- 8 -
Communication parameters
Protocol
Modbus RTU
Operation mode
Slave
Port settings
Baud rate: 9600 bps
Parity: NONE
Stop bits: 1
Modbus address
(factory settings)
1÷245
Measurement registers
address
description
com-
mand
type
atr
0
Active energy (R0)
03
int
R
1
Active energy (R1)
03
int
R
2
Active energy (R2)
03
int
R
6
Meter address
06
int
W
Legend:
R – read, W – write.
Modbus RTU protocol parameters