Federal Signal

 signaling.fedsig.com

Certification

Certificate Nos.

• 

IECEx Cert No.:IECEx BAS 15.0104X

• 

UKEX Cert No,: SGS23UKEX0086X

• 

ATEX Cert No.: Baseefa15ATEX0155X  

• 

ATEX coding: 

 II 2 G D

Protection

• 

Ex db IIB T5 Gb or Ex db e IIB T5 Gb

• 

Ex tb IIIC T100°C Db IP66 (Tamb= -55°C to + 49°C)

• 

Ex db IIC T4 Gb or Ex db e IIC T4 Gb

• 

Ex tb IIIC T135°C Db IP66 (Tamb= -55°C to + 70°C)

Standards

• 

EN60079-0:2018 

• 

EN60079-1:2014

• 

EN IEC 60079-7:2015+A1:2018

• 

EN60079-31:2014

• 

IEC60079-0:2017 7th Ed

• 

IEC60079-1:2014-06 7th Ed I

• 

EC60079-7:2017 5.1 Ed

• 

IEC60079-31:2013 2nd Ed.

Specific Conditions of Use

• 

The Modular Audible Device enclosure incorporates a sinter and the volume is greater than 100 cm

3

; therefore, use 

of the Modular Audible Device in a carbon disulphide gas atmosphere is not permitted.

• 

The Modular Audible Device has external non-metallic surfaces that may provide an electrostatic charging hazard. 

See the manufacturer's instructions for further information.

• 

The Modular Audible Device has metallic components in the non-metallic walls of the enclosure that can store 

electrical charge and therefore may provide a potential electrostatic discharge. The metallic brass inserts have a 

capacitance of 24 pF. See the manufacturer's instructions for further information.

cULus Zone Certifications

This equipment is for use in Class I, Zone 1, and Zone 21 hazardous (classified) locations. It has been investigated with 

reference to risks to life and property and for conformity to the installation and use in provisions of Articles 505 and 506 

of NFPA 70 (NEC).

These models use protections:

• 

Class I, Zone 1, AEx db IIC T4 Gb or AEx db eb IIC T4 Gb

• 

Zone 21, AEx tb IIIC T135°C Db IP66 (Tamb= -55°C to +70°C)

• 

Ex db IIC T4 Gb or Ex db eb IIC T4 Gb

• 

Ex tb IIIC T135°C Db IP66 (Tamb= -55°C to +70°C)

UL Fire Alarm Certifications

See page 14.

Unpacking the Sounder

After unpacking the sounder, examine it for damage that may have occurred in transit. If it has been damaged, do not 

attempt to install or operate it. File a claim immediately with the carrier, stating the extent of the damage. Carefully 

check all envelopes, shipping labels, and tags before removing or discarding them. If any parts are missing, please call 

Federal Signal Customer Support at +1 708-534-4756 or +1 877-289-3246. 

Creating Combination Fixtures in the Field

The Federal Signal Global Series Ex de products can be connected together in the field using interchangeable E-box end 

caps and a proprietary coupling system. See Figure 1.

Содержание G-SND

Страница 1: ...e in certain situations permanent hearing loss You should take appropriate precautions such as wearing hearing protection After installation test the sound system to ensure proper operation The purcha...

Страница 2: ...arge The metallic brass inserts have a capacitance of 24 pF See the manufacturer s instructions for further information cULus Zone Certifications This equipment is for use in Class I Zone 1 and Zone 2...

Страница 3: ...the product is Ex db marked only it is for use in gas atmospheres If the product is Ex db e marked it uses the increased safety terminal enclosures and is only for gas atmospheres If the product is Ex...

Страница 4: ...Ex d e Surface Mount Sounder Mount the sounder to a flat surface using the six 8 5 mm mounting holes Use installer supplied fasteners suitable for the surface to which the device will be mounted Figu...

Страница 5: ...eassembling the unit Painting and surface finishes other than those applied by Federal Signal Corporation are not permitted Cable termination should be in accordance with specifications applying to th...

Страница 6: ...a of the phase conductor Cable termination for these models should be in accordance with specifications applying to the application It is recommended that all cables and cores be fully identified Use...

Страница 7: ...Connect the line hot power source wire to the terminal block position marked L1 on the PCB d Connect the neutral common power source wire to the terminal block position marked L2 on the PCB e Connect...

Страница 8: ...osition marked L2 on the PCB d Connect the positive power source wire to the terminal block position marked L1 on the PCB e Connect the ground wire to the terminal block position marked EARTH f Connec...

Страница 9: ...1 s Factory setting Preparing to Wire the Ex de Increased Safety Models SHOCK HAZARD To avoid electrical shock hazards do not connect wires when power is applied Failure to observe this warning may l...

Страница 10: ...r side of any terminal must be joined in a suitable manner e g two conductors into a single insulated crimped bootlace ferrule 3 To connect wires press the button on the terminal block with a Phillips...

Страница 11: ...y two tones are remotely selectable on Ex de 120 Vac units 24 Vdc operation remote switching of tones with remote power a Connect the negative power source wire to the position marked L2 on the termin...

Страница 12: ...hat the nameplate remains readable After performing any maintenance test the sounder system to ensure that it is operating properly Failure to follow all safety precautions and instructions may result...

Страница 13: ...14 In Line E Box Coupler Kit G KIT EC180 90 Degree E Box Coupler Kit G KIT EC90 Extension Box Spacer Kit G KIT EXTB Single Trunnion Kit G KIT ST Dual Trunnion Kit G KIT DT Adapter M20 Male to 1 2 Fema...

Страница 14: ...ltage Vdc 16 Vdc to 33 Vdc NOTE UL evaluated this product only to the stated operational voltage range It was not evaluated to 80 to 110 of the voltage range The sounder is factory set with the tone s...

Страница 15: ...echnical Assistance Contact our Technical Support Team at 1 708 587 3587 or signalsupport fedsig com Repair Service A return authorization is required Contact your Authorized Distributor or Federal Si...

Страница 16: ...dicionales disponibles en signaling fedsig com Customer Support 1 800 344 4634 1 708 534 4756 iordersup fedsig com Technical Support 1 800 755 7621 1 708 587 3587 signalsupport fedsig com signaling fe...

Отзывы: