Heat recovery unit with cooling circuit -
RCF
-
0208-6180549-rev. 02
10
GB
Controls manual
Components
Compressor
The compressor is controlled by the relays of
the control panel on board of the unit.
Compressors are turned on and off according
to the temperatures detected and the tempe-
rature control functions that have been set.
Compressor configuration
The compressor must be connected to
output NO1.
Compressor timing
Compressor start-up and shut-down opera-
tions must comply with the safety times set
by the user using the parameters described
below. A safety period must elapse between
shut-down and start-up of the same com-
pressor (compressor on...off safety time) con-
trolled by parameter Pa C01;
This parameter also applies to when the
device is started up.
ON
OFF
Pa C01
Pa C02
Time
COMPR
Pa C01: OFF-ON safety time
Pa C02: ON-ON safety time
A safety period must elapse between one
start-up and the next (compressor on...on
safety time) controlled by parameter Pa C02.
Reversing valve
The reversing valve refers to the “heat pump”
operating mode. The reversing valve is off if
the instrument is OFF and on standby.
Fans
The fans are cabled on a single relay output
NO2 (see wiring diagrams). The fans are confi-
gured to operate in continous mode.
Electric heating coil (MBX) and Water heating
coil (MBC)
Connect the electric heating coil or the water
heating coil to the NO4 relay output (see
wiring diagrams).