EMM-7 

instruction manual 

IM442-EU-F v0.4 

pag. 7  

Programming of the address for the communication network (

SET ID ADR

) (only for vers. with serial output)

After the confirm with the 

A

 key of the previous value, the message 

ID aDR

 will appear on

F

 display; to set the value 

that will identify the instrument when it will be connected in a EIA485 communication network, proceed with the 
modality, already described. The settable values are from 1 to 247. To confirm, press the 

A

 key. 

Programming of the baud rate (

SET BDR

) (only for vers. with serial output)

The following setting is the baud rate. The message

SET

appears on

G

display, the message

SET BDR

on the first

two parts of

F

display to indicate the programming of the baud rate displayed on the third part (L3) o

f

 the

F

display. To

modify the value set, it’s necessary to use the

C

key to decrease and

B

to increase the rate. The values settable are:

-

19.2

 => 19200 

baud 

-

9.60

 => 9600 

baud 

-

4.80

 => 4800 

baud 

-

2.40

 => 2400 

baud 

Press 

A

 to confirm the value displayed. 

Programming of the serial parameters (only for vers. with serial output)

On

G

 display will appear the message 

SET

. The following message will appear on 

F

 display using the 

B

 and 

C

 keys. 

To confirm press the 

A

 key. 

8  1

 

8 data bit / 1 stop bit

PAR

No parity

NO

8  2

 

8 data bit / 2 stop bit  

PAR

No parity 

NO

8  1

 

8 data bit / 1 stop bit

PAR

Even parity 

EVE

8  1

 

8 data bit / 1 stop bit 

PAR

Odd parity 

ODD

Programming of the Password (

SET PAS

)

The instrument is supplied without password. When a password (from 0002 to 9999) is set, using the 

B

 (to increase), 

C

 (to decrease) and 

A

 (to confirm) keys, only who know this value can to enter in the setup. The password, in fact, is 

required all the time that someone try to enter in the setup (pressing the 

A

 and 

B

 key at the same time). If the 

password is wrong, the message 

PASS ERR

 will appear on 

F

 display and the instrument go back to the measures 

visualization. To input the password, when required by the instrument, at the enter of the setup, use the 

A

,

B

 and 

C

keys as the same way done previously. 

The menu is cyclic. After the last setting, the instrument go back to the first page of Setup (SETUP). It’s always 
possible to come back to measures visualization mode pressing at the same time the 

A

 and 

C

 keys.

PEAK VALUES AND ENERGY COUNTERS RESET (

RESET

)

From the measures visualization mode, pressing the 

A

 and 

C

 keys simultaneously the message 

SETUP

 will appear 

on

F

 display, press the key 

C

 until the message 

RESET

 appears on the same display. To accede to the menu, press 

the

A

 key. Now it’s possible to select the enabling of cancellation type, by pressing the 

C

 key, according with following 

types: 

RESET PEA

: all maximum value will be delete. 

RESET AVG

: all average and average maximum value (maximum demand) will be delete. 

RESET EN

: with 

NORMAL

 as energy mode (

EN

) the total energy counters will be delete, with 

TOT  PAR

 the 

partial energy counters will be delete (as when the digital input is closed) and with 

TB1 TB2

 the band 

counters will be delete. 

RESET ALL

:  to delete average maximum values and energy counters. 

Entry to menu: 

seT UP

Æ

seT Up
RESET
SET DO1 
SET DO2 
SET AN OUT 
SET HR_ 
--- OFF OFF

  

(the visualization depends on the settings and the I/O status)

RESET PEA 

NO

 / 

YES

Confirm Reset

Deleting maximum values (max) 

RESET AVG 

NO

 / 

YES

Confirm Reset

Deleting average values (avg) 
and maximum demand (maxD) 

RESET EN 

NO

 / 

YES

Confirm Reset

Deleting energy counters 

RESET ALL 

NO

 / 

YES

Confirm Reset

Deleting maximum and average 
values, and energy counters 

To enable the chosen type, press the 

B

 key to change the indication on display 

G

 from 

NO

 to 

yes

.

Confirm enabling cancellation, by pressing the 

A

 key. The indication on display 

G

 change from 

yes

 to 

---

.

www.fanox.com

[email protected]

Tel: 0034 94 471 14 09

Fax: 0034 94 471 05 92

Pag 7

Содержание EMM-7

Страница 1: ...tion digital output serial output RS485 insulated current inputs neutral current input digital input alternative to analog Output option MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N 6 V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 6 V L L phase and three phase currents A kA A L1...

Страница 2: ...0 60Hz 1 3 20 60Vac 24 72Vdc 1 3 85 230Vac 90 250Vdc It s possible for example to take the auxiliary power supply between phase and neutral in a 4 wires system or phase phase in a 3 wires system without neutral or from a VT in a medium voltage application measure voltage inputs 4 terminals are available for the connection to the 3 phase and neutral of the network of measure the maximum voltage pha...

Страница 3: ...ires without neutral or with neutral not supplied the N terminaln must not be connected INSERTION ON THREE PHASE LINE WITH 4 WIRES EMM EMM imeasure voltage inputs Voltage insertion with 3 VT N L1 L2 L3 VL1 VL2 VL3 N P1 P2 S1 S2 S2 S1 In EMM with internalCT with Ineutral option CT connection to read the neutral current Digital Outputs DO1 output if used as PULSE is linked to the ACTIVE ENERGY count...

Страница 4: ...energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x 1000 Using the C key the display indicates the type of the energy displayed Using the A and B keys the disp...

Страница 5: ...output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with serial output seT ID ADR Increase Set address of network from 001 to 247 Decrease seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 48...

Страница 6: ...ing of the average time seT AVG T After the programming phase previously described pressing another time the A key on the F display will appear the message AVG T and the average time settable from 1 to 30 minutes To increase the value press the B key To decrease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximu...

Страница 7: ...is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page of Setup SETUP It s always possible to come back to measures visualiza...

Страница 8: ...ital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the minimum threshold set ALR LO The activation of the alarm output will come after some seconds of delay set ALR DL In the REMOTE mode the output status will be decided from the status of the corr...

Страница 9: ...OLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with low threshold value The B to increase and C to decrease keys are used to set the high and the low thresholds values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is ...

Страница 10: ...ll appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will appear the parameter to link to the analog output and selectable pressing more time the B key Pressing the A key to confirm the parameter selected SET THE HIGH AND THE LOW THRESHOLD Now it s necessary to set the end scale value high limit ...

Страница 11: ...part L1 the status of digital input on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output DO2 The visualization of the digital input status activated that is supplied and deactivated that is not supplied depends of the type of energy visualization NORMAL TOT PAR e TB1 TB2 With NORMAL the digital input will be indicated with ON...

Страница 12: ... of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in correspondence of the kWh and KVArh on the front panel turn on to indicate the visualization of the active and reactive energy counters The led...

Страница 13: ... max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg 6 W max avg 6 VAr max avg 6 VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg I N avg phase and neutral currents average phase and neutral currents max maxD avg 6 W avg 6 Var avg 6 VA avg three pha...

Страница 14: ...the manual of EMI1 serial converter EIA485 INTERFACE COMUNICATION RS485 It is possible to exchange information between the instrument and a PC PLC or other compatible system through the asynchronous serial line RS485 The interface EIA485 allows a multi drop connection in order to connect various instruments in the same network The maximum suggested length for a RS485 connection is 1200m For longer...

Страница 15: ...instruction manual IM442 EU F v0 4 pag 15 DIMENSIONS 96 96 81 14 9 90 92 92 R3 cut out panel flush mounting for panel DIN 43700 www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 15 ...

Страница 16: ...with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse Pulse duration 100 200 300 400 500 milliseconds selectable DO1 active energy pulse output accumulated Tb1 Tb2 DO2 reactive energy pulse output accumulated Tb1 Tb2 digital Input Changing time band function or reset partial counters Opto isolated input Insulation 2500 V...

Отзывы: