22
Operation, Installation, and Maintenance Manual
LW-401
3. Press the Drill key to change the state of
the selected output.
4. Press the ACK key when done.
Test Level 4 - Last Event Record
1. Press the Reset key 4 times to select
Test Level 4.
2. Press the Silence key to select the event
to be reviewed per the following table:
Example: 4-1 reviews the last zone in
alarm.
Level
Feature
4-1
Review Last Alarm
4-2
Review Last Zone Trouble
4-3
Review Last Verification
4-4
Review Last Supervisory
3. The Zone Alarm LED for the last zone in
alarm will be on. Similarly, the Zone
Trouble LED will be on for the last zones
in supervisory and trouble conditions.
4. Press the ACK key when done.
Test Level 5 - Lamp Test
1. Press the Reset key 5 times to select
Test Level 5.
2. Press the Silence key to select the
lamps to be tested as indicated in the
following table:
Example: 5-1 tests Local Display.
Level
Feature
5-1
Test the Local Display
5-2
Test Remote Annunciators
3. Press and hold the Drill key to turn
the lamps on.
4. Press the ACK key when done.
Test Level 6 - Clear the Last Event
Record
1. Press the Reset key 6 times to select
Test Level 6.
2. Press the Silence key to select this
function. There is no other function to be
selected.
3. Press the Drill key to clear the event
record.
4. Press the ACK key when done.