LE-03MB - User manual
38
9.10. Read demand interval,slide time, display time, LED time
Start
L field
L field Start C field A field CI field
DIF
VIF
Check sum
Stop
68H
05
05
68H 53/73
FE
51
30
81
CS
16
Example:
(Meter address is 01)
Master to Slave:
68 05 05 68 53 FE 51 30 81 53 16
Slave to Master:
E5
Bytes
Parameters
Data structure
Notice
4
Header telegram
68 16 16 68
Header telegram RSP_UD
3
08 A 72
C field =08 address A CI field72
4
78 65 34 21
Identification number =12345678
2
24 40
Manufacturer ID 4024
1
01
Generation 1
1
02
Energy meter
1
55
ACCESS NO
1
00
STATUS
2
00 00
Signature
7
Demand interval,
slide time,
display time, LED time
0A
DIF: 30 digit BCD
FD
VIF: FD
3A
VIFE: dimensionless / no VIF
15010610
Demand interval: 15 min.
Slide time: 01 min.
Display time: 06 sec
LED time: 10 sec
1
CHECK SUM
CS
1
End
16