background image

Heat recovery unit with cooling circuit - 

RCF

 -

0208-6180549-rev. 02

18

GB

Controls manual 

• relay ON in cooling mode
• relay ON in heating mode

Pa H39 Offset AI1 
Pa H40 Offset AI2 
Pa H41 Offset AI3 

This  parameter  can  be  used  to  compensate 
for  the  error  that  may  occur  between  the 
temperature  (or  pressure)  reading  and  the 
actual value.

Pa H42 Offset AI4 

These parameters can be used to compensa-
te for the error that may occur between the 
temperature reading and the actual tempe-
rature.

Pa H43 Mains frequency

• 0= Mains frequency: 50 Hz
• 1= Mains frequency: 60 Hz

Pa H44 Family serial address
Pa H45 Device serial address

Used  to  select  the  serial  address.  Both  nor-
mally set to 0.

Pa H46 User password

Can be used to enter the password required 
to access second level parameters. 

Pa H47 Copy card write password

The password that must be entered to copy 
parameters to the copy card.

Pa H48 Number of compressors per circuit

• 1= 1 Compressor
• 2= 2 Compressors (or 2 steps)

Pa  H49  Enable  pressure/temperature  based 
operating

•  0=parameters  Pa  H07=0  (probe  AI3 
absent), Pa F01 = 3 (operation in response to 
request from compressor)  are forced.  
•  1=temperature-based  operating,  parame-
ters  Pa  H07,  Pa  F01  are  forced  to:  Pa  H07= 
1 (AI3 temperature probe), Pa F01= 3 (opera-
ting in response to request from compressor). 
• 2=pressure-based operating, parameters Pa 
H07,  Pa  F01  are  forced  to:  Pa  H07=  2  (AI3 
probe operation based on pressure), F01= 0 
(proportional operating). 
• = 3 no constraints are set on parameters

Pa H50 Compressor start-up sequence

0=compressors start according to operating 
hours (balancing of operating hours)
1=compressor 1 is started first and then com-
pressor (or capacity step) 2 (fixed sequence).

Pa H51 Compressor 2 or capacity step pola-
rity

•  0=  relay  ON  if  compressor  2/capacity  step 
ON
•  1=  relay  ON  if  compressor  2/capacity  step 
OFF

Pa H52 Selection of degrees °C or °F

• 0= degrees °C
• 1=  degrees °F

Pa  H53  Display  of  air/air  machine  SET 
POINT

For  a  simpler  user  interface  in  air-air  ver-
sions, by setting parameter Pa H53 = 1 the 
set point for the mode selected is displayed 
normally

Pa H54 Customer code 1

This is a number ranging from 0 to 999 that 
the user can assign for internal use.

Pa H55 Customer code 2

This is a number ranging from 0 to 999 that 
the user can assign for internal use.

Pa H56 Polarity of alarm relay

• 0 = output is active (contact closed) when 
there is an alarm
•  1  =  the  contact  is  open  with  the  same 
conditions

Pa H57 Enable alarm relay in off position

• 0 = inactive alarm output in OFF or stand-
by mode or remote off
•  1  =  active  alarm  output  in  OFF  or  stand-
by mode or remote off

Pa H58 Enables change-over from keyboard 
in hysteresis of analogue change-over

•  0  =  change-over  is  not  possible  in  hyste-
resis 
• 1 = change-over is possible in hysteresis 

Alarm parameters

Pa  A01  Low  pressure  pressure  switch  by-
pass time.

Determines  the  delay  between  starting  up 
the compressor and starting up the low pres-
sure digital alarm diagnostics. It is expressed 
in seconds

Pa A02 Number of low pressure events per 
hour 

Used  to  set  the  number  of  low  pressure 
digital  alarm  events  per  hour.  If  exceeded, 
the system will switch from automatic reset 
to manual reset.

Pa  A03  Bypass  time  for  worn  filters  activa-
ted by evaporator fan

Used to set a delay in triggering off the worn 
filter digital alarm activated by the evapora-
tor fan. It is expressed in seconds

Pa  A04  Duration  of  active  worn  filters 
input

Used  to  set  a  period  of  time  during  which 
the  worn  filter  digital  input  must  remain 
active. When  this  period  has  elapsed,  the 
alarm is generated. The timer starts after the 
worn filters by-pass time. It is expressed in 
seconds. 

Pa  A05  Duration  of  inactive  worn  filters 

input

 

Used  to  set  a  period  of  time  during  which 
the  worn  filter  digital  input  must  remain 
inactive.  When  this  period  has  elapsed, 
the  alarm  is  deactivated.  It  is  expressed  in 
seconds. 

Pa  A06  Number  of  worn  filter  events  per 
hour

Used to set the number of worn filter digi-
tal  alarm  events  per  hour.  If  the  number 
is  exceeded,  the  alarm  is  switched  from 
automatic to manual reset. If the alarm is in 
manual reset mode, the fan is shut down.

Pa  A07  By-pass  time  for  compressor  ther-
mal switch activated by compressor

Used to set a delay for triggering the com-
pressor  thermal  switch  alarm  activated  by 
the compressor. It is expressed in seconds

Pa  A08  Number  of  compressor  1  and  2 
thermal switch alarm events per hour

Used to set the number of compressor ther-
mal  switch  alarm  events  per  hour.  If  the 
number is exceeded, the alarm is switched 
from automatic to manual reset.

Pa A09 Number of condensing fan thermal 
switch events per hour

Used  to  set  the  number  of  fan  thermal 
switch alarm events per hour. If the number 
is  exceeded,  the  alarm  is  switched  from 
automatic to manual reset.

Pa A10 Anti-freeze alarm by-pass time 

Determines  the  delay  between  turning  on 
the  machine  and  activation  of  the  anti-
freeze  alarm;  it  is  enabled  only  in  heating 
mode. It is expressed in minutes. 

Pa A11 Anti-freeze alarm set point 

Used  to  set  the  temperature  below  which 
the anti-freeze alarm is triggered.

Pa A12 Anti-freeze alarm differential

Used  to  set  the  anti-freeze  alarm  differen-
tial.

Pa A13 Number of anti-freeze alarm events 
per hour 

Used to set the number of anti-freeze alarm 
events per hour. If the number is exceeded, 
the  alarm  is  switched  from  automatic  to 
manual reset.

Pa  A14  Enable  minimum  alarm  during 
defrosting

Enables  the  minimum  alarm  during  defro-
sting.  If  0  the  minimum  alarm  is  disabled 
during defrosting. 

Pa A15 Over-temperature set point

Sets the temperature value AI1. If exceeded, 
the over-temperature alarm E46 is triggered.

Pa A16 Over-temperature ON duration

Determines  the  duration  of  the  condition 
AI1>A25.  If  exceeded,  alarm  E46  is  trigge-
red.

Содержание RCF Series

Страница 1: ...0208 6180549 rev 02 FAST S p A CONTROLS MANUAL GB HEAT RECOVERY UNITS WITH COOLING CIRCUIT RCF SERIES...

Страница 2: ......

Страница 3: ...ristics 6 Installation of remote panel 6 Wiring of remote panel 7 User interface 7 Men levels 9 Components 10 Functions 11 Diagnostics 13 Parameters setting 16 Parameters 17 Technical characteristics...

Страница 4: ...oys Seamless round copper tubes for air conditioning and refrigeration 2 designed manufactured and commercialized in compliance with the following EEC Directive PED safety 97 23 CE Machinery safety 98...

Страница 5: ...ly limited through the use of technical protection means and measures G E N E R A L H A Z A R D S I G N A L Carefully adhere to all the indications n e x t t o t h e i c o n Failure to comply with the...

Страница 6: ...assword inside the electrical panel remote panel max distance 150m to be connected directly to the unit wiring cable not included Troubleshooting The controls check and mark the fol lowing possible fa...

Страница 7: ...onfigured as digi tal inputs with parameters Pa H05 Pa H06 Pa H08 8 digital inputs are therefore available Wiring of remote panel Important Never connect the keyboard when the instrument is on Avoid s...

Страница 8: ...r more than 2 seconds you move one level up If the last level of a menu is displayed press the button and release it within two seconds to go up one level In men operating mode it shows the pre vious...

Страница 9: ...D d I s r e t e m a r a P r A P d r o w s s a P s s P e u l a V g n i l o o C t e S e u l a V g n i t a e H t e S e u l a V t u p n I e u g o l a n A s u t a t S t u p n I l a t i g i D x e d n I r e...

Страница 10: ...and start up of the same com pressor compressor on off safety time con trolled by parameter Pa C01 This parameter also applies to when the device is started up ON OFF Pa C01 Pa C02 Time COMPR Pa C01...

Страница 11: ...cooling and freeheating are used to cool or heat the internal environment using outdoor air The external air enters the environment through a damper that mixes it with the recirculated air from insi d...

Страница 12: ...e compressor is ON the control starts the defrost coun tdown 1 min countdown When 1 min pas sed the control device starts the defrosting process At this point Pad06 compressor valve time delay 30 sec...

Страница 13: ...rms are sampled every 225 seconds Example if the number of events is set to 3 the duration of the alarm must last between 2 225 seconds and 3 225 seconds for the alarm to be switched from automatic to...

Страница 14: ...OFF ON Automatically reset unless alarm events per hour reaches the value of parameter Pa A08 after which it is manually reset Not active when Pa A07 time is counted after a compressor is turned on E0...

Страница 15: ...d as worn filters see digital inputs remains inactive for a period of time equal to Pa A05 Not active when the Pa A03 time is counted after fan is turned on OFF OFF3 Reset is carried out automatically...

Страница 16: ...e contact is open The ID4 is configured as active when the contact is closed The ID5 input is configured as active when the contact is closed Relay 1 is connected to the compressor Relay 2 is connecte...

Страница 17: ...ermal switch 2 Worn filters 3 Remote Heating Cooling 4 Remote ON OFF 5 Thermal switch compressor 2 6 Request for second compressor capa city step 7 damper opening Pa H22 Configuration of output NO2 0...

Страница 18: ...a A01 Low pressure pressure switch by pass time Determines the delay between starting up the compressor and starting up the low pres sure digital alarm diagnostics It is expressed in seconds Pa A02 Nu...

Страница 19: ...eating mode 3 continuous operating of fan in cooling mode on request in heating mode 4 continuous operating of fan in heating mode on request in cooling mode Pa P02 Delay between fan ON and com presso...

Страница 20: ...if Pa H49 1 la temperatura al di sotto la quale viene avviato il ciclo di sbrinamento Pa d09 Temperature at which defrost ends if Pa H49 1 Temperature above which the defrost cycle is ended Pa d10 En...

Страница 21: ...Enables dynamic set point 1 0 1 Flag 0 Pa H32 Dynamic set point off set in cooling mode 50 12 7 12 7 C 1 0 Pa H33 Dynamic set point off set in heating mode 0 12 7 12 7 C 1 0 Pa H34 Outdoor temperatur...

Страница 22: ...Pa C02 ON ON safety time 36 0 255 Seconds 10 20 Pa C03 Temperature control hysteresis in cooling mode 15 0 25 5 C 2 Pa C04 Temperature control hysteresis in heating mode 15 0 25 5 C 1 5 Pa C05 Regula...

Страница 23: ...eed in heating mode 100 0 100 80 Pa F17 Minimum fan speed temperature pressure set point in heating mode 100 500 800 C 10 kPa 10 180 Pa F18 Proportional band in heating mode 100 0 255 C 10 kPa 10 40 P...

Страница 24: ...2 AWG 16 28 1 5 way p2 5 5 way connector with remote control and copy card programming AWG 24 30 1 2 3 way connector remote keyboard AWG 22 30 Display and LEDs 3 digits sign 5 red LEDs Buttons 2 butt...

Страница 25: ...ntegrated In terms of automatic operating featu res as a type 1 action control device with reference to manufacturing tolerances and drifts As a class 2 device in relation to protec tion against elect...

Страница 26: ...NOTES...

Страница 27: ...ht to introduce at any time whatever modifications deemed necessary to the improvement of the product FAST S p A TRATTAMENTO DELL ARIA 35044 Montagnana PD Italy Via Luppia Alberi 170 Tel 39 0429 80631...

Отзывы: