Rev. 32
71/114
1.14. Damped oscillatory magnetic
fields
IEC 61000-4-10
Level 5, Field strenght 100 A/m, Frequency
100KHz and 1MHz, Repetition frequency 40
trans./s at 100KHz, 400 trans/s at 1MHz,
Duration of each application 3s.
1.15. Ring wave immunity test
IEC 61000-4-12
Level 4, Line to earth for all terminals ±4kV.
Line to Line for all terminals excepts
Communication port ±2kV
2. Product safety requirements
(including
thermal
short
time
rating)
2.1. Impulse voltage
IEC 60255-27
IEC 60255-5
Each group to earth and with rest of the groups
in short-circuit ±5kV. Differential mode for each
one of the groups ±1kV
2.2. AC or DC dielectric voltage
IEC 60255-27
IEC 60255-5
Each group to earth and with rest of the groups
in short-circuit 2kVac, 50Hz, 1 minute
2.3. Insulation resistance
IEC 60255-27
IEC 60255-5
500V applied between each group to earth and
with rest of the groups in short-circuit
2.4. Protective bonding resistance
IEC 60255-27
Test current 2xIn, Test voltage 12Vac during
60s. Resistance shall be less than 0.1 ohm
3. Burden
3.1. AC burden for CT
IEC 60255-1
Declared on manual
3.2. AC burden for VT
3.3. AC, DC burden for power
supply
3.4. AC, DC burden for binary
inputs
4. Contact performance
IEC 60255-27
5. Communication requirements
ModBus RTU
IEC 61850
IEC 60870-5-103
IEC 60870-5-104
DNP 3.0
6.
Climatic
environmental
requirements
IEC 60255-27
6.1. Cold
IEC 60068-2-1
Cold Operation Ab, -25ºC, 72h
Cold transport & Storage Ad, -40ºC, 72h
6.2 Dry heat
IEC 60068-2-2
Dry Heat Operation Bb, +70ºC, 72h
Dry Heat transport & Storage Bd, +85ºC, 72h
6.3 Change of temperature
IEC 60068-2-14
Change of Temperature Nb, Upper temp
+70ºC, Lower temp -25ºC, 5 cycles, Exposure
time 3h, Transfer time 2 min.
Содержание SIA-B
Страница 9: ...www fanox com Rev 32 9 114 The dimensions are in mm Cut out pattern ...
Страница 11: ...www fanox com Rev 32 11 114 Cut out pattern 2 3 Striker dimensions 2 3 1 PRT 15 ...
Страница 12: ...www fanox com Rev 32 12 114 2 3 2 PRT A 44 5 B 49 5 C 56 5 D 64 5 E 42 5 ...
Страница 19: ...www fanox com Rev 32 19 114 3 3 Functional Diagram ...
Страница 24: ...www fanox com Rev 32 24 114 Dimensions ...
Страница 27: ...www fanox com Rev 32 27 114 Dimensions Model CT16 5 Model CT08 5 ...
Страница 42: ...www fanox com Rev 32 42 114 ...
Страница 43: ...www fanox com Rev 32 43 114 ...
Страница 44: ...www fanox com Rev 32 44 114 ...
Страница 45: ...www fanox com Rev 32 45 114 ...
Страница 47: ...www fanox com Rev 32 47 114 ...
Страница 48: ...www fanox com Rev 32 48 114 ...
Страница 49: ...www fanox com Rev 32 49 114 ...
Страница 101: ...www fanox com Rev 32 101 114 Trip Voltage Level 17 Vdc C Nominal current 8 C CT type CT008 ...
Страница 113: ...www fanox com Rev 32 113 114 NOTES ...
Страница 114: ...www fanox com Rev 32 114 114 ...