Fantech PLATINUM STAGE Скачать руководство пользователя страница 2

2

TABLE OF CONTENTS

TECHNICAL DATA

HRV-XI 450

............................................................................................. 3

ERV-XI 450

............................................................................................. 5

ERV-WI 500

............................................................................................. 7

OPERATION

Modes Of Operation  ......................................................................................9

Optional Remote Controls ............................................................................. 9

INSTALLATION

.................................................................................................. 10

Mounting the Unit  ....................................................................................... 10

Location & Ducting....................................................................................... 11

Examples

.......................................................................................... 14

Air Flow Balancing ...................................................................................... 16

MAINTENANCE

............................................................................................17

ELECTRICAL CONNECTIONS 

........................................................................ 18

Limited Warranty

• The HRV-XI 450 heat recovery

polypropylene core has a limited
lifetime warranty.

• The ERV-XI 450 energy recovery

enthalpy core has a limited 5 year
warranty.

• The ERV-WI 500 energy recovery

enthalpy wheel has a limited 1 year
warranty.

• The HRV-XI 450 & ERV-XI 450 has a

warranty that is limited to 5 years on
parts and 7 years on the motor & the
ERV-WI 500 has a warranty that is
limited to 1 year on parts and 7 years
on the motors each from the date of
purchase, including parts replaced
during this time period. If there is no
proof of purchase available, the date
associated with the serial number will
be used for the beginning of the
warranty period.

• The motors found in all Fantech

HRV/ERV’s require no lubrication,
and are factory balanced to prevent
vibration and promote silent
operation.

• The limited warranty covers normal

use. It does not apply to any defects,
malfunctions or failures as a result of
improper installation, abuse,
mishandling,  misapplication,
fortuitous occurrence or any other
circumstances outside Fantech’s
control.

• Inappropriate installation or 

maintenance may result in the
cancellation of the warranty.

• Any unauthorized work will result in 

the cancellation of the warranty.

• Fantech is not responsible for any 

incidental or consequential damages
incurred in the use of the ventilation
system.

• Fantech is not responsible for

providing an authorized service
centre near the purchaser or in the
general area.

• Fantech reserves the right to supply

refurbished parts as replacements.

• Transportation, removal and

installation fees are the responsibility
of the purchaser.

• The purchaser is responsible to

adhering to all codes in effect in his
area.

* This warranty is the exclusive and

only warranty in effect relative to the
ventilation system and all other
warranties either expressed or
implied are invalid.

ASHRAE Standard 62-2001 defines acceptable ventilation rates for
various applications.

Outdoor Air Requirements Examples

Application

CFM per Person

L/s per Person

Coin-operated laundry

15

8

Cafeteria, Fast Food

20

10

Bars

30

15

Conference Room

20

10

Reception Area

15

8

Beauty Shop

25

13

Classroom

15

8

Libraries

15

8

Medical

15

8

Photo Studios

15

8

Living Areas 

(residential)

.35 air changes per hour but
not less than 15 cfm (7.5 L/s)
per person

Autopsy Rooms

– (0.5 cfm/Ft

or 2.5 L/s m

2

)

Locker Rooms

– (0.5 cfm/Ft

or 2.5 L/s m

2

)

* Swimming Pools

– (0.5 cfm/Ft

or 2.5 L/s m

2

)

Public Restrooms 

(cfm/wc or cfm/urimac)

50

25

* Call factory for details   1.800.565.548

Содержание PLATINUM STAGE

Страница 1: ...anical equipment i e a forced air furnace or air handler oper ating at a higher static After installation the compatibility of the two pieces of equipment must be confirmed by measuring the airflow s...

Страница 2: ...r circumstances outside Fantech s control Inappropriate installation or maintenance may result in the cancellation of the warranty Any unauthorized work will result in the cancellation of the warranty...

Страница 3: ...mm depth Cores are manufactured using silicone to withstand extreme temperature variations Aluminum cores are optional FILTERS Four 4 Washable Electrostatic Panel Type Air Filters 11 75 298mm x 15 380...

Страница 4: ...58mm 1 9 47mm 22 0 556mm 8 0 202mm 8 0 202mm 0 0 2 0 4 0 6 0 8 1 1 2 1 4 1 6 1 8 2 0 50 100 150 200 250 300 350 400 450 500 0 0 49 8 99 5 149 3 199 0 248 8 298 6 348 3 398 1 447 8 497 6 0 35 71 106 14...

Страница 5: ...lectrically connected with a quick connect for fast and easy inspection of blowers CORES Two 2 modular enthalpic energy recovery cores configured for an efficient cross flow ventilation Each core is 1...

Страница 6: ...1 24 59 94 130 165 201 236 271 Airflow cfm Airflow L s Static Pressure in W C Static Pressure Pa Med High Contact Factory for wiring info Med High High Med Low 0 67 0 69 0 71 0 73 0 75 0 77 0 79 0 81...

Страница 7: ...and threaded rod not supplied or placed on a platform CONTROLS Low voltage 24VAC internal dry contacts to activate unit from off position to high speed see wiring diagram DEFROST A preset 5 minute def...

Страница 8: ...mm 14 355mm 8 203mm 17 67 449mm 5 90 149mm 54 30 1379mm 56 30 1429mm 50 23 1276mm 32 16 817mm 30 40 772mm 18 32 465 4mm 3 24 82mm High Speed Low Speed Airflow L s Airflow cfm Static Pressure Pa Static...

Страница 9: ...perate in continuous exchange mode at a reduce exchange rate Continuous mode is recommended since pollu tants are slowly but constantly being generated in a building NOTE Model ERV WI 500 is a single...

Страница 10: ...the freezing point A P trap should be made in the drain line This will prevent odors from being drawn back up into the unit The drain connection is a 1 2 NPT nipple MOUNTING LOCATION The HRV ERV must...

Страница 11: ...rimeter of the weatherhood must be sealed to prevent leakage into the building The design and size of the weatherhoods or louvers chosen by the installer must allow for adequate free area Water and sn...

Страница 12: ...ductwork Because an HRV ERV is designed to bring fresh air into the building structures may require supply voltage interrupt when smoke or flame sensors are triggered or when a central fire alarm syst...

Страница 13: ...ll 6 152 mm to 12 305 mm from the ceiling Push the Fantech grille MGE metal or PGE plastic into the optional mounting collar or directly into installed elbow INSTALLING DUCTS TO FROM INSIDE CON T PRAC...

Страница 14: ...of duct work number of fittings used in duct work duct heater etc Fully Dedicated System Stale air drawn from areas of contamination Fresh air supplied to main areas HRV ERV must be balanced External...

Страница 15: ...ittings used in duct work duct heater etc SUPPLY IN EXHAUST OUT HRV UNIT RETURN AIR DUCT AIR HANDLER UNIT SUPPLY IN BALANCING DAMPERS SUPPLY IN EXHAUST OUT HRV UNIT SUPPLY DUCT EXHAUST AIR TO HRV UNIT...

Страница 16: ...the other duct The flows should now be balanced Actual airflow can be determined from the gauge reading The value read on the gauge is called the velocity pressure The Pitot tube comes with a chart th...

Страница 17: ...core guide approximately 1 4 6mm followed by the other side c mount the top flange of the core guide into the top channel approximately 1 4 6mm d with all four corners in place and the core straight a...

Страница 18: ...B6 LIVE TB1 White White Red TB4 TB6 Red TB8 TB10 NO TB7 NC NO TB3 COM SUPPLY R2 COM DEFROST R3 NC NO COM R4 TB1 Defrost Timer 1 2 1 5 4 5 3 2 4 5 4 3 1 2 3 2 1 5 4 3 WIRING DIAGRAM ERV XI 450 120 VAC...

Страница 19: ...2 1 1 2 Brown OPTIONAL SPEED CONTROL Blue TB4 SUPPLY MOTOR TB2 TB4 Blue EXHAUST Brown MOTOR Black TB7 TB8 5 4 Black SPEED CONTROL TB10 TB9 OPTIONAL 5 4 WHEEL MOTOR 13 9 12 14 TB5 TB1 TB6 TB3 R1 3 R2...

Страница 20: ...Ontario Western Canada 10 6665 Tomken Road Mississauga Ontario Canada L5T 2C4 T 1 800 407 6195 F 1 800 407 8965 T 1 905 696 9235 F 1 905 696 9236 Qu bec Atlantic Provinces 50 Kanalflakt Way Bouctouch...

Отзывы: