CONDITION
Unit Noisy
Close proximity to the counter, vaulted ceilings, tile and overall open floor
plan as well as grouping equipment together can all amplify unit “noise”
Check that the condensing coil is not restricted.
If equipped, check that the condenser filter is not restricted
Check the evaporator and condenser fan blades are not hitting anything.
Check panels for loose fasteners and bent panels that can allow for
vibration.
Check refrigeration lines and condensing unit for vibration.
Check compressor for any abnormal noises.
Lights Not Working
Check that the light switch is on.
Shelf lights – lamp cord must be fully seated into receptacle, gently tap
them in with a rubber mallet if needed to make full contact. Check that the
lamp cord is plugged into
the end of the LED light strip. – Replace light if necessary.
Check power AC input voltage at LED driver.
Check to DC output voltage at LED driver.
If no output, disconnect output from unit wiring harness and try again as
LED driver will put itself into protect mode if output harness has a short. –
Replace driver if necessary.
NOISE AND LED LIGHTS
RSSM/RSSD/RSSL – ERSSHP – TSSM - NSSM - LMD/LMDM – LPRSS/ELPRSS
OPEN AIR MERCHANDISERS