CH130RFR

RADIO FREQUENCY AMBIENT THERMOSTAT 
FOR FAN-COILS 

Содержание CH130RFR

Страница 1: ...CH130RFR RADIO FREQUENCY AMBIENT THERMOSTAT FOR FAN COILS ...

Страница 2: ...ng 14 Operation 14 Operation check 15 Technical features of the actuator 16 TABLE OF CONTENTS Introduction 3 Controls and signals 4 Controls 4 Signals 4 User s manual 5 Summer Winter selection 5 Operating modes 6 Comfort operating mode 6 Economy operating mode 6 OFF function OFF 7 Fan speed selection 7 Maintenance 7 Installation 7 Fastening the socket 8 Electric connections 8 Fastening the thermos...

Страница 3: ...rough radio frequencies The CH130RF is powered by two AA size bat teries 1 5 V It is able to drive two valves and control a 3 speed fan coil motor in manual mode The thermostat measures the ambient tem perature either through an internal probe or an external sensor It keeps the set point by act ing on the ventilation speed The wide display shows the measured tem perature the fan speed the program ...

Страница 4: ...n winter operation 9 Low battery charge Controls and signals Controls 5 1 2 3 4 1 Fan speed increase button 2 Fan speed decrease button 3 Selected program temperature value increase button 4 Selected program temperature value decrease button 5 Thermostat reset button Button combinations press simultan 1 2 Summer Winter switch 3 4 Comfort Economy switch 2 4 Celsius Fahreneit switch ...

Страница 5: ...hat the range will decrease if obstacles are found between the CH130RF and the CH172DRF To start the thermostat after the same has been installed proceed as follows 1 Select the Summer Winter operation 2 Select the operating mode 3 Select the fan speed Summer Winter selection To switch from the Winter operation i e heat ing system to the Summer operation i e cooling system and vice versa press the...

Страница 6: ...nged from 2 C to 40 C by 0 1 C steps Operating modes The CH130RF thermostat features three dif ferent manual operating modes Comfort Economy and the OFF function OFF Comfort operating mode With the Comfort operating mode the ther mostat regulates the heating or cooling sys tem operation in order to always keep the same comfort temperature set To switch from Economy to Comfort press buttons 3 and 4...

Страница 7: ...s minimum medium maximum by pressing buttons 1 and 2 Maintenance The thermostat should be cleaned by using a soft cotton cloth No detergent should be used Installation The thermostat installation involves carrying out the following operations Fastening the socket Making the electric connections Fastening the thermostat onto the socket Inserting and replacing the batteries Configuring the thermosta...

Страница 8: ...ith no deformation and that the connecting multi pole connector is located in the right bottom DRILLING CENTERS BATTERY COMPARTMENT SCREWS SOCKET FASTENING HOLES MULTI POLE CONNECTOR corner To ensure correct operation the socket shall be placed at a height of approximately 1 5 me tres from the floor far from heat sources direct sunlight etc and doors windows Electric connections External probe con...

Страница 9: ...rmostat down to the socket make sure that the multi pole connec tor is engaged correctly Inserting and replacing the batteries Insert two AA batteries 1 5 V into the battery compartment according to the correct polarity the negative pole shall press the metal spring located on the right when viewing the ther mostat from the front Fit the battery top cover back into place A pair of new batteries wi...

Страница 10: ...arameter To modify the current parameter press buttons 1 and 2 To exit the parameter press but ton 3 Once all parameters have been set press button 1 until the END message appears then press button 3 Now the thermostat will save the modified parameters into the internal memory and will automatically exit the param eter menu On the contrary if buttons 1 and 4 are pressed simultaneously when the END...

Страница 11: ...lve ON OFF type used for heat ing both during the heating and the cooling in fact the valve will control both hot water and cold water 2 four tube system the thermostat will drive one valve ON OFF type used for heating plus one additional valve ON OFF type used for cooling depending on the needs of the en vironment P02 External probe 1 not available with this version 2 not available with this vers...

Страница 12: ...justed from 2 0 to 40 0 C It rep resents the lower limit for all the set points Comfort and Economy in the heating mode P09 Winter upper limit set point tem perature It can be adjusted from 2 0 to 40 0 C It rep resents the upper limit for all the set points Comfort and Economy in the heating mode P10 Summer lower limit set point tem perature It can be adjusted from 2 0 to 40 0 C It repre sents the...

Страница 13: ...mperature probe distance 10 m max Reference temperature gradient 4 K h Radio signal features 868 350 MHz 15mW Signal max range in free air 30 m indoors 70 m outdoors Conforming to the directives 2006 95 CE 2004 108 CE 1993 68 CE Complying with the standards R TTE EN 300 220 3 EN 60730 1 EN60730 2 9 ErP classification ErP Class IV 2 EU Reg 811 2013 813 2013 DIN bar CH172DRF actuator Application and...

Страница 14: ...ARNING Prior to carrying out any operation on the unit make sure that you have discon nected the mains connecting cables Operation The unit operating status is indicated by the LED represented by GREEN good RF signal level YELLOW poor RF signal level RED low or poor RF signal level or signal not detected Alternating GREEN RED relay switch on manual mode Alternating GREEN YELLOW RED OFF sig nal sel...

Страница 15: ...esponding red LEDs Below is the switch on sequence 1 accessing the manual mode and valve 1 switch on 2 valve 1 switch on engine speed 1 3 valve 1 switch on engine speed 2 4 valve 1 switch on engine speed 3 5 valve 2 switch on 6 valve 2 switch on engine speed 1 7 valve 2 switch on engine speed 2 8 valve 2 switch on engine speed 3 9 exiting the manual mode Perform a self learning procedure as de scr...

Страница 16: ...IP00 pollution degree 2 Software class A Max temperature T45 Disconnection type 1B micro disconnection Pulse voltage 4000V Type of assem bling DIN bar Dimensions DIN bar 6 module container 106 x 93 x 42 mm Conforms with the directives 2006 95 CE 2004 108 CE 1993 68 CE Complying with the standards EN60730 1 R TTE EN 300 220 3 EN 301 489 3 Fantini Cosmi S p A reserve the right to make any necessary ...

Страница 17: ...y out 2 Insert batteries in the first CH130 3 Start self learning procedure between the CH130 and relevant CH172DRF as per manual instruction 4 Remove batteries from the first CH130 5 Repeat the procedure from 1 to 4 for other kits 6 When all the self learning procedure had been done with all kits insert the batteries in each thermostat and test the heating cooling system ...

Страница 18: ...18 NOTES ...

Страница 19: ... indicates that the product was placed on the market after August 13 2005 By participating in separate collection of products and batteries you will help to assure the proper disposal of products and batteries and thus help to prevent potential negative consequences for the environment and human health For more detailed information about the collection and recycling programmes available in your co...

Страница 20: ...FANTINI COSMI S p A Via dell Osio 6 20090 Caleppio di Settala Milano ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicosmi it EXPORT DEPARTMENT Ph 39 02 95682229 export fantinicosmi it www fantinicosmi com ...