Table 3 Choosing cable-entry devices for
Equipment in Potentially Explosive Atmospheres
Models
Ex
Atmospheres
Cable Entry Devices
(cable glands, stopping plugs, etc.)
G-LED-XXX-D-X
(Ex db surface mount)
Gas
Cable entry devices shall be equipment
certified as flameproof. To maintain the ingress
protection of the flameproof beacon enclosure,
we recommend the cable entry device be
IP66 certified.
G-LED-XXX-E-X
(Ex db surface mount)
Gas
For the flameproof beacon enclosure, cable
entry devices shall be equipment certified
as flameproof. To maintain the ingress
protection of the flameproof beacon enclosure
we recommend the cable entry device be
IP66 certified. For the increased safety
terminal enclosures (terminal boxes), cable
entry devices shall be equipment certified
as increased safety and shall maintain an
IP rating of IP54.
G-LED-XXX-D-X
(Ex db surface mount)
G-LED-XXX-E-X
(Ex db e surface
mount)
Dust
Cable entry devices for the Beacon and
terminal enclosures shall be equipment
certified as dust protected. To maintain the
ingress protection of the beacon and terminal
enclosures the cable entry devices shall be
IP6X certified.