LE-03MB - User manual
32
9.6. Read out of instantaneous electrical information
The instantaneous electrical information includes:
V, I, P, Q, S, PF, Hz ect. MD
9.6.1. How to read instantaneous electrical information by using primary address
Start L field L field Start C field
A field
CI field
Check sum
Stop
68H
3
3
68
53/73
XX
B1
CS
16
Master to Slave:
68 03 03 68 53
XX
B1 05 16
Slave to Master:
Variable data structure (instantaneous electrical information)
If the primary address is 01, then XX=01
9.6.2. How to use secondary address to read out the instantaneous electrical information
Step 1
Initialization Slave
Master to Slave:
10 40 FF 3F 16
Slave to Master:
No answer
Step 2
Check the secondary address. After receiving the command, the slave will check if the secondary address in
the command is same with its secondary address or not.
Master to Slave:
68 0B 0B 68 73 FD 52 78 56 34 12 FF FF FF FF D2 16
Slave to Master:
E5
Step 3
Use Secondary Address to read out the instantaneous electrical information
Master to Slave:
68 03 03 68 53
FD
B1 01 16
Slave to Master:
Variable data structure