Limited Warranty: 

This product’s limited warranty can be found at www.fedsig.com/SSG-Warranty

SAFETY MESSAGES TO INSTALLERS AND USERS

 

: Products should be installed by a licensed electrician and follow 

all safety instructions. Failure to do so may result in property damage, serious injury, or death.

• 

Read and understand all instructions before installing or operating this equipment.

• 

To avoid electrical shock hazards, do not connect wires when power is applied. Failure to observe this warning may 

lead to serious injury or death.

• 

Never alter the unit in any manner. Safety in hazardous locations may be endangered if additional openings or other 

alterations are made in units specifically designed for use in these locations.

• 

Do not connect this station to the system when power is on.

• 

After installation, ensure that all threaded joints are properly tightened.

• 

Keep the unit tightly closed when in operation.

• 

After installation, test the station and the system to ensure that it is operating properly.

• 

After testing is complete, provide a copy of this instruction sheet to all personnel.

• 

Establish a procedure to routinely check the station and system for proper activation and operation.

Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death.

Certifications

ATEX and IECEx Certification Information:

Certificate Nos.

ATEX Cert No.: DEMKO 19 ATEX 1939X 

IECEx Cert No.: IECEx UL 19.0074X

ATEX coding

 II 2 G D

Protection

II 2 G Ex db eb mb IIC T4 Gb (Tamb= -40°C to +70°C) 

CP-BG models: II 2 D Ex tb IIIC T100°C Db IP66 

CP-PB models: II 2 D Ex tb IIIC T100°C Db IP65

EN60079-0, EN60079-1, EN60079-7, EN60079-18, EN60079-31, IEC60079-0, IEC 60079-1, IEC60079-7, IEC60079-18, 

IEC60079-31

Refer to Certificates for specific standard versions.

Specific Conditions of Use

1. 

The equipment has an optional protective non-metallic cover that may provide a potential electrostatic charging 

hazard.

Manual Call Point

Pushbutton and Break Glass Stations for Use in 

Hazardous Locations

25500424 Rev A2 0522

Содержание CP-PB Series

Страница 1: ...stallation test the station and the system to ensure that it is operating properly After testing is complete provide a copy of this instruction sheet to all personnel Establish a procedure to routinel...

Страница 2: ...11 certification 3 To enable correct installation and operation review all sections in this manual 25500424A for all technical installation and maintenance data UL C UL Signaling Certification Inform...

Страница 3: ...einforced polyester GRP thermoset plastic housing and faceplate for corrosion resistance 40 C to 70 C ambient operational coverage Static dissipative GRP housings and faceplates One or two switches av...

Страница 4: ...d 6 V 12 V 24 V or 48 V LED bi color status indicator High impact resistant clear polycarbonate cover flap with or without various instructional labels e g LIFT COVER BREAK GLASS TO ACTIVATE on interi...

Страница 5: ...inter Figure 1 Removing the keyway UNLOOSENM4SETSCREW TOREMOVERESET KEYWAYANDBEARING WASHERIFPRESENT UNLOOSENTWOM4 CAPTIVATEDSCREWS REMOVE BUTTON ANDSCREW Figure2 ACTUATORSPRING PIVOTBOSSES CLEAR ACTU...

Страница 6: ...Chamber Access All models of the Call Point station have the same rear chamber access method for internal wiring management mounting the unit to a vertical wall surface and general maintenance routin...

Страница 7: ...accordance with the installation instructions and local jurisdictions and codes Use installer supplied fasteners suitable for the mounting surface All models of the Call Point station have the same re...

Страница 8: ...corrosive environment applications mounting the station to a rigid surface Ensure that all cable glands and stopping plugs are certified with a suitable sealing washer o ring to ensure the NEMA IP ra...

Страница 9: ...on the aluminum mounting bracket and remove it from the rear housing taking care as it still remains directly wired to the front housing assembly 2 Strip the incoming wiring leads to the station to t...

Страница 10: ...ull double throw switch device on a double pull double throw device input terminals 6 7 and 8 are used as secondary inputs with common Figure 8 Standard SPDT switch wiring Figure 9 Standard DPDT switc...

Страница 11: ...tivation current draw of 13 mA of the red alarm state LED function will not interfere with the alarm notification panel If it does the hookup of the red LED lead must be disconnected from the terminat...

Страница 12: ...990 00 1320 00 3300 411 41 767 44 1164 71 1650 00 4700 427 27 824 56 1301 54 1938 75 5000 429 62 833 33 1323 53 1987 95 5600 433 61 848 48 1362 16 2076 40 10000 448 90 909 09 1525 42 2481 20 12000 452...

Страница 13: ...ATE ACTIVATION INDICATOR STATUS POSITIONS VISUAL ACTIVATION INDICATOR WITH RESET KEYWAY ALARM STATEACTIVATED Reset Test For the manual pushbutton stations resetting is accomplished by rotating the act...

Страница 14: ...s resetting is accomplished by either of two methods following the previously mentioned two methods of activating the stations 1 To replace the broken glass panel follow the directions on page 16 Once...

Страница 15: ...re some important safety instructions and precautions you should follow with regards to all instructions within this manual Read and understand all instructions before operating this system If you acq...

Страница 16: ...this manual to do so Replacing the Break Glass Panel CP BG units To replace a broken glass panel on the station CUTTING HAZARD Safety gloves are required when accessing the internal front chamber with...

Страница 17: ...DELS Installing Servicing the Reset Keyway The reset keyway is factory attached on the CP PB and CP BG stations On the CP BG x x x xxx xx 2 E54 11 approved stations it is provided separately to be use...

Страница 18: ...ertified models To remove or remove reattach a cover flap 1 Remove the front faceplate per directions found earlier in Call Point Front Chamber Access on page 5 Place the two stainless steel pivot pin...

Страница 19: ...es resistor along with two wire ties Tools needed after internal access Wire cutter 1 Philips screwdriver To service the module 1 Ensure that the power is off and the station is in NORMAL mode 2 Open...

Страница 20: ...reseat the module in its reliefs screw it in place and try again e After confirming that the station actuates properly use the two wire ties provided within the kit to bundle and tie the switch wires...

Страница 21: ...station faceplate s designated label area Make sure the application area is free from any dirt smudges or oil prior to application Figure 31 Installing the label OPTIONALINDIVIDUALSTAINLESSSTEELFACEP...

Страница 22: ...ion of hazardous atmospheres disconnect the fixture from the supply circuit before opening EXPLOSION HAZARD Substitution of any component may impair suitability for Class I Division 2 Service Technica...

Страница 23: ...used with 24V LED option 2 2K 2200 2 4K 2400 3 3K 3300 also used with 48V LED option 3 6K 3600 4 7K 4700 5 6K 5600 10K 10000 12K 12000 15K 15000 22K 22000 33K 33000 47K 47000 Potted Diode Module 5A K...

Страница 24: ...g com signaling fedsig com Part Description Federal Signal Part Use Faceplate Label EN54 11 K71400701A CP BG x x x xxx xx 2 EN54 11 stations Faceplate Label Stainless Steel FIRE K71400976A 01 CP BG an...