LE-01MR v.2 – User manual v.1.0.0
18
2
Energy returned (ex-
port)
3
Export
4
Import- Export
12
Calculating power de-
mand
0x1010 4112 R/W
1
Value Operation
0
Power demand is cal-
culated on the basis of
successive, full time in-
tervals
1
Power demand calcu-
lated on the basis of
the moving average
over a given period of
time
13
The period of calculat-
ing power demand
0x1011 4113 R/W
1
Value in minutes. Setting range
from 1 to 30 minutes.
14
Configuration of the
measured values indi-
cated on the display
0x1012 4114 R/W
4
Parameter that allows you to limit
the number of measured values
visible on the LCD.
Each parameter corresponds (in
order as shown in the LCD descrip-
tion table) to one bit of that param-
eter. Bit set to 1 means the meas-
urement is visible on the LCD, bit
set to 0 means the parameter is not
visible.
Note
: the data is stored in the two
upper registers (0x1014-0x1015).
Note
: If the entire parameter is re-
set, no values will be displayed on
the meter screen.
15 PIN
0x1016 4118 R/W
1
The PIN code restricts access to the