Rev. 32
33/114
Taped specific CTs
In the case of SIA-B, the necessary current to perform the testing is provided through the no
conventional current transformers. These CTs have a pass-through hole (from P1 to P2 in the picture
blow) for primary current measurement, 2 terminals (S1 and S2 in the picture below) for secondary
current measurement and power supply for the relay and 2 terminals (C and D in the picture below) to
perform the testing:
Example with a current injector:
The testing consists on the injection of 1A in these last terminals providing a simulated primary current
value. These primary values depend on the CT type:
CURRENT
TRANSFORMER
Injected
Current
Primary Current
CT16
1 A
50 A
The correct measurement of these values in the relay guarantees that the whole current range will be
measured.
Содержание SIA-B
Страница 9: ...www fanox com Rev 32 9 114 The dimensions are in mm Cut out pattern ...
Страница 11: ...www fanox com Rev 32 11 114 Cut out pattern 2 3 Striker dimensions 2 3 1 PRT 15 ...
Страница 12: ...www fanox com Rev 32 12 114 2 3 2 PRT A 44 5 B 49 5 C 56 5 D 64 5 E 42 5 ...
Страница 19: ...www fanox com Rev 32 19 114 3 3 Functional Diagram ...
Страница 24: ...www fanox com Rev 32 24 114 Dimensions ...
Страница 27: ...www fanox com Rev 32 27 114 Dimensions Model CT16 5 Model CT08 5 ...
Страница 42: ...www fanox com Rev 32 42 114 ...
Страница 43: ...www fanox com Rev 32 43 114 ...
Страница 44: ...www fanox com Rev 32 44 114 ...
Страница 45: ...www fanox com Rev 32 45 114 ...
Страница 47: ...www fanox com Rev 32 47 114 ...
Страница 48: ...www fanox com Rev 32 48 114 ...
Страница 49: ...www fanox com Rev 32 49 114 ...
Страница 101: ...www fanox com Rev 32 101 114 Trip Voltage Level 17 Vdc C Nominal current 8 C CT type CT008 ...
Страница 113: ...www fanox com Rev 32 113 114 NOTES ...
Страница 114: ...www fanox com Rev 32 114 114 ...