK BLK 18GA 14GA 14GA 14GA R BL OR W G FLOAT SWITCH M G BLK BR OR BLK CONDENSATE PUMP OPTIONAL CONDENSATE PUMP OR CONDENSATE EVAPORATOR AS PER ORDER 14GA 18GA R Y G B...

Страница 44: ...PERATE 120V 15A CIRCUIT REQUIRED BLK BASE FAN INSTALLED WHEN OPTIONAL CONDENSATE PAN IS USED STANDARD ON ALL REMOTES BLK R EEV 5 4 3 2 1 SUCTION SENSOR PRESS TRANS Blk Blk Red Wht Yel Grn Org Red RSV...

Страница 45: ...AN MOTOR TO RUN 100 DOES NOT CYCLE WITH COMPRESSOR W G BLK BLK 18GA 14GA 14GA 14GA W BL OR W G FLOAT SWITCH M G BLK BR OR BLK CONDENSATE PUMP OPTIONAL CONDENSATE PUMP OR CONDENSATE EVAPORATOR AS PER O...

Страница 46: ...RCUIT REQUIRED BLK BASE FAN INSTALLED WHEN OPTIONAL CONDENSATE PAN IS USED STANDARD ON ALL REMOTES LIGHTING CIRCUIT R B R B PLUG SOCKET PLUG SHELF LIGHT LED SHELF LIGHT LED SHELF LIGHT LED SHELF LIGHT...

Страница 47: ...LED BLK BLK BL G POWER SUPPLY 24V OUTPUT B R REMOTE 120V 60HZ NSSM NSSL 3 4 5 6 LED LIGHT CIRCUIT 91 21065 4 10 16 18 W BLK POWER IN W G BLK 120 VOLTS 60 HERTZ 1 PHASE W WHITE R RED BR BROWN G GREEN B...

Страница 48: ...5 4 BLK OR RED BLK OR RED 208 240 VOLTS 60 HERTZ 1 PHASE OPTIONAL POWER CORD WITH NEMA 6 20P PLUG CONDENSER FAN COMPRESSOR RELAY 4 5 2 1 FAN MOTOR LEAD REMOVED FROM TERMINAL 5 AND WIRED TO RUN 100 FAN...

Страница 49: ...100 FAN MOTOR TO RUN 100 DOES NOT CYCLE WITH COMPRESSOR W G BLK BLK 18GA 14GA 14GA 14GA W BL OR W G FLOAT SWITCH M G BLK BR OR BLK CONDENSATE PUMP OPTIONAL CONDENSATE PUMP OR CONDENSATE EVAPORATOR AS...

Страница 50: ...KET PLUG R B R B PLUG SOCKET PLUG SHELF LIGHT LED SHELF LIGHT LED SHELF LIGHT LED SHELF LIGHT LED SHELF LIGHT LED TOP LIGHT LED SHELF LIGHT LED SHELF LIGHT LED SHELF LIGHT LED SHELF LIGHT LED SHELF LI...

Страница 51: ...ly WARNING This product can expose you to chemicals including chromium which is known to the State of California to cause cancer and birth defects or other reproductive harm For more information go to...

Страница 52: ...LIGHT UPDATE BJW 11 01 18 3420 C USER CONTROL WARRANTY SERVICE PARTS UPDATE BJW 05 03 19 D CHANGED R449A TXV BJW 06 13 19 3497 E UPDATED DUAL PRESSURE CONTROL INFO ADC 8 6 19 3506 F UPDATED FOR R449a...

Отзывы: