11
Installation and Maintenance Instructions
Model 371LED-120 Rotating Light
Wiring the Light
SHOCK HAZARD
To avoid electrical shock hazards, do not connect wires while
power is applied.
The Model 371LED comes assembled from the factory with two
color-coded leads for wiring to a junction box. If desired, the
factory leads can be removed and the supply connections can be
directly made to the terminal block located on the bottom of the
light base as described below
1.
Disassemble the light (Figure 4 on page 12):
a)
Remove the dome assembly by grasping the die-cast ring
attached to the dome and turning it counter-clockwise.
b)
Remove three #10 Phillips screws that secure the LED
/
motor module to the housing.
c)
Remove the LED
/
motor module.
d)
If preferred, remove the factory-supplied leads from the
terminal block.
2.
If you are using conduit side-entries, attach a Myers®
STTTB-2 or a T&B
®
H075TBH 3/4-inch NPT conduit hub
with a 3/4-inch NPT close nipple (both installer-supplied)
to the housing and securely tighten the hub. When side
entries are used, the bottom 1-inch NPT conduit entry must
be plugged with a threaded plug (installer-supplied). (See
“Table 4 Accessories” on page 15.)
3.
Route the supply wires (10 AWG to 16 AWG) into the light
housing.
4.
Strip a maximum of 0.28 inch (7 mm) of insulation from
the ends of the power leads. Connect the wires to the
terminal block by inserting the stripped ends of the wires
into the connectors as far as they can travel.