Preparing to Wire the Ex d Flameproof Models

SHOCK HAZARD 

- To avoid electrical shock hazards, do not connect wires when power is applied. Failure to observe this 

warning may lead to serious injury or death.

CIRCUIT BOARD DAMAGE

 - The DC sounders are polarity sensitive and MAY BE DAMAGED by incorrect electrical 

hookup. When connecting the DC sounder to the voltage supply lines, POLARITY MUST BE OBSERVED. In addition, 

damage will result if the voltage rating of the particular model is exceeded by more than 10 percent.

This section has wiring instructions for the flameproof models G-SND 24 Vdc, 120 Vac, 220-240 Vac.

Ex d units are supplied with an eleven-position PCB-mounted screw terminal block. The maximum wire gauge is 4 mm  

(12 AWG). The wire must be rated 85°C or higher. Use only stranded cable to terminate the sounder. The cross-sectional 

area of the primary earth (ground) must equal the cross-sectional area of the phase conductor.

Cable termination for these models should be in accordance with specifications applying to the application. It is 

recommended that all cables and cores be fully identified. Use the appropriate cable gland for the application. Gland 

entry threads are M20-1.5 x 6H.

Tools needed:

• 

1.5 mm A/F hexagon key

• 

2 mm flat-tip screwdriver

• 

No. 1 Phillips

®

 screwdriver

• 

Wire stripper

Figure 6  Ex d in/out PCB connections

VOLTAGE 

SELECTOR 

SWITCH

D8

D2

D1

D4

D3

J1

F1

S1

S2

F2

D7

D5

D6

R1

DC

120

230

AC

T4

T3

T2

T1 SEL EARTH

L2

L2

L1

L1

Wiring the Ex d Models

To wire the Ex d flameproof sounder:

1. 

Unscrew the M3 hex set screw on the side of the housing one full turn.

2. 

Remove the cover from the housing by turning the cover counterclockwise. Three 120-degree spaced reliefs are 

provided for a 3/8-inch spanner wrench if needed. If the cover will not unscrew, back out the set screw a few 

additional turns.

3. 

Loosen the captive Phillips

®

 screw retaining the driver/printed circuit board (PCB).

4. 

Slide out the PCB until the terminals clear the housing. Strip the wire insulation 6.5 mm (0.25 in). Maximum screw 

tightening torque is 0.5 N•m (4.5 in-lb).

Содержание G-SND

Страница 1: ...e in certain situations permanent hearing loss You should take appropriate precautions such as wearing hearing protection After installation test the sound system to ensure proper operation The purcha...

Страница 2: ...arge The metallic brass inserts have a capacitance of 24 pF See the manufacturer s instructions for further information cULus Zone Certifications This equipment is for use in Class I Zone 1 and Zone 2...

Страница 3: ...the product is Ex db marked only it is for use in gas atmospheres If the product is Ex db e marked it uses the increased safety terminal enclosures and is only for gas atmospheres If the product is Ex...

Страница 4: ...Ex d e Surface Mount Sounder Mount the sounder to a flat surface using the six 8 5 mm mounting holes Use installer supplied fasteners suitable for the surface to which the device will be mounted Figu...

Страница 5: ...eassembling the unit Painting and surface finishes other than those applied by Federal Signal Corporation are not permitted Cable termination should be in accordance with specifications applying to th...

Страница 6: ...a of the phase conductor Cable termination for these models should be in accordance with specifications applying to the application It is recommended that all cables and cores be fully identified Use...

Страница 7: ...Connect the line hot power source wire to the terminal block position marked L1 on the PCB d Connect the neutral common power source wire to the terminal block position marked L2 on the PCB e Connect...

Страница 8: ...osition marked L2 on the PCB d Connect the positive power source wire to the terminal block position marked L1 on the PCB e Connect the ground wire to the terminal block position marked EARTH f Connec...

Страница 9: ...1 s Factory setting Preparing to Wire the Ex de Increased Safety Models SHOCK HAZARD To avoid electrical shock hazards do not connect wires when power is applied Failure to observe this warning may l...

Страница 10: ...r side of any terminal must be joined in a suitable manner e g two conductors into a single insulated crimped bootlace ferrule 3 To connect wires press the button on the terminal block with a Phillips...

Страница 11: ...y two tones are remotely selectable on Ex de 120 Vac units 24 Vdc operation remote switching of tones with remote power a Connect the negative power source wire to the position marked L2 on the termin...

Страница 12: ...hat the nameplate remains readable After performing any maintenance test the sounder system to ensure that it is operating properly Failure to follow all safety precautions and instructions may result...

Страница 13: ...14 In Line E Box Coupler Kit G KIT EC180 90 Degree E Box Coupler Kit G KIT EC90 Extension Box Spacer Kit G KIT EXTB Single Trunnion Kit G KIT ST Dual Trunnion Kit G KIT DT Adapter M20 Male to 1 2 Fema...

Страница 14: ...ltage Vdc 16 Vdc to 33 Vdc NOTE UL evaluated this product only to the stated operational voltage range It was not evaluated to 80 to 110 of the voltage range The sounder is factory set with the tone s...

Страница 15: ...echnical Assistance Contact our Technical Support Team at 1 708 587 3587 or signalsupport fedsig com Repair Service A return authorization is required Contact your Authorized Distributor or Federal Si...

Страница 16: ...dicionales disponibles en signaling fedsig com Customer Support 1 800 344 4634 1 708 534 4756 iordersup fedsig com Technical Support 1 800 755 7621 1 708 587 3587 signalsupport fedsig com signaling fe...

Отзывы: