Repair Kits  

1

2

"- 2" (15-50mm)

Ordering COde 

MOdeL 

 

Size

 

 

in 

mm

Check Kits

0710590 

RK 767FR CK 

1

2

3

4

 

15, 20

0710591 

RK 767FR CK 

25

0710592 

RK 767FR CK 

1

1

4

 - 2 

32 - 50

Kits consist of:

 Check disc assembly (disc & disc holder). Bonnet 0-ring and Check Spring.

Vent Float Kits

0710593 

RK 767FR V 

1

2

3

4

 

15, 20

0710594 

RK 767FR V 

25

0710595 

RK 767FR V 

1

1

4

 - 2 

32 - 50

Kits consist of:

 Float vent disc assembly (vent float, seal & spring) and Bonnet 0-ring.

Bonnet Assembly Kits 

0710596 

RK 767FR B 

1

2

3

4

 

15, 20

0710597 

RK 767FR B 

25

0710598 

RK 767FR B 

1

1

4

 - 2 

32 - 50

Kits consist of:

 Bonnet, Bonnet O-ring, Vent spring, hood & hood screws.

Rubber Parts Kits 

 

 

0710599 

RK 767FR RT 

1

2

3

4

 

15, 20

0710600 

RK 767FR RT 

25

0710601 

RK 767FR RT 

1

1

4

 - 2 

32 -50

Kits consist of:

 Vent disc, Check disc and Bonnet O-ring.

Seat Kits

0710602 

RK 767FR S 

1

2

3

4

 

15, 20

0710603 

RK 767FR S 

25

0710604 

RK 767FR S 

1

1

4

 - 2 

32 - 50

Kits consists of:

 Seat, Seat O-ring and Bonnet O-ring.

FEBCO reserves the right to change or modify product design, construc-

tion, specifications, or materials without prior notice and without incurring 

any obligation to make such changes and modifications on FEBCO prod-

ucts previously or subsequently sold.

Freeze Protection Guidelines

Purging of a PVB Assembly with Pressurized Air

1.  Close main shutoff valve.
2.   Open upstream drain, test cocks and isolation ball valves  

to depressurize line.

3.  Purge with pressurized line.
4.   Leave test cocks and isolation ball valve handles in 45°  

angle to drain ball valves and prevent casting damage.

Outlet drain 

Valve

Main Shutoff Valve

Upstream (inlet) drain

Flow

Valve Pit

12" Minimum Clearance 

Above the Highlest Point of 

downstream Piping

Sprinkler System 

Piping

zone Control

Servicing the Vacuum Breakers

Internal parts can be removed, repaired or inspected without removing the 

valve from the piping.

Disassembly

1.  Shut off the supply pressure and drain the valve.
2.  Remove the two hood screws and the hood.
3.   Place a wrench on the parallel flats of bonnet and stem assembly.  

Turn counter clockwise and remove.

4.  Remove the vent assembly.
5.   Press down on the spring retainer and disengage it from the  

retaining lugs. Then turn 90° and remove.

6.   Remove the spring retainer and spring. Note that the large  

diameter of the spring is down on the guide assembly.

7.  Remove the check disc holder and guide assembly.
8.  Disassemble the check disc holder assembly.

Reassembly

Reassemble in the reverse order utilizing the new parts from the repair kit.

Installation Instructions

Using FPHB-1 Hydrant

Note:

  PVB's must be installed a minimum of 12" (300mm) above  

the highest point of water in the sprinkler system.

Water Supply

FPHB-1 with FeBCO 

767Fr Series

To Sprinklers

drain Port or Blow down

767FR/LF767FR

1"-2" 

(25-50mm)

767FR/LF767FR

1

/

2

", 

3

/

4

"

(15, 20mm)

USA:  4381 N. Brawley • Ste. 102 • Fresno, CA • 93722 • Tel. (559) 441-5300 • Fax: (559) 441-5301 • www.FEBCOonline.com

Canada:  5435 North Service Rd. • Burlington, ONT.  • L7L 5H7 • Tel. (905) 332-4090 • Fax: (905) 332-7068 •  www.FEBCOonline.ca

RP/IS-F-767FR  1006 

EDP# 1915947 

© 2010 FEBCO

A Watts Water Technologies Company