VISUALIZATION PEAK AND AVERAGE VALUES

Pressing at the same time the 

A

 and 

B

 keys, on 

F

 display will appear the 

average and maximum stored value, that are selected using the 

B

 key while 

a luminous segment on the 

G

 display indicates the type of the maximum 

and/or average value. 

AVG

: the average values are calculated on a average time set. The 

calculation is at fixed window and it’s sinchronized when the instrument turn 
on.

The stored maximum values are the two types: 

MAX

: the instantaneous maximum values store the maximum value 

achieved by the parameter of measure for at least one second. 

MAX AVG

: the average maximum values (maximum demand) store the 

maximum value achieved in the average time as set in the setup menu; 

The integration for the calculating of the average values is synchronized all the time that the instrument turn on. 
Press 

A

 and 

B

 keys another time to come back to the measures visualization. The instrument will come back to the 

measure visualization automatically if for 10 seconds no one button is pressed. 
The average value, the maximum value and the maximum average value selectable with 

B

 key are the following: 

parameter 

Identifications / description 

G display 

V

L1-N max

 V 

L2-N max

 V 

L3-N max

phase voltages 

maximum instantaneous phase voltages 

max

maxD

avg

I

L1 max

 I 

L2 max

 I 

L3 max

 I 

N max

phase and neutral currents 

maximum instantaneous phase currents 

max

maxD

avg

6

 W 

max

6

 VAr 

max

6

 VA 

max

three-phase power 

maximum three phase powers (

6

max

maxD

avg

I

L1 max avg

 I 

L2 max avg

 I 

L3 max avg

 I 

N max avg

phase and neutral currents 

maximum of average phase and neutral currents (max. demand) 

max

maxD

avg

6

 W 

max avg

6

 VAr 

max avg

6

 VA 

max avg

three-phase power 

maximum of average three phase powers (maximum demand)

max

maxD

avg

I

L1 avg

 I 

L2 avg

 I 

L3 avg

 I 

N avg

phase and neutral currents 

average phase and neutral currents 

max

maxD

avg

6

 W 

avg

6

 Var 

avg

6

 VA 

avg

three-phase power 

average three phase powers

max

maxD

avg

NOTE relative to the measure 

The refresh time of the display is lower of a second and it depends by the time of calculating of the measure and concerning the
methodology of measure used in the way to allow a comfortable reading of value also in presence of fast variation of the measure
parameter.
If the multimeters are used on single phase lines, the measures are referred at the phase L3. The other data displayed and relative
to the three-phase system must not considered. 
If the measure indicated by the instrument are not reliable or absurd it’s necessary to verify the connection of the measure inputs of 
currents and voltages because must be respected the sequence of the phase, the corresponding of the currents and voltages of the
same phase (the L1 voltage phase and the TA located on L1 phase must be connected on the L1 input) and the sense of the 
current (the S1 terminals of the TA must be connected at the S1 terminals of the instrument). 
In some application where the secondary is connected to other instruments apart from the EMM multimeter, some problems could 
happen concerning the typology of the amperometric inputs. 
If there are some problem call the assistance service. 

B

C

D

E

F

A

G

246
285
277

-

www.fanox.com

[email protected]

Tel: 0034 94 471 14 09

Fax: 0034 94 471 05 92

Pag 13

Содержание EMM-7

Страница 1: ...tion digital output serial output RS485 insulated current inputs neutral current input digital input alternative to analog Output option MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N 6 V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 6 V L L phase and three phase currents A kA A L1...

Страница 2: ...0 60Hz 1 3 20 60Vac 24 72Vdc 1 3 85 230Vac 90 250Vdc It s possible for example to take the auxiliary power supply between phase and neutral in a 4 wires system or phase phase in a 3 wires system without neutral or from a VT in a medium voltage application measure voltage inputs 4 terminals are available for the connection to the 3 phase and neutral of the network of measure the maximum voltage pha...

Страница 3: ...ires without neutral or with neutral not supplied the N terminaln must not be connected INSERTION ON THREE PHASE LINE WITH 4 WIRES EMM EMM imeasure voltage inputs Voltage insertion with 3 VT N L1 L2 L3 VL1 VL2 VL3 N P1 P2 S1 S2 S2 S1 In EMM with internalCT with Ineutral option CT connection to read the neutral current Digital Outputs DO1 output if used as PULSE is linked to the ACTIVE ENERGY count...

Страница 4: ...energy counters Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x 1000 Using the C key the display indicates the type of the energy displayed Using the A and B keys the disp...

Страница 5: ...output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with serial output seT ID ADR Increase Set address of network from 001 to 247 Decrease seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 48...

Страница 6: ...ing of the average time seT AVG T After the programming phase previously described pressing another time the A key on the F display will appear the message AVG T and the average time settable from 1 to 30 minutes To increase the value press the B key To decrease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximu...

Страница 7: ...is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page of Setup SETUP It s always possible to come back to measures visualiza...

Страница 8: ...ital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the minimum threshold set ALR LO The activation of the alarm output will come after some seconds of delay set ALR DL In the REMOTE mode the output status will be decided from the status of the corr...

Страница 9: ...OLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with low threshold value The B to increase and C to decrease keys are used to set the high and the low thresholds values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is ...

Страница 10: ...ll appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will appear the parameter to link to the analog output and selectable pressing more time the B key Pressing the A key to confirm the parameter selected SET THE HIGH AND THE LOW THRESHOLD Now it s necessary to set the end scale value high limit ...

Страница 11: ...part L1 the status of digital input on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output DO2 The visualization of the digital input status activated that is supplied and deactivated that is not supplied depends of the type of energy visualization NORMAL TOT PAR e TB1 TB2 With NORMAL the digital input will be indicated with ON...

Страница 12: ... of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in correspondence of the kWh and KVArh on the front panel turn on to indicate the visualization of the active and reactive energy counters The led...

Страница 13: ... max avg I L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg 6 W max avg 6 VAr max avg 6 VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg I N avg phase and neutral currents average phase and neutral currents max maxD avg 6 W avg 6 Var avg 6 VA avg three pha...

Страница 14: ...the manual of EMI1 serial converter EIA485 INTERFACE COMUNICATION RS485 It is possible to exchange information between the instrument and a PC PLC or other compatible system through the asynchronous serial line RS485 The interface EIA485 allows a multi drop connection in order to connect various instruments in the same network The maximum suggested length for a RS485 connection is 1200m For longer...

Страница 15: ...instruction manual IM442 EU F v0 4 pag 15 DIMENSIONS 96 96 81 14 9 90 92 92 R3 cut out panel flush mounting for panel DIN 43700 www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 15 ...

Страница 16: ...with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse Pulse duration 100 200 300 400 500 milliseconds selectable DO1 active energy pulse output accumulated Tb1 Tb2 DO2 reactive energy pulse output accumulated Tb1 Tb2 digital Input Changing time band function or reset partial counters Opto isolated input Insulation 2500 V...

Отзывы: