- 1 -

LE-03d CT400

Electric energy meter, 

3-phase

The LE-03d CT400 is a static (electronic) calibrated electricity 

meter of three-phase alternating current in a semidirect system.

The meter is designed to work with current transformers with 

a primary current of 400 A and a secondary current of 5 A. The 

maximum measured current of the system is determined by the 

value of the primary current of the current transformer used. 

When using transformers with dedicated parameters, the meter 

shows the actual value of electricity consumed by the system.

A special electronic system under the influence of flowing cu-

rrent and applied voltage in each phase generates pulses pro-

portional to the energy drawn in the respective phase. Energy 

consumption in the phase is indicated by a flashing of corre-

sponding LED (L1, L2, L3). The sum of the three phase pulses is 

indicated by a flashing LED and converted into energy absorbed 

throughout the three-phase system. Its value is displayed by the 

segment LCD display.

Purpose

Functioning

F&F Filipowski sp. j.

Konstantynowska 79/81, 95-200 Pabianice, POLAND

phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71

www.fif.com.pl; e-mail: [email protected]

Do not dispose of this device in the trash along with other waste! 

According to the Law on Waste, electro coming from households free of charge and can 

give any amount to up to that end point of collec� on, as well as to store the occasion of 

the purchase of new equipment (in accordance with the principle of old-for-new, regard-

less of brand). Electro thrown in the trash or abandoned in nature, pose a threat to the 

environment and human health.

Содержание LE-03d CT400

Страница 1: ...n in the respective phase Energy consumption in the phase is indicated by a flashing of corre sponding LED L1 L2 L3 The sum of the three phase pulses is indicated by a flashing LED and converted into energy absorbed throughout the three phase system Its value is displayed by the segment LCD display Purpose Functioning F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 4...

Страница 2: ...ou to connect another pulse device SO that reads pulses generated by the meter No additional connected equipment is required for proper ope ration of the meter The meter has sealable input and output terminal covers to pre vent any attempts to bypass the meter Pulse output Sealing ...

Страница 3: ... 3 The meter is marked with individual serial number allowing its unambiguous identification The marking is laser engraved and cannot be removed Meter number Front description ...

Страница 4: ...conductors and con nect the secondary outputs to the terminals in accordance with the markings 1 2 L1 3 4 L2 5 6 L3 5 N wire connect to terminal 15 6 In order to increase the safety of the system and the measu rement accuracy it is recommended to ground the terminals S2 of the secondary side of current transformers 7 Additional pulse receiver connected optional to terminals 9 i 8 Additional pulse ...

Страница 5: ... 5 Current measurement circuits 1 2 L1 phase 3 4 L2 phase 5 6 L3 phase Pulse output open collector 8 transistor emitter 9 transistor collector cont on next page Schemat podłączenia ...

Страница 6: ...ansformer type 400 5 A measurement accuracy IEC62052 11 IEC62053 21 1 rated frequency 50 Hz insulation protection class II own power consumption 10 VA 2 W indication range 0 9999999 kWh constant 300 pulses kWh current consumption signalling 3 red LED read out signalling red LED pulse output type open collector maximum voltage 27 V DC maximum current 27 mA pulse constant 300 pulses kWh pulse time 3...

Страница 7: ...dealer or contact us directly F F Filipowski sp j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which conformity is declared can be found www fif com pl on the product subpag...

Страница 8: ...ervoltage circuit breakers Before connecting the power supply make sure that all cables are connected correctly It is essential to observe the operating conditions of the meter supply voltage humidity temperature To avoid electric shock or damage to the meter turn off the power supply whenever the connection is changed Do not make any changes to the unit yourself Doing so can re sult in damage to ...

Отзывы: