domestic and industrial automation
LE-01MR v.2 – User manual v.1.0.0
19
meter configuration through the
panel on the front of the meter.
16
Auxiliary energy meter
reset
0x2002 8194 R/W
1
Value Operation
0x2000
Active energy meter re-
set
0x4000
Reactive energy meter
reset
0x6000
Active and reactive en-
ergy meter reset
17
Power demand meters
reset
0x2003 8195 R/W
1
To reset the selected power de-
mand value, enter one of the fol-
lowing values into the register
Value Operation
0xA501
Demand for active
power
0xA502
Demand for reactive
power
0xA504
Maximum active
power demand
0xA508
Maximum reactive
power demand