Check the seams on the pan if it is a folded pan as the silicone could be
compromised. Reseal if necessary or replace pan assembly as needed.
If the single PTC heater is heating, it is likely not the problem with the
proper voltage applied.
If equipped, check that condensate pan or pump is properly plugged in or
hardwired to power
.
If the pump is running, but cannot evacuate to water,
clean the condensate pump impeller, drain tube and discharge tubing or
replace pump assembly as required.
Note: Owner Responsibility
Pump and deck may be removed from tank by pushing tabs located on
tank sides away from the deck while lifting on pump cover.
Periodically inspect the condensate pump tank to assure it is free of
accumulated dirt or sludge.
DO NOT
use solvent cleaners. Clean tank
with soap and warm water only. Check valve may be removed for
cleaning or replacement by unscrewing with a 9/16” wrench. Clean Inlet
and outlet piping. Reassemble system and check for correct operation.
CRR/RSS
Hybrid Merchandiser Top
Section Refrigerated Only.
Check that the drain trap assembly did not become dislodged during
shipment or installation and that it is correctly positioned over the
condensing unit pan with hot gas loop.
Check that the drain trap is free of debris such as algae, food product and
packaging.
31