domestic and industrial automation
LE-01MR v.2 – User manual v.1.0.0
13
8 Resetting the maximum active
power consumption indicator
The registered value of the maximum active power demand
appears on the display as
P
Press and hold down the button on the front of the meter to
reset the indication.
9 Setting the display time of a pa-
rameter
Lcd xx, where xx is the time after which the meter view will
automatically switch to display the next parameter. Setting
range 0 – 99 Seconds. A value of 0 stops automatic switching.
10 Setting the period for power de-
mand calculation
Length of time interval (in minutes) from which the value of
power demand will be calculated.
The parameter is set in the range from 1 to 30 minutes, the
default value is 15 minutes.
11 Calculation of total energy con-
sumption
A parameter that determines how the total energy consump-
tion reading is obtained:
Value Operation
1
Total energy = Import (energy imported)
2
Total energy = Export (energy exported)
3
Total energy = Export
4
Total energy = Import - Export
The default value is 3.
12 Setting up the PIN number
You can set your own code to secure access to the meter con-
figuration.
The PIN code restricts access to the meter
configuration through the meter control
panel. Access via the RS-485 communica-
tion port is not blocked.