CONNECT REFRIGERANT PIPING

The following guidelines should be followed when installing
refrigerant piping. Comply with all local, state, and federal
codes and/or regulations pertaining to this type of
equipment and its installation.

1.  Run the tubing by the most direct route and support

every few feet. Do not run the lines underground unless
they are in a chase. Leave enough material between
structure and unit to absorb vibration.

2.  Insulate the vapor line to prevent sweating and line loss.

In underground chases, the vapor line should be
insulated to provide vibration isolation between the
vapor and liquid line. A minimum of 3/8” insulation is
recommended in conditioned space and 1/2” to 3/4” in
unconditioned space. Ensure that tubing insulation is
pliable and completely surrounds vapor tube.

3.  In general, the piping should be sloped toward the

outdoor unit to prevent oil trapping. Where vertical
risers occur, a suction line trap should be located at the
base of the riser to assure proper oil return.

Precautions

Refer to the chart below for the minimum recommended tube
outside diameter sizes on liquid and suction lines. Ensure that
vapor and liquid tube diameters are appropriate for unit
capacity. Run refrigerant tubes as directly as possible by
avoiding unnecessary turns and bends.

Undersized line sets will increase the refrigerant pressure drop
between the indoor evaporator and outdoor unit, resulting in
a decrease in system capacity. Oversizing the line sets may result
in excessive refrigerant charge, thereby making the system
more susceptible to liquid migration.

When passing refrigerant tubes through the wall, seal opening
with RTV or other pliable silicon based caulk.

Avoid direct tubing contact with water pipes, duct work, floor
joists, wall studs, floors, and walls.

Do not suspend refrigerant tubing from joists and studs with a
rigid wire or strap which comes in direct contact with tubing.

When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. 

Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.

Condensing units are available with pre-charged, sweat-type
copper connecting fittings.

Units are factory charged for 15’ of line set tubing.

Adjust charge 0.65 oz per foot of variation from chart for
1/4" and 5/8" line set.

Adjust charge 0.66 oz per foot of variation from chart for
3/8” and 3/4” line set.

Adjust charge 0.67 oz per foot of variation from chart for
3/8" and 7/8" line set.

Adjust charge 0.72 oz per foot of variation from chart for
1/2" and 1 1/8" line set.

WARNING

IF THE INSTALLER IS MAKING UP HIS OWN LINE SETS, HE
MUST MAKE SURE THE TUBING IS CLEAN OF ANY
IMPURITIES OR MOISTURE. USE ONLY CLEAN AIR
CONDITIONING AND REFRIGERATION GRADE SEAMLESS
COPPER TUBING. PLUMBING GRADE COPPER IS
INADEQUATE. TO ENSURE A CLEAN SYSTEM FREE OF ANY
CONTAMINANTS, PURGING WITH DRY NITROGEN AND A
DEEP VACUUM IS NECESSARY ON ALL SWEAT-TYPE
MODELS AND ON THE UNCHARGED PORTIONS OF ALL
MODELS NOT INCORPORATING PRECHARGED LINES. IT IS
DESIRABLE TO PULL A VACUUM TO 1,000 MICRONS (29.96”
HG) TO ENSURE TROUBLE FREE OPERATION.

3” MIN.

10’ MAX

20’

OUTDOOR
SECTION

INDOOR
COIL

LIQUID 
LINE

SUCTION 
LINE

LIQUID LINE SIZES

CONDENSER

MODEL

NUMBER

C18ABD1

3/8”

3/8”

3/8”

3/8”

C24ABD1

3/8”

3/8”

3/8”

3/8”

C30ABD1

3/8”

3/8”

3/8”

3/8”

C36ACD1

3/8”

3/8”

3/8”

3/8”

C42ACD1

3/8”

3/8”

3/8”

3/8”

C48ACD1

3/8”

3/8”

3/8”

3/8”

C60ACD1

1/2”

1/2”

1/2”

1/2”

LINE SET LENGTH AND SIZE

15 FT

LINE SET

25 FT

LINE SET

50 FT

LINE SET

75 FT*

LINE SET

SUCTION LINE SIZES

CONDENSER

MODEL

NUMBER

C18ABD1

3/4”

3/4”

3/4”

3/4”

C24ABD1

3/4”

3/4”

3/4”

3/4”

C30ABD1

7/8”

7/8”

7/8”

7/8”

C36ACD1

7/8”

7/8”

7/8”

7/8”

C42ACD1

7/8”

7/8”

7/8”

1 1/8”

C48ACD1

7/8”

7/8”

7/8”

1 1/8”

C60ACD1

1 1/8”

1 1/8”

1 1/8”

1 1/8”

15 FT

LINE SET

25 FT

LINE SET

50 FT

LINE SET

75 FT*

LINE SET

WARNING

REFRIGERANT LINE LENGTH MUST NOT EXCEED 75’ ON
HORIZONTAL RUNS AND 40’ ON VERTICAL RISERS.

LINE SET LENGTH AND SIZE

* DO NOT EXCEED 75 FT MAX LINE SET LENGTH

Can only be
20’ vertical
separation
without
additional
accessories.

11

7

Содержание Split System Air Conditioner

Страница 1: ...Braze Joints 3 Evacuation 3 Opening the Service Valve Step Valve 3 CONNECT REFRIGERANT PIPING 4 Precautions 4 Liquid Line Sizes 4 Suction Line Sizes 4 SUBCOOLING CHARGING 5 OPERATION INSTRUCTIONS 5 MAINTENANCE INSTRUCTIONS 5 CONDENSING UNIT NOMENCLATURE 6 LIMITED WARRANTY 7 NOTE THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATIO...

Страница 2: ... representations contained in the limited warranty CODES The installer SHALL comply with all local state and federal codes and or regulations pertaining to this type of equipment and its installation Such codes and or regulations should take precedence over any recommendations contained herein in lieu of local codes Installations SHALL be made in accordance with the National Electrical Code local ...

Страница 3: ...denser as close as possible to the evaporator will increase the system capacities by reducing the line set refrigerant pressure drop and will make the system less susceptible to liquid migrations due to less refrigerant charge 1 The installer shall check available power to make certain it matches the unit rating plate located inside control box cover and that constant voltage can be maintained to ...

Страница 4: ...d wire If thermostat is located more than 100 ft from unit as measured along the control voltage wires use No 16 AWG wire to avoid excessive voltage drop 3 All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power Note Use of available 24 volt accessories may exceed the minimum power requir...

Страница 5: ... with tubing When necessary use hanger straps which are 1 in wide and conform to shape of tubing insulation Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation Condensing units are available with pre charged sweat type copper connecting fittings Units are factory charged for 15 of line set tubing Adjust charge 0 65 oz per foot of variation from chart...

Страница 6: ...icensed Contractor for filter replacement schedules and instructions WARNING SERIOUS PERSONAL INJURY OR DEATH MAY RESULT IF WATER SPRAY IS DIRECTED TOWARD LIVE ELECTRICAL CONNECTIONS OR POWER SOURCES Model 5 SUB COOLING CHARGING Coils with TXVs should be charged 10 12 degrees or one degree of sub cooling For proper sub cooling readings a standard high side gauge is required for pressure readings U...

Страница 7: ... Hz 2 230 Volts 1 Phase 50 Hz 3 208 230 Volts 3 Phase 60 Hz 4 460 Volts 3 Phase 60 Hz 5 230 Volts 3 Phase 50 Hz 6 380 Volts 3 Phase 50 Hz C Air Conditoner CH Heat Pump A F Fedders Poduct Type Brand V Sweat Fitting Type D R 22 Refrigerant Z R 410A Refrigerant Variations Electrical Designation B 21 1 2 W x 21 1 2 D x H C 29 1 2 W x 29 1 2 D x H Chassis Size Nominal Capacity Series CONDENSING UNIT NO...

Страница 8: ...pment nor for refrigerant used For warranty purposes the purchase date is established by a proof of purchase If a proof of purchase can not be verified then warranty period will be measured from the date of manufacture plus 6 months Cost of repair or replacement of consumable parts is not covered under the terms of this warranty Replacement parts are warranted only for the balance of the original ...

Отзывы: