Installation and Maintenance Instructions
Models 151XST and 151XST-S
Table 3 Flash rate and candelas
Model
Flash Rate
per Minute
Candela
Peak
1
ECP
2
151XST(-S) 012-024__
80
520,000
165
151XST(-S)-120__
80
520,000
165
151XST(-S)-240__
80
520,000
165
__ Indicates color: (A) amber, (B) blue, (C) clear, (G) green,
(M) magenta or (R) red.
1
Peak candela is the maximum light intensity generated
by a flashing light during its light phase.
2
ECP (Effective Candela) is the intensity that would appear
to an observer if the light were burning steadily.
Table 4 Hazardous Location Rating
Temperature Code at Maximum Temperature, °C
Hazardous Location
66 ºC
Class I, Div 2, Groups A, B, C & D
T1/301º
Class II, Div 1, Groups E, F & G
T5/100º
Class III
T5/100º
To reduce the risk of fire or explosion, do not install the beacon
in a hazardous location if the operating temperature exceeds the
ignition temperature of hazardous atmosphere.
Before proceeding, use Table 4 above as a guide and determine
that the unit’s operating temperature DOES NOT exceed the
hazardous atmosphere’s ignition temperature.
For marine applications, all wiring including supply wire must be
stranded wire and meet the USCG (CFR46) Sections (110-113).
NOTE:
In high-humidity environments when units are mounted
dome down, condensation may occur in the conduit system. Use
properly rated conduit seals/drains to prevent moisture from
entering the fixture.