8

SW6 Poles 6 - 8

 

These switches are not used. Leave them in 

the 

OFF

 position.

Note

Eco

VFC may operate in an unpredictable manner if 

any of the switches, SW6 Poles 6-8, are in the ON 

position. 

 11.  Replace the cover of the 

Eco

VFC.

 12.  Insert a 0 - 7 bar (0 -100 psi) pressure gauge into 

the 1/4” line test port of the submerged pump 

(or other pressurized test location in the piping 

system). Turn power on to the 

Eco

VFC at the 

load center, turn on the submerged pump at the 

dispenser and inspect the line test port for leaks. 

If there are any leaks, immediately turn off the 

submerged pump at the dispenser and the load 

center and repair the leaks.

 13.  Begin purging the air from the piping system by 

activating a dispenser handle and pumping product 

into an approved container. Verify that while the 

pump is on but no product is being dispensed, 

the pressure reading on the gauge is equal to the 

related pressure from Table 4 in Step 22,  

+0.3 / -0.5  bar  (+5 / -7  psi).

Note: 

If pressure in the piping system is much lower than 

selected, it is possible that the polarity of the motor 

power wires is not correct, causing the motor to 

run in reverse rotation. Turn off the pump at the 

power supply, (wait one minute after LED display 

blanks before opening the cover) and change the 

connection of any two wires at the pump or at the 

Eco

VFC motor terminals. Turn the pump back on 

and read the pressure gauge again. The electrical 

connection, which gives the higher reading on the 

pressure gauge, is the correct one.

 

14.  Complete purging the remaining air from the piping 

system and dispensers. If using Master-Slave or 

Master-Slave/Alternating Circuit, continue with 

next section. If not, go to “

Eco

VFC Site Set-Up” 

section.

Master-Slave Control Connections

Note: 

For Master / Slave and Alternating configurations, 

the 

Eco

VFC can only be paired with other 

Eco

VFC’s. Because of enhanced communication 

protocols, the 

Eco

VFC is not capable of 

communication with the IST-VFC unless SW6 Pole 

3 (IST-VFC Compatibility Mode) is switched ON. 

IST-VFC Compatibility Mode is available in rev 1.18 

software or higher EcoVFCs. 

To avoid the risk of potentially lethal 

electrical shock, explosion or fire, 

always tag and lock circuit breakers 

in the off position before removing the 

cover of the EcoVFC.

After disconnecting power to the 

EcoVFC, wait one minute after LED 

display blanks before opening the 

cover for servicing. Voltage stored 

in the capacitor bank of the EcoVFC 

presents a risk of potentially lethal 

electrical shock even after power is 

disconnected. 

 15.  When two IST pumps or STP units with VS4 

or VS2 suffix are installed to be run in parallel 

(discharging into the same line) three different 

modes of operation are possible, as follows:

Master – Slave 

When a hook voltage is present at the Master it will turn 

on. When demand for product increases (more nozzles 

open) the Master will call the Slave controller to turn on. 

This will maintain the product flow rate in high demand 

situations. In this configuration, the slave unit(s) will run 

only when requested to do so by the master unit.

Alternating Circuit 

The controllers will rotate being the one to turn on as the 

hook voltage turns on and off. Only one controller is on 

at a time in this configuration. Not available in IST-VFC 

Compatibility Mode.

Master – Slave and Alternating Circuit 

A combination of the above two configurations. The first 

controller to turn on rotates and when the demand for 

product increases, additional controllers will be called on to 

assist.
See Figure 5 wiring diagram for the RS485 connections.

 16. 

For Master – Slave Configuration

 (not applicable 

to IST-VFC Mode)

Set 

Master

 

SW3 Pole 3

 to 

ON

SW3 Pole 8 

to 

OFF

,

 

and

 

verify that on 

SW2

 all switches are 

OFF

Set 

Slave(s)

, verify that 

SW3 Pole 3 

and

 SW3 

Pole 8 

are set 

OFF

 (factory default). Set 

SW2

 

switches of Slave(s) per 

Table 1

.

Warning

Warning

Содержание EcoVFC

Страница 1: ...on and Owner s Manual Eco VARIABLE FREQUENCY CONTROLLER Franklin Fueling Systems 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 800 225 9787 Fax 1 608 838 6433 www franklinfueling com 2016 FFS...

Страница 2: ...ult in serious fire or explosion Before entering a containment sump check for the presence of hydrocarbon vapors If hydrocarbon vapors are at unsafe levels ventilate the sump with fresh air re check t...

Страница 3: ...compatible with competitive makes of variable speed models The EcoVFC is compatible with the IST VFC for communication in Master Slave configurations only if the EcoVFC has software revision 1 18 or...

Страница 4: ...nd hold button and the Pump status display will show the last 3 fault conditions the EcoVFC encountered Reset Button Resets controller of any fault condition Communications LED Used in Master Slave ty...

Страница 5: ...08mm2 14 AWG 75 meters 250 feet 4 Replace the cover of the pump junction box and securely tighten in place The compression seal is not a replacement for the vapor explosion seals required by the NEC...

Страница 6: ...phase power only If 200 250V 50 Hz Single Phase power supply is only available the EcoVFC must be replaced with the FE Petro MagVFC which will olny be capable of driving a PMA VS2 in this application...

Страница 7: ...le EcoVFC controllers working together See Alternating Circuit Control section for details default is OFF Note Not functional in IST VFC Compatibility Mode set with SW2 Pole 5 per Table 1A SW6 Pole 1...

Страница 8: ...ther EcoVFC s Because of enhanced communication protocols the EcoVFC is not capable of communication with the IST VFC unless SW6 Pole 3 IST VFC Compatibility Mode is switched ON IST VFC Compatibility...

Страница 9: ...laves s SW3 pole 3 OFF and set SW2 switches per Table 1A Line leak detection performance can be affected when using multiple EcoVFCs FE Petro does not recommend using the Alternating Circuit feature i...

Страница 10: ...set connect the signal from the dispenser hook to the terminals of the Master EcoVFC only The Master controller will energize the Slave s when needed without a signal from the dispenser 19 When all co...

Страница 11: ...le 2 Summary of Master Slave 30 minute Alternating Setup Software version 1 24 or higher Below is a table summarizing the SW3 and SW6 settings to enable the EcoVFC to alternate active pumps every 30 m...

Страница 12: ...ch locations Example For a Master controller with a 20 000 gallon tank when set to address 20 the pump will run for 30 minutes For a Slave controller with a 12 000 gallon tank when set to address 12 t...

Страница 13: ...SW3 3 O N 1 2 6 4 5 7 SW6 O N 1 6 2 4 3 5 8 7 SW3 6 SW6 O N 2 1 3 4 5 7 8 6 O N 2 1 3 4 5 7 8 SW2 SW6 position 5 ON SW6 position 4 ON SW3 position 8 ON Set according to Table 3 Each controller address...

Страница 14: ...sition Pressure 0 1 7 bar 24 psi 1 1 8 bar 26 psi 2 1 9 bar 28 psi 3 2 1 bar 30 psi 4 2 2 bar 32 psi 5 2 3 bar 34 psi 6 2 5 bar 36 psi 7 2 8 bar 38 psi 8 2 9 bar 40 psi 9 42 psi Table 4 SW1 Settings T...

Страница 15: ...the revision xx yy Note If the display stops on yy there may be an issue of low incoming voltage or loose input power connections Immediately after the EcoVFC has been reset or turned ON Pr NN Pressur...

Страница 16: ...Pole 6 ON 4hp setting may cause this false indication when operating in SW1 positions 0 6 4 Check fuel level in storage tank if product level is low schedule fuel delivery when delivery is complete a...

Страница 17: ...or submersible wiring in the beginning of this manual Code Condition Potential Causes Proposed Action Er Extended Run Continuous hook signal applied for greater than 60 minutes without change in pumpi...

Страница 18: ...results e g Black to red 2 ohms Readings between any of the three motor control wires and ground should be an open circuit If readings in this step are incorrect go to Step 7 if readings are correct c...

Страница 19: ...lacement in 3 flashes section if readings are correct there is problem with the wiring between the EcoVFC and this point 7 Remove the junction box cover and do conductivity test on wires from junction...

Страница 20: ...llasted in water 8 Remove four 5 16 cap screws that connect the PMA with Allen wrench and remove the PMA from the motor discharge head Note Prior to mounting a new PMA check lead assembly wires inside...

Страница 21: ...ly TO MOTOR TO LINE GND ORG RED BLK GND L1 L2 L3 N 1 9 0 Switches located on user interface panel SW1 3 4 2 SW2 5 6 7 8 2 1 5 4 3 SW3 3 2 1 6 5 4 8 7 SW6 1 4 3 2 7 6 5 8 Switch Handle Dispenser RETURN...

Страница 22: ...e only TO MOTOR TO LINE L3 N L2 L1 GND BLK RED ORG GND 5 SW1 0 3 2 7 4 6 1 9 8 O N SW2 1 2 3 5 4 0 1 2 3 4 5 6 7 8 9 SW3 SW2 1 J23 1 2 3 4 TO LINE USER INTERFACE PANEL 8 O N SW3 3 2 1 5 4 7 6 O N SW6...

Страница 23: ...ion instructions for further details Wiring must conform to all federal state and local codes Control panels are for non hazardous indoor use only TO MOTOR TO LINE L3 L2 L1 GND BLK RED ORG GND 5 SW1 0...

Страница 24: ...uctions for further details Wiring must conform to all federal state and local codes Control panels are for non hazardous indoor use only TO MOTOR TO LINE L3 L2 L1 GND BLK RED ORG GND 5 SW1 0 3 2 7 4...

Страница 25: ...de 2 1 1 2 3 4 5 6 7 5 4 3 SW3 O N 1 9 0 SW1 3 4 2 SW2 5 6 7 8 2 1 5 4 3 SW3 3 2 1 6 5 4 8 7 SW6 1 4 3 2 7 6 5 8 O N O N O N On IST VFC Mode Off 2HP Motor Not used Not used in IST VFC mode Not used in...

Страница 26: ...2016FFS 228001102 Rev 10...