5. 

Follow the instructions starting below for your line voltage and continue to Step 6 on page 6. Refer to Figure 6 for 

the voltage selector switch and Table 1 on page 9 for the tone chart. For remote tone selection, refer to Table 

5 on page 14. 

Figure 7  Locations of tone and volume switches

TONE 

SELECTOR 

SWITCH

VOLUME 

CONTROL: FULL 

CLOCKWISE 

=  MAX. VOLUME

220-240 Vac Operation (no remote switching of tones)

a. 

Set the voltage selector switches to 230 and AC.

b. 

Turn the tone selector switch to the desired tone.

c. 

Connect the line (hot) power source wire to the terminal block position marked L1 on the PCB.

d. 

Connect the neutral (common) power source wire to the terminal block position marked L2 on the PCB.

e. 

Connect ground wire to the terminal block position marked EARTH.

120 Vac operation (no remote switching of tones)

a. 

Set the voltage selector switches to 120 and AC.

b. 

Turn the tone selector switch to the desired tone.

c. 

Connect the line (hot) power source wire to the terminal block position marked L1 on the PCB.

d. 

Connect the neutral (common) power source wire to the terminal block position marked L2 on the PCB.

e. 

Connect ground wire to the terminal block position marked EARTH.

24 Vdc operation (no remote switching of tones)

a. 

Set the voltage selector switches to 230 and DC.

b. 

Turn the tone selector switch to the desired tone.

c. 

Connect the positive (+) power source wire to the terminal block position marked L1 on the PCB.

d. 

Connect the negative (–) power source wire to the terminal block position marked L2 on the PCB.

e. 

Connect ground wire to the terminal block position marked EARTH.

220-240 Vac operation (remote switching of tones)

a. 

Set the voltage selector switches to 230 and AC.

b. 

Set the tone selector switch to 0.

c. 

Connect the line (hot) power source wire to the terminal block position marked L1 on the PCB.

d. 

Connect the neutral (common) power source wire to the terminal block position marked L2 on the PCB.

e. 

Connect ground wire to the terminal block position marked EARTH.

f. 

Connect the common wire from the remote switching device to the terminal block position marked SEL.

Содержание G-SND

Страница 1: ...e in certain situations permanent hearing loss You should take appropriate precautions such as wearing hearing protection After installation test the sound system to ensure proper operation The purcha...

Страница 2: ...arge The metallic brass inserts have a capacitance of 24 pF See the manufacturer s instructions for further information cULus Zone Certifications This equipment is for use in Class I Zone 1 and Zone 2...

Страница 3: ...the product is Ex db marked only it is for use in gas atmospheres If the product is Ex db e marked it uses the increased safety terminal enclosures and is only for gas atmospheres If the product is Ex...

Страница 4: ...Ex d e Surface Mount Sounder Mount the sounder to a flat surface using the six 8 5 mm mounting holes Use installer supplied fasteners suitable for the surface to which the device will be mounted Figu...

Страница 5: ...eassembling the unit Painting and surface finishes other than those applied by Federal Signal Corporation are not permitted Cable termination should be in accordance with specifications applying to th...

Страница 6: ...a of the phase conductor Cable termination for these models should be in accordance with specifications applying to the application It is recommended that all cables and cores be fully identified Use...

Страница 7: ...Connect the line hot power source wire to the terminal block position marked L1 on the PCB d Connect the neutral common power source wire to the terminal block position marked L2 on the PCB e Connect...

Страница 8: ...osition marked L2 on the PCB d Connect the positive power source wire to the terminal block position marked L1 on the PCB e Connect the ground wire to the terminal block position marked EARTH f Connec...

Страница 9: ...1 s Factory setting Preparing to Wire the Ex de Increased Safety Models SHOCK HAZARD To avoid electrical shock hazards do not connect wires when power is applied Failure to observe this warning may l...

Страница 10: ...r side of any terminal must be joined in a suitable manner e g two conductors into a single insulated crimped bootlace ferrule 3 To connect wires press the button on the terminal block with a Phillips...

Страница 11: ...y two tones are remotely selectable on Ex de 120 Vac units 24 Vdc operation remote switching of tones with remote power a Connect the negative power source wire to the position marked L2 on the termin...

Страница 12: ...hat the nameplate remains readable After performing any maintenance test the sounder system to ensure that it is operating properly Failure to follow all safety precautions and instructions may result...

Страница 13: ...14 In Line E Box Coupler Kit G KIT EC180 90 Degree E Box Coupler Kit G KIT EC90 Extension Box Spacer Kit G KIT EXTB Single Trunnion Kit G KIT ST Dual Trunnion Kit G KIT DT Adapter M20 Male to 1 2 Fema...

Страница 14: ...ltage Vdc 16 Vdc to 33 Vdc NOTE UL evaluated this product only to the stated operational voltage range It was not evaluated to 80 to 110 of the voltage range The sounder is factory set with the tone s...

Страница 15: ...echnical Assistance Contact our Technical Support Team at 1 708 587 3587 or signalsupport fedsig com Repair Service A return authorization is required Contact your Authorized Distributor or Federal Si...

Страница 16: ...dicionales disponibles en signaling fedsig com Customer Support 1 800 344 4634 1 708 534 4756 iordersup fedsig com Technical Support 1 800 755 7621 1 708 587 3587 signalsupport fedsig com signaling fe...

Отзывы: