21
LW-401 Operation, Installation, and Maintenance Manual
LW-401
Test Level 1—One Person System Test
Important
Inform the person in charge of the LW-401
fire alarm system that a One Person Test is
to be performed and that part or all of the
fire detection system will be disabled. It is
also advisable (or may be required) to notify
the fire department of the test.
The One Person Test feature allows the
installer to test the system in the following
two ways.
• When a device is alarmed, the system
notification appliances sound and the
appropriate IDC alarm LED lights for 2
seconds.
• When a device is alarmed, the sounding
of the appliances is eliminated—only
the system display annunciates.
1. Press the Reset key once to select Test
Level 1.
2. Press the Silence key once or twice to
select the type of test you wish to
perform.
Example: 1-1 enables test with
notification appliances;
1-2 enables test without
appliances.
Test Level 2 - Test System Relays
1. Press the Reset key twice to select Test
Level 2.
2. Press the Silence key to select one of
the four relays to be tested as indicated
in the following table:
Example: 2-1 tests the System Alarm
Relay.
Level
Feature
2-1
Test System Alarm Relay
2-2
Test NAC 1 Relay
2-3
Test System Trouble Relay
2-4
Test NAC 2 Relay
3. Press the Drill key to change the state of
the selected relay. Please note that
testing the NAC relays will activate the
appliances on that circuit.
4. Press the ACK key when done.
Test Level 3 - Test Optional Outputs
1. Press the Reset Key 3 times to select
Test Level 3.
2. Press the Silence Key to select one of
the eight outputs to be tested as
indicated in the following table:
Example: 3-1 tests Relay Output 1.
Level
Feature
3-1
Test Output 1
3-2
Test Output 2
3-3
Test Output 3
3-4
Test Output 4
3-5
Test Output 5
3-6
Test Output 6
3-7
Test Output 7
3-8
Test Output 8
The Outputs on each card are organized
according to the following table:
LWZE-4A
LWZR-8
Output 1 = Relay 1
Relay 1
Output 2 = Relay 2
Relay 2
Output 3 = Relay 3
Relay 3
Output 4 = Relay 4
Relay 4
Output 5 = OC 1
Relay 5
Output 6 = OC 2
Relay 6
Output 7 = OC 3
Relay 7
Output 8 = OC 4
Relay 8
Note: OC = Open Collector