background image

16

PITOT TUBE BALANCING PROCEDURE

PITOT TUBE

BALANCING PROCEDURE

The following is a method of field balancing an HRV/ERV
using a Pitot tube, advantageous in situations when flow
stations are not installed in the ductwork.  Procedure
should be performed with the HRV/ERV on high speed.

The first step is to operate all mechanical systems on high
speed, which have an influence on the ventilation system,
i.e. the HRV/ERV itself and the forced air HVAC system or
air handler if applicable.  This will provide the maximum
pressure that the HRV/ERV will need to overcome, and
allow for a more accurate balance of the unit.

Drill a small hole in the duct (about 3/16"), four feet down-
stream of any elbows or bends, and two feet upstream of
any elbows or bends.  
These are recommended distances but the actual installa-
tion may limit the amount of straight duct.
The Pitot tube should be connected to a magnehelic gauge
or other manometer capable of reading from 0 to 0.25 in (0-
62 Pa) of water, preferably to 3 digits of resolution.  The
tube coming out of the top of the pitot is connected to the
high pressure side of the gauge.  The tube coming out of
the side of the pitot is connected to the low pressure or ref-
erence side of the gauge.

Insert the Pitot tube into the duct; pointing the tip into the
airflow. For general balancing it is sufficient to move the
pitot tube around in the duct and take an average or typ-
ical reading. Repeat this procedure in the other (supply
or return) duct.  Determine which duct has the highest
airflow (highest reading on the gauge).  Then damper
that airflow back to match the lower reading from the
other duct.  The flows should now be balanced.  Actual
airflow can be determined from the gauge reading.  The
value read on the gauge is called the velocity pressure.
The Pitot tube comes with a chart that will give the air
flow velocity based on the velocity pressure indicated by
the gauge.  This velocity will be in either feet per minute
or meters per second.  To determine the actual airflow,
the velocity is multiplied by the cross sectional areas of
the duct being measured.

The accuracy of the air flow reading will be affected by
how close to any elbows or bends the readings are
taken.  Accuracy can be increased by taking an average
of multiple readings as outlined in the literature supplied
with the Pitot tube.

Magnehelic

Magnehelic

Gauge

Duct

Air

Flow

Pitot
Tube

A

The duct’s airflow
velocity is measured
with a magnehelic
gauge and a pitot
tube. See “Pitot Tube
Balancing
Procedure” next
page.

• To avoid airflow

turbulence and
incorrect readings,
the airflow velocity
should be measured
on steel ducting a
minimum of 3 duct
cross-section from
the unit or elbow and
before any transition.

• The balancing procedure consists of measuring the exhaust air leaving the system

and the supply air entering the system and ensuring that these two are equal. A
deviation of 10% or less is acceptable. In such cases, it is recommended to have a
greater amount of exhaust air than supply air as so to increase the supply air’s
temperature.

AIR FLOW BALANCING

PRACTICAL
TIPS

• If the unit’s airflows are

not properly balanced...

- The unit may not operate

at it’s maximum
efficiency.

-  Heat & Energy recovery

core damage may occur.

- The unit’s use could

cause negative or
positive pressure in the
building causing cold air
to enter or other
combustible equipment
to backdraft.

- The unit may not 

defrost properly.

A

*

Pitot tube and gauge

Содержание PLATINUM STAGE

Страница 1: ...anical equipment i e a forced air furnace or air handler oper ating at a higher static After installation the compatibility of the two pieces of equipment must be confirmed by measuring the airflow s...

Страница 2: ...r circumstances outside Fantech s control Inappropriate installation or maintenance may result in the cancellation of the warranty Any unauthorized work will result in the cancellation of the warranty...

Страница 3: ...mm depth Cores are manufactured using silicone to withstand extreme temperature variations Aluminum cores are optional FILTERS Four 4 Washable Electrostatic Panel Type Air Filters 11 75 298mm x 15 380...

Страница 4: ...58mm 1 9 47mm 22 0 556mm 8 0 202mm 8 0 202mm 0 0 2 0 4 0 6 0 8 1 1 2 1 4 1 6 1 8 2 0 50 100 150 200 250 300 350 400 450 500 0 0 49 8 99 5 149 3 199 0 248 8 298 6 348 3 398 1 447 8 497 6 0 35 71 106 14...

Страница 5: ...lectrically connected with a quick connect for fast and easy inspection of blowers CORES Two 2 modular enthalpic energy recovery cores configured for an efficient cross flow ventilation Each core is 1...

Страница 6: ...1 24 59 94 130 165 201 236 271 Airflow cfm Airflow L s Static Pressure in W C Static Pressure Pa Med High Contact Factory for wiring info Med High High Med Low 0 67 0 69 0 71 0 73 0 75 0 77 0 79 0 81...

Страница 7: ...and threaded rod not supplied or placed on a platform CONTROLS Low voltage 24VAC internal dry contacts to activate unit from off position to high speed see wiring diagram DEFROST A preset 5 minute def...

Страница 8: ...mm 14 355mm 8 203mm 17 67 449mm 5 90 149mm 54 30 1379mm 56 30 1429mm 50 23 1276mm 32 16 817mm 30 40 772mm 18 32 465 4mm 3 24 82mm High Speed Low Speed Airflow L s Airflow cfm Static Pressure Pa Static...

Страница 9: ...perate in continuous exchange mode at a reduce exchange rate Continuous mode is recommended since pollu tants are slowly but constantly being generated in a building NOTE Model ERV WI 500 is a single...

Страница 10: ...the freezing point A P trap should be made in the drain line This will prevent odors from being drawn back up into the unit The drain connection is a 1 2 NPT nipple MOUNTING LOCATION The HRV ERV must...

Страница 11: ...rimeter of the weatherhood must be sealed to prevent leakage into the building The design and size of the weatherhoods or louvers chosen by the installer must allow for adequate free area Water and sn...

Страница 12: ...ductwork Because an HRV ERV is designed to bring fresh air into the building structures may require supply voltage interrupt when smoke or flame sensors are triggered or when a central fire alarm syst...

Страница 13: ...ll 6 152 mm to 12 305 mm from the ceiling Push the Fantech grille MGE metal or PGE plastic into the optional mounting collar or directly into installed elbow INSTALLING DUCTS TO FROM INSIDE CON T PRAC...

Страница 14: ...of duct work number of fittings used in duct work duct heater etc Fully Dedicated System Stale air drawn from areas of contamination Fresh air supplied to main areas HRV ERV must be balanced External...

Страница 15: ...ittings used in duct work duct heater etc SUPPLY IN EXHAUST OUT HRV UNIT RETURN AIR DUCT AIR HANDLER UNIT SUPPLY IN BALANCING DAMPERS SUPPLY IN EXHAUST OUT HRV UNIT SUPPLY DUCT EXHAUST AIR TO HRV UNIT...

Страница 16: ...the other duct The flows should now be balanced Actual airflow can be determined from the gauge reading The value read on the gauge is called the velocity pressure The Pitot tube comes with a chart th...

Страница 17: ...core guide approximately 1 4 6mm followed by the other side c mount the top flange of the core guide into the top channel approximately 1 4 6mm d with all four corners in place and the core straight a...

Страница 18: ...B6 LIVE TB1 White White Red TB4 TB6 Red TB8 TB10 NO TB7 NC NO TB3 COM SUPPLY R2 COM DEFROST R3 NC NO COM R4 TB1 Defrost Timer 1 2 1 5 4 5 3 2 4 5 4 3 1 2 3 2 1 5 4 3 WIRING DIAGRAM ERV XI 450 120 VAC...

Страница 19: ...2 1 1 2 Brown OPTIONAL SPEED CONTROL Blue TB4 SUPPLY MOTOR TB2 TB4 Blue EXHAUST Brown MOTOR Black TB7 TB8 5 4 Black SPEED CONTROL TB10 TB9 OPTIONAL 5 4 WHEEL MOTOR 13 9 12 14 TB5 TB1 TB6 TB3 R1 3 R2...

Страница 20: ...Ontario Western Canada 10 6665 Tomken Road Mississauga Ontario Canada L5T 2C4 T 1 800 407 6195 F 1 800 407 8965 T 1 905 696 9235 F 1 905 696 9236 Qu bec Atlantic Provinces 50 Kanalflakt Way Bouctouch...

Отзывы: