background image

4

Avoid to make probe connections close to distribution 

cables with high current loads.

Connect  the  different  devices  according  to  shown 

diagrams.

Make sure that coupling connections are clean and 

not oxidised.

Connect the control unit Fastons to the proper cou-

plings on the terminal base, pressing them down to 

full bedding.

Then tighten the fastening bolt.

OPERATION TYPE SELECT SWITCH

Switch  G  (pg 6) shall be used for immediate selec-

tion  between  proportional-time  control  of  motor-op-

erated mixing valves (wiring diagrams 1 and 2) and 

burner ON/OFF control (wiring diagram 3).

CIRCULATION PUMP CONTROL

EV02F control unit is preset for automatic circulation 

pump control.

If connections are carried out according to shown dia-

grams, the circulation pump will be working during the 

following  operating  modes:  AUTOMATIC  1,  always 

ON, always economy; and it will be off when in OFF 

mode. It will also be off (with the exception of the an-

tifreeze protection) in the antifreeze operating mode 

and at night in the AUTOMATIC 2 operating mode.

To make the most of the remaining heat accumulated 

during  the  daytime  mode,  the  pump  will  shutdown 

(with  60-minute  adjustable  delay)  after  turning  the 

system off.

SERVO CONTROL OPERATION TEST

Turn control unit selector   H  (pg 6) to ON and OFF 

positions, check for proper valve movement and com-

pare it with plate data.

When the selector is at OFF, the valve control lever 

pointer shall move to COLD; when the selector is at 

ON, the lever pointer shall move to HOT.

Otherwise exchange servo control connections 2 - 3 

or connections 6 - 8 on the control unit base.

IN  THE  EVENT  OF  SYSTEM  UNSUCCESSFUL 

OPERATION CHECK THE FOLLOWING:

Supply voltage, that shall be: 230V 50Hz.

Probe  circuit,  by  means  of  the  tester  provided  for 

measuring the resistance value.

Connections  and  settings  of  burner  thermostats, 

safety thermostats, etc.

Turn  the  daytime  ambient  temperature  regulation 

knob fully clockwise and counterclockwise for several 

consecutive times: if the two pilot lamps turn on and 

Содержание EV02F

Страница 1: ...e set programming determines the delivery water temperature value to be sent to the system to keep the set ambient temperature constant The control unit is fitted with quartz clock for daily programmi...

Страница 2: ...in insulat ing material with transparent cover Protection IP40 installation wall flush or rear panel mounting TECHNICAL DATA Control unit consumption 5VA Supply voltage 230V 10 50Hz Compliance with CE...

Страница 3: ...re similar to those tabulated below Resistance values as a function of temperature EC11 OUTSIDE PROBE TEMPERATURE RESISTANCE C DELIVERY PROBES EC12 EC13 TEMPERATURE RESISTANCE C 40 8629 35 7853 30 711...

Страница 4: ...ff with the exception of the an tifreeze protection in the antifreeze operating mode and at night in the AUTOMATIC 2 operating mode To make the most of the remaining heat accumulated during the daytim...

Страница 5: ...ervo controls powered with 230 V 50 Hz Circulation pump supply Servo control Supply voltage Common Open Close Delivery probe EC12 EC13 Outside probe EC11 230 V 50 Hz Circulation pump supply Circulatio...

Страница 6: ...mfort Automatic 2 nightime antifreeze daytime comfort Screw for mechanical connection between electronic panel and terminal base Quartz clock for daily programming FRONT CONTROL PANEL L H G F E A A B...

Страница 7: ...the purpose and with heat conducting paste interposed in order to guarantee proper heat conduction The immersion probe EC13 must be fitted in the pip ing with the sheath filled with mineral oil or si...

Страница 8: ...8 EXAMPLES OF HYDRAULIC CONNECTIONS FOR MIXING VALVES 3 WAY SECTOR POWER OPERATED MIXING VALVE 3 WAY ROTOR POWER OPERATED MIXING VALVE 4 WAY ROTOR POWER OPERATED MIXING VALVE...

Страница 9: ...turn slightly knob F counterclockwise if it is higher turn knob F clockwise Check again temperature after 24 hours If required keep on adjusting knob F position like indicated in the table below unti...

Страница 10: ...NAL INSTRUCTIONS WINTER MODE DUTY Open the circulation pump gate valves Start the pump If the system is equipped with mixing valve operate the valve manually to remove any sediment deposi ted inside t...

Страница 11: ...etely then turn the system off b stop water circulation pump c close circulation pump gate valves to prevent hot water infiltration into radiator circuits during the sum mer since mixing valves do not...

Отзывы: